Evaluation of Fire Investigation as the Separation Distances for Several Types of Insulation Panels (단열패널 종류별 이격거리에 따른 화재감식 평가)

  • Kim, Jeong-Hun;Kim, Da-Seul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.22 no.4
    • /
    • pp.403-412
    • /
    • 2021
  • Despite strengthening requirements for fire retardancy and applied buildings of insulation panels, the number of fires and influence of damage have increased. In this study, the thermal effects were evaluated as the separation distances, and three types of EPS panel, glass wool panel, and gypsum board panel were then selected. Temperature sensors on the panels were installed vertically from the ground. The fire source on the lamination layer of lumber was ignited by changes in the separation distances (0 cm, 25 cm, 50 cm) from the panels. The test results suggested that the maximum temperature was 349 ℃ in the EPS panel. The inside/outside shape changes were limited by the height of the low and middle positions until the critical point of a 25 cm separation distance. Furthermore, the combustion marks appeared after 500 s on average, and then the EPS panel with a high fire strength showed a broad "U type" pattern, glass wool panel, and gypsum board panel showed medium or narrow "V type" pattern. Therefore, the acquired data can provide valuable information for evaluating the fire risks and verifying fire investigation from buildings composed of these insulation panels.