• 제목/요약/키워드: ESS system

검색결과 539건 처리시간 0.028초

고속철도 변전소 피크부하 저감용 ESS 용량 산정 및 경제성 분석 (Sizing and Economic Analysis of Battery Energy Storage System for Peak Shaving of High-Speed Railway Substations)

  • 김슬기;김종율;조경희;변길성
    • 전기학회논문지
    • /
    • 제63권1호
    • /
    • pp.27-34
    • /
    • 2014
  • The paper proposed a sizing method of an energy storage system(ESS) for peak shaving of high-speed railway substations based on load profile patterns of substations. A lithium based battery ESS was selected since it can produce high-power at high speed that peak shaving requires, and also takes up a relatively smaller space for installation. Adequate size of the ESS, minimum capacity which can technically meet a peak shaving target, was determined by collectively considering load patterns of a target substation, characteristics of the ESS to be installed, and optimal scheduling of the ESS. In case study, a local substation was considered to demonstrate the proposed sizing method. Also economic analysis with the determined size of ESS was performed to calculate electricity cost savings of the peak shaving ESS, and to offer pay-back period and return on investment.

도시철도 부하특성을 고려한 ESS의 최적 운영방안 연구 (Study on the Optimal Operation of ESS Considering Urban Railway Load Characteristic)

  • 허재행;신승권;박종영;김형익
    • 전기학회논문지
    • /
    • 제64권10호
    • /
    • pp.1508-1516
    • /
    • 2015
  • This paper proposes the optimal operation of ESS (Energy Storage System) in the substation of urban railway in an economical point of view. Since the load patterns of urban railway have different characteristics with the general power demand pattern, the characteristics motivate us to develop the optimal operation algorithm for ESS under Korean electricity billing system. We also introduce two different ESS operation strategies for peak load shaving and electricity consumption charge minimization respectively, and formulate each scheme. Historical data from Namgwangju substation are used for economical comparison of the strategies. The results show that the proposed algorithm is the most cost-effective ESS operation scheme among the strategies and reduces around 5 percent of electric charges compared to the charge without ESS operation.

Simulink 모델을 활용한 주파수추종용 ESS 운전 특성분석 (Historical Operation Characteristic Analysis of Energy Storage System for Governor Free using Simulink Model)

  • 조성민;임지훈;이성은
    • 전기학회논문지
    • /
    • 제66권6호
    • /
    • pp.905-910
    • /
    • 2017
  • As the development of BESS(Battery Energy Storage System), the application of BESS in load frequency control is considered as effective method. So, KEPCO(Korea Electric Power Corporation) have installed about 236MW ESS for GF(Govner Free) function from 2014. In this paper, we implemented Simulink Model for KEPCO GF ESS and analyzed one year historical operation data generated by Simulink model and actually measured frequency data. The operation results were divided into action for maintaining SOC and frequency. In addition, we also analyzed cycle life of GF ESS using two ESS cycle life model. We concluded the ESS cycle life models are not appropriate, because Most of the SOC swing in operation results are below 10%.

ESS를 고려한 배전계통 재폐로 동작에 관한 연구 (A Study on the Reclosing Operation of Distribution System considering the ESS)

  • 서훈철;김철환;이상봉
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.583-584
    • /
    • 2015
  • Energy Storage System(ESS) can be used as several purposes such as uninterruptible power supply (UPS), frequency regulation, maximum load cut, and etc. This paper analyzes and simulates the reclosing operation in distribution system with ESS for frequency regulation and maximum load cut. To solve the effect from ESS, two sequences in reclosing process are added to conventional reclosing. The modelings and simulations of reclosing operation using EMTP/ATPDraw are performed.

  • PDF

에너지 저장 시스템 (ESS)용 배터리의 운전조건에 따른 성능 저하 및 태양광 연계형 ESS 모니터링 연구 (Performance Degradation of a Battery in an Energy Storage System (ESS) under Various Operating Conditions and Monitoring Study of ESS Connected with Photovoltaic)

  • 정윤이;정한주;정연기;이재영;이홍기
    • 한국수소및신에너지학회논문집
    • /
    • 제25권3호
    • /
    • pp.311-318
    • /
    • 2014
  • Performance degradation of a battery in 20 kWh energy storage system (ESS) under various operating conditions was studied. And energy saving of the ESS was also monitored by connecting with 20 kW photovoltaic (PV). PV-connected ESS saved 5~7% of energy consumption in 2013 compared to that without such system in 2012. As charge-discharge cycle increased, capacity decreased and the performance degradation was glaringly obvious after 40 cycles. And as charge and discharge rate increased, the performance degradation was more serious. After 50 charge-discharge cycles, a lot of degraded product was deposited on the surface of anode and cathode electrodes, and the cathode side was more contaminated. Therefore, in order to maintain the cell performance, it was more important to protect the degradation of the cathode side.

비상전원 기능을 갖는 3kW급 하이브리드 ESS 개발 (Development of 3kW Hybrid ESS with Function of Emergency Power Supply)

  • 양석현;김민재;최세완;조준석
    • 전력전자학회논문지
    • /
    • 제20권1호
    • /
    • pp.11-18
    • /
    • 2015
  • This paper proposes a high-efficiency 3-kW hybrid ESS with emergency power supply. The proposed system enables efficient use of power from photovoltaic (PV) cells and energy storage system (ESS). The proposed system can operate as an uninterruptible power supply (UPS) when grid fault occurs, providing seamless transfer from grid-connected mode to stand-alone mode. The LLC converter for PV achieves ZVS turn-on of switches and ZCS turn-off of diodes, and the isolated bidirectional DC-DC converter for ESS achieves ZCS turn-off regardless of load condition, resulting in high efficiency. The efficiency and performance of the proposed hybrid ESS has been verified by a 3-kW prototype.

효율적 전력 관리를 위한 독립형 가로등의 ESS 설계 및 구현 (Design and Implementation of an ESS for Efficient Power Management of Stand-Alone Type Street Lights)

  • 강진구
    • 디지털산업정보학회논문지
    • /
    • 제12권2호
    • /
    • pp.1-6
    • /
    • 2016
  • Several efforts to replace the use of existing fossil energy resources have already been made around the world. As a result, a new industry of renewable energy has been created, and efficient energy distribution and storage has been promoted intensively. Among the newly explored renewable energy sources, the most widely used one is solar energy generation, which has a high market potential. An energy storage system (ESS) is a system as required. In this paper, the design and implementation of an ESS for the efficient use of power in stand-alone street lights is presented. In current ESS applied to stand-alone street lights, either 12V~24V DC (from solar power) or 110V~220V AC (from commercial power) is used to recharge power in systems with lithium batteries. In this study, an ESS that can support both solar power and commercial power was designed and implemented; it can also perform emergency recharge of portable devices from solar powered street lights. This system can maximize the scalability of ESSes using lithium batteries with efficient energy conversion, with the advantage of being an eco-friendly technology. In a ripple effect, it can also be applied to smart grids, electric vehicles, and new, renewable storage markets where energy storage technology is required.

도시철도 시스템 전기요금 절감을 위한 혼합정수계획법 기반 ESS(에너지저장장치) 스케줄링 기법 (Mixed Integer Programming (MIP)-based Energy Storage System Scheduling Method for Reducing the Electricity Purchasing Cost in an Urban Railroad System)

  • 고락경;공성배;주성관
    • 전기학회논문지
    • /
    • 제64권7호
    • /
    • pp.1125-1129
    • /
    • 2015
  • Increasing peak load is one of the major concerns about operation of urban railroad systems. Since ESSs (Energy Storage Systems) have a great potential for shaving the peak load, there has been a growing interest in the use of ESS for peak load reduction. Also, ESS can be optimally scheduled to minimize the electricity purchasing cost under a given ToU (Time-of-Use) tariff by taking advantage of electricity price difference between peak and off-peak time. This paper presents a Mixed Integer Programming (MIP)-based ESS scheduling method to minimize the electricity purchasing cost under a ToU tariff for an urban railroad system.

에너지 저장 장치가 적용된 태양광 하이브리드 모듈형 시스템의 전력 조류 제어 (Power Flow Control of PV Hybrid Module System with ESS)

  • 이순령;김영호;장진우;최봉연;원충연
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2013년도 전력전자학술대회 논문집
    • /
    • pp.473-474
    • /
    • 2013
  • In this paper, a power flow control of PV hybrid module system with ESS is proposed. Photovoltaic(PV) hybrid module system is consist of individual converter, central inverter, and energy storage system(ESS). Because PV power can be changed in particular hours and environment condition, the power management control for ESS is required. In this paper, the power flow control method for PV hybrid module system with ESS is proposed. The validity of proposed control method is verified by simulations and theoretical analysis.

  • PDF

ESS 기능을 갖는 하이브리드 UPS (Hybrid UPS with Energy Storage System Function)

  • 임승범;홍순찬
    • 전력전자학회논문지
    • /
    • 제19권3호
    • /
    • pp.266-275
    • /
    • 2014
  • This paper proposes the hybrid UPS(Uninterruptible Power Supply) with ESS(Energy Storage System) function. The proposed hybrid UPS is operating in four states, which are normal state, battery state, ESS state, and bypass state. In case of peak load time or power shortage, the system is operating in ESS state in which the stored energy of the battery is used to manage the power effectively. The validity of proposed system are verified by simulations and experiments.