웨이블렛 변환을 이용한 직렬 아크고장 신호 분석 (Analysis of Series Arc-Fault Signals Using Wavelet Transform)

  • 방선배;박종연
    • 전기학회논문지
    • /
    • 제57권3호
    • /
    • pp.494-500
    • /
    • 2008
  • This paper presents the analyzed result of the series arc fault current by using the discrete wavelet transform. The series arcing is caused by a loose connection in series with the load circuit. The series arc current is limited to a moderate value by the resistance of the device connected to the circuit, such as an appliance or a lighting system. The amount of energy in the sparks from the series arcing is less than in the case of parallel arcing but only a few amps are enough to be a fire hazard. Therefore, it is hard to detect the distinctive difference between a normal current and a intermittent arc current. This paper, presents the variation of the ratio of peak values and RMS values of the series arc fault current, and proposes the novel series arc fault detecting method by using the discrete wavelet transform. Loads such as a CFL lamp, a vacuum cleaner, a personal computer, and a television, which has the very similar normal current with the arc current, were selected to confirm the novel method.

형광등용 안정기의 화재원인 판정에 관한 연구 (A Study on the Judgment of Fire Cause of Ballast for Fluorescent Lamp)

  • 최충석;백동현
    • 한국화재소방학회논문지
    • /
    • 제14권3호
    • /
    • pp.1-5
    • /
    • 2000
  • 본 연구에서는 옥내 조명으로 널리 사용되고 있는 형광등용 안정기의 화재위험성을 분석하였다. 안정기권선을 실체현미경으로 분석한 결과 용융흔을 다수 발견할 수 있었으나, 육안으로 원인 판정은 불가하였다. $700^{\circ}C$ 이상에서 열열화된 안정기 권선은 연신구조(elongation structure)가 없어지고 구리입자의 확대된 형태만 보였다. 단락 권선의 금속현미경 분석에서 경계면을 중심으로 주상조직 및 보이드 성장의 규칙성이 확인된 것으로 보아 전기적인 단락이 층간에 일어났음이 증명되었다. SEM을 이용한 미세구조 분석에서 용융된 부분이 확인되었다. EDX를 이용한 스펙트라 분석에서 Cu의 구성요소인 CuL 및 CuK liness 뿐만 아니라 OK line이 고르게 관측되고 있다. 이것은 재결합 과정에서 산소가 반응에 참여했음을 의미한다.

  • PDF

저압분전반에서 접지 경로를 통한 차단기의 트래킹 화재위험성에 관한 연구 (A study on the Fire Hazard for the Tracking of RCD through Ground Path at Low Voltage Cabinet Panel)

  • 김동욱;이기연;김동우;길형준;김향곤;정영식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 춘계학술대회 논문집
    • /
    • pp.349-352
    • /
    • 2008
  • The electrical accidents result from insulation blackdown due to over voltage and overheating due to the excess of allowable current, deterioration of insulation performance due to the passage of time, and so on. In this paper, the insulating characteristics of phenolic resin using insulating materials for low voltage were analyzed and the tracking test was performed according to IEC Publ. 112.

  • PDF

전기차용 고전압 케이블의 화재 위험성에 관한 연구 (A Study on the Fire Risk of High-voltage Cables for Electrical Vehicles)

  • 강신동;박예진;김시현;김재호
    • 한국안전학회지
    • /
    • 제38권4호
    • /
    • pp.8-14
    • /
    • 2023
  • This study presents the characteristics of short circuits (SCs) caused by excessive currents in high-voltage cables used in electric vehicles and emphasizes the need to calculate the cross-sectional areas of these cables according to the SC current. Three direct current power supplies were connected in parallel to test the SC characteristics caused by excessive currents, and a timer and a magnetic contactor were used to deliver the conduction time and SC current. A circular infrared-radiation heater was used to test the temperature-dependent SC characteristics, a thermocouple was used to measure the temperature, and a shunt resistor was used to measure the current. As the SC current increased, the fusing time of the cable decreased. Additionally, a high-voltage cable (with an area of 16 mm2 ) used in electric vehicles fused when a current (approximately equal to 55 times the allowable current) flowed for 0.2 s (operating time of the protective device). When the SC current is 10 kA, the cable may fuse during the operating time of the protective device, thus creating a fire hazard. In electric vehicles, the size of the SC current increases in proportion to the capacity of the battery. Thus, the cross-sectional areas of the cables used should be calculated accordingly, and cable operations should be properly coordinated with the surrounding protective devices.

반복 피로에 의한 전원 코드의 화재위험성 (The Fire hazard of the wire due to repetition stress)

  • 김동욱;길형준;김향곤;최충석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.60-62
    • /
    • 2006
  • 전원 코드에서의 전기재해는 외부의 기계적피로에 의해 피복이나 피복 내부의 도체가 손상되어 이루어지는 경우가 많다. 특히, 전기청소기, 모발건조기 등 이동용 전기제품에서 잦은 반복 스트레스로 인해 전원 코드에서 반단선에 의한 전기화재가 발생한다. 본 연구에서는 전원 코드에 반복 스트레스를 받았을 때 전선의 소선이 손상되는 과정을 X-ray를 이용하여 소손 패턴을 분석하였으며, 반단선에 의한 불꽃 발생과정을 초고속 카메라로 촬영하였다. 또한 소손된 전원 코드를 실체 현미경 및 금속현미경을 이용하여 전선피복과 도체에 나타나는 특징을 분석하였다. 이러한 연구를 통하여 전원코드의 반복 피로에 의한 화재발생 메커니즘과 화재원인 분석에 유용한 자료가 될 것으로 기대된다.

  • PDF

Wavelet 변환을 이용한 고저항 지락고장 검출 (High Impedance Fault Detection using Wavelet Transform)

  • 김현;김철환
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제48권12호
    • /
    • pp.1492-1497
    • /
    • 1999
  • High impedance fault(HIF) is defined as fault the general overcurrent relay can not detect or interrupt. Especially when HIF occur in residential areas, energized high voltage conductor results in fire hazard, equipment damage or personal threat. This paper proposes the model of the high impedance fault in transmission line using the ZnO arrester and resistance to be implemented within EMTP. The performance of the proposed model is tested on a typical 154[kV] korean transmission line system under various fault conditions. Wavelet transform is efficient and useful for the detection of high impedance fault in power system, because it uses variable windows according to frequency. In this paper, HIF detection method using wavelet transform can distinguish HIF form similar fault like arcfurance load, capacitor bank switching and line switching.

  • PDF

Wavelet 변환을 이용한 고저항 지락사고 고장점 추정 (Fault Location Estimation for High Impedance Fault using Wavelet Transform)

  • 김현;김철환
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권8호
    • /
    • pp.369-373
    • /
    • 2000
  • High impedance fault(HIF) is defined as a fault that the general overcurrent relay can not detect or interrupt. Especially when HIF occurs in residential areas, energized high voltage conductor results in fire hazard, equipment damage or personal threat. This paper proposes a fault location estimation algorithm for high impedance fault using wavelet transform. The algorithm is based on the wavelet analysis of the fault voltage and current signals. The performance of the proposed algorithm is tested on a typical 154kV korean transmission line system under various fault conditions. From the tests presented in this paper it can be concluded that a fault location estimation algorithm using wavelet transform can precisely calculate the fault point for HIF.

  • PDF

개별스위치 멀티탭 사용에 의한 전기화재 위험성 연구 (A study on the Electrical Fire Hazard by using individual switch multiple-tap)

  • 박광묵;방선배;이기연;서길오;정종호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.1529-1530
    • /
    • 2015
  • 본 논문에서는 점점 증가하고 있는 전기적 요인에 의한 화재 중에서 최근 발생한 개별스위치 멀티탭 화재 사례를 분석하였으며 개별스위치의 반복동작실험과 과전류 인가 시 시간에 따른 개별스위치 멀티탭의 온도변화 특성을 관찰하고 개별 스위치 사용에 따른 전기화재 위험성을 분석하였다.

  • PDF

태양광 접속함의 트래킹에 의한 전기화재 위험성 연구 (A study on the Electrical Fire Hazard by the Tracking of Solar Connection box)

  • 박광묵;방선배;김동욱;이기연;김재현;박진영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.1531-1532
    • /
    • 2015
  • 본 논문에서는 태양광 발전설비 보급에 따라 증가하고 있는 태양광 접속함의 화재 사례를 분석하고 착화재현실험을 통하여 전기화재 위험성을 분석하였다. 전압 및 전류에 따른 태양광 접속함의 온도변화 특성을 분석하였으며, 특히 태양광 접속함의 트래킹에 의한 착화실험과정 통하여 전기적 특이점을 분석하고 트래킹에 의한 전기화재 예방대책을 제시하였다.

  • PDF

에어컨 배수펌프 설치 실태 및 개선방안 분석 - 창원시를 중심으로 (Analysis on Installation Conditions Survey and Improvement of Drain Pump in Air-Conditioner : Focusing on Changwon City)

  • 김성삼
    • 조명전기설비학회논문지
    • /
    • 제26권8호
    • /
    • pp.102-106
    • /
    • 2012
  • This paper was carried out to survey fire hazard and improvement at the drain pump in air-conditioners. Based on the results of analysis, the proposal of electrical accidents prevention and a construction improvement are as follows. A power connection of the drain pump has two types, an electrical outlet type and direct connection type at control board of air-conditioner. The electrical outlet types need a bulletin sign or education as malfunction of the drain pump include an additional accidents, current leakage and overflowing with water on the floor from breaker trip by exterior cause and breaker off by mistake of worker. On the other hand, the direct connection types prevent a power interruption as exterior cause, but it has some trouble, cut of ground cable and without protection device. Usually it doesn't work by electrician when air-conditioner and the drain pump power work. Therefore an education or countermeasures are recommended for not electrician. Generally malfunction of the drain pump causes accumulated materials into the tank. Even though the accumulated materials lead to an overheating and burning as failure of detector occur an idling, periodic inspection of the air-conditioner filter and the drain pump tank prevent the trouble.