• Title/Summary/Keyword: EX2000 excitation system

Search Result 5, Processing Time 0.026 seconds

PSS Tuning of EX2000 Excitation System in Thermal Plant: Part I- Optimal PSS Parameter Design (대형 화력발전소 EX2000 여자시스템 PSS 튜닝 : Part 1- 최적 PSS 파라메터 설계)

  • Kim, D.J.;Moon, Y.M.;Kim, S.M.;Kim, J.Y.;Hwang, B.H.;Choi, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.13-14
    • /
    • 2008
  • This paper describes the optimal PSS parameter design for the PSS of EX2000 excitation system. The suggested tuning technique uses the model-based PSS tuning method which have three steps: generation system modeling, determination of PSS parameters, and on-site test. Using this method, the PSS parameters of EX2000 system in Dangjin T/P #4 was designed and verified by linear analysis program, PSS/E, and EMTDC/PSCAD.

  • PDF

PSS Tuning of EX2000 Excitation System in Thermal Plant: Part II-Site Tuning Test and Validation (대형 화력발전소EX2000 여자시스템 PSS 튜닝 : Part 2-현장 튜닝시험 및 검증)

  • Kim, D.J.;Moon, Y.M.;Kim, S.M.;Kim, J.Y.;Hwang, B.H.;Choi, J.M.
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.15-16
    • /
    • 2008
  • This paper describes the on-site PSS Tuning Test of EX2000 excitation of Dangin T/P #4. The on-line 2% AVR step test in 500MW was performed by setting PSS gain from 0 to 15 by 3 increasement. The time-domain measured data was also analyzed by DFT analysis. Finally, the measured data was replicated and verified by running the time-domain dynamic simulation.

  • PDF

Tuning of Dual-input PSS and Its Application to 612 MVA Thermal Plant: Part 2-Field Testing and Performance Verification (다중입력 PSS 튜닝 방법과 612 MVA 화력기 적용: Part 2-현장 튜닝시험 및 성능검증)

  • Kim, Dong-Joon;Moon, Young-Hwan;Kim, Sung-Min;Kim, Jin-Yi;Hwang, Bong-Hwan;Cho, Jong-Man
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.4
    • /
    • pp.665-670
    • /
    • 2009
  • The second paper, Part 2, describes the field testing of IEEE type PSS2A EX2000 excitation in the Dangjin 612 MVA T/P #4. The final PSS gain, $K_s$, was determined by inputting 2%-step signals into AVR at a loading of 500MW and increasing $K_s$, from 0 to 15 in increments of 3. After the field testing, the measured data was also analyzed by Discrete Fourier Transformation(DFT) analysis, and the model parameters of generation system were verified by replicating the measured data with the transient stability program.

Tuning of Dual-input PSS and Its Application to 612 MVA Thermal Plant: Part 1-Tuning Methology of IEEE Type PSS2A Model (다중입력 PSS 튜닝 방법과 612 MVA 화력기 적용: Part 1-IEEE PSS2A 튜닝 방법)

  • Kim, Dong-Joon;Moon, Young-Hwan;Kim, Sung-Min;Kim, Jin-Yi;Hwang, Bong-Hwan;Cho, Jong-Man
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.4
    • /
    • pp.655-664
    • /
    • 2009
  • This paper, Part 1, describes the effective dual-input PSS parameter design procedure for the IEEE Type PSS2A against the Dangjin 612 MVA thermal plant's EX2000 excitation system. The suggested tuning technique used the model-based PSS tuning method and consisted of three steps: 1) generation system modeling; 2) determination of PSS2A model parameters using linear, time-domain transient and 3-phase simultaneous analyses, and 3) field testing and verification, which are described in Part 2. The effective PSS2A model parameters of EX2000 system in the Dangjin T/P #4 were designed according to the suggested procedure, and verified by using three analyses.

Field test Results for PSS Parameter Tuning in Seo-Incheon Power Plant (서인천 복합화력 발전소의 PSS 파라메터 Tuning)

  • Shin, Jeong-Hoon;Kim, Tae-Kyun
    • Proceedings of the KIEE Conference
    • /
    • 1998.07c
    • /
    • pp.1143-1146
    • /
    • 1998
  • Static excitation systems with high gain and fast response times greatly aid transient stability. but at the same time tend to reduce small signal stability. The objective of the power system stabilizer(PSS) control is to provide a positive contribution to damping of the generator rotor angle swings, which are in a broad range of frequencies in the power system. Therefore, this paper shows the field test results for the GE's EX2000 PSS tuning on units at Seo-Incheon power plant. The test is to verify that the PSS response meets GE's design, criteria. The responses of generator terminal voltage, active power, field voltage and current were analyzed and PSS gain was tuned by 10 finally.

  • PDF