• 제목/요약/키워드: EMTDC/PSCAD

검색결과 690건 처리시간 0.022초

배전계통에 전력용 변압기 병렬운전시 22.9 kV SFCL Bus Tie 적용방안에 관한 연구 (A Study on the Application of SFCL on 22.9 kV Bus Tie for Parallel Operation of Power Main Transformers in a Power Distribution System)

  • 온민귀;김명후;김진석;유일경;임성훈;김재철
    • 전기학회논문지
    • /
    • 제60권1호
    • /
    • pp.20-25
    • /
    • 2011
  • This paper analyzed the application of Superconducting Fault Current Limiter (SFCL) on 22.9 [kV] bus tie in a power distribution system. Commonly, the parallel operations of power main transformers offer a lot of merits. However, when a fault occurs in the parallel operation of power main transformer, the fault currents might exceed the interruption capacity of existing protective devices. To resolve this problem, thus, the SFCL has been studied as the fascinating device. In case that, Particularly, the SFCL could be installed to parallel operation of various power main transformers in power distribution system of the Korea Electric Power Corporation (KEPCO) on 22.9 [kV] bus tie, the effect of the resistance of SFCL could reduce the increased fault currents and meet the interruption capacity of existing protective devices by them. Therefore, we analyzed the effect of application and proposed the proper impedance of the R-type SFCL on 22.9 [kV] bus tie in a power distribution system using PSCAD/EMTDC.

d-q 등가회로를 이용한 이중여자 유도발전기 보호 (Protection for DFIG using the d-q Equivalent Circuit)

  • 강용철;이지훈;강해권;장성일;김용균;박군철
    • 전기학회논문지
    • /
    • 제57권12호
    • /
    • pp.2173-2178
    • /
    • 2008
  • A doubly-fed induction generator(DFIG) system has been widely used in the modem wind turbines due to variable-speed operation, high efficiency and small converter size. It is well known that an inter-turn fault of a generator is very difficult to be detected. The DFIG system uses a wound rotor induction machine so that the magnetizing current of the generator can be fed from both the stator and the rotor. This paper proposes a protection algorithm for a DFIG using the d-q equivalent circuit in the time domain. In the case of a DFIG, the voltages and currents of the rotor side as well as the voltages and currents of the stator are available. The proposed algorithm estimates the instantaneous(i.e., converted into the stationary frame) induced voltages from the rotor and the stator sides. If the difference between the two estimated induced voltages exceeds the threshold, the proposed algorithm detects the inter-turn fault. The algorithm can detect a inter-turn fault of a winding. The performance of the proposed algorithm is validated using a PSCAD/EMTDC simulator under inter-turn fault conditions and normal operating conditions such as an external fault and the change of the wind speed.

온라인 전기자동차 시스템의 고조파 및 고주파가 배전계통에 미치는 영향에 관한 연구 (Effect of Harmonics and High-Frequency on OLEV System in Distribution Power System)

  • 최성호;허재선;한운기;김재철
    • 전기학회논문지
    • /
    • 제63권6호
    • /
    • pp.738-745
    • /
    • 2014
  • Recently, various measures have been discussed for overcoming depletion of fossil fuels and environmental pollution. One of the measures is electric vehicles. But electric vehicles has some limitations from high cost of battery and low efficiency, so operation distance of electric cars is limited. Also there are difficulties that charging lines should be connected by an electric car whenever it charges. Thus, many studies have been conducted to overcome the limitation using conventional batteries of electric vehicles. As a result, the OLEV(On-Line Electric Vehicle) was developed. But the OLEV system is some limitations. The OLEV system causes power quality problems when it charges. Power quality problem cannot be ignored because OLEV systems are closely connected by distribution grids. In this paper, the OLEV system is designed by using PSCAD/EMTDC, and the power quality is measured and evaluated. Power quality is divided by two cases; harmonics and high-frequency. Harmonics were evaluated according to IEEE Std. 519-1992. But the evaluation of High-frequency could not take it because there was no standard. For this reason, the data measured by OLEV system was compared with the EN50065 regulation.

Overvoltage Protection Controller Design of Distributed Generation Connected to Power Grid Considering Islanding Condition

  • Cha, Jae-Hun;Park, Kyung-Won;Ahn, Hong-Seon;Kwon, Kyoung-Min;Oh, Jin-Hong;MAHIRANE, Philemon;Kim, Jae-Eon
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권2호
    • /
    • pp.599-607
    • /
    • 2018
  • Distributed generation (DG) is being highlighted as an alternative for future power supplies, and the number of DG systems connected to conventional power systems is steadily increasing. DG generators are designed using power electronics and can give rise to various power quality problems, such as overvoltage or overcurrent. Particularly, unintentional islanding operation can occur in a conventional power system when the power grid is separated from the DG systems. Overvoltage may occur in this situation, depending on the power generation and power consumption. However, overvoltage phenomena might not happen even when islanding occurs. Therefore, it is necessary to analyze the fault characteristics during islanding. In this study, a fault analysis of islanding operation was carried out using PSCAD/EMTDC, and a countermeasure for the overvoltage problem is proposed.

양방향 지능형 반도체 변압기의 조류제어와 입력전압 Sag 보상 특성분석 (Power flow control and Input voltage Sag compensation Analysis of Bidirectional Intelligent Semiconductor Transformer)

  • 김도현;이병권;한병문;이준영;윤영두;최남섭
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2013년도 전력전자학술대회 논문집
    • /
    • pp.345-346
    • /
    • 2013
  • 본 논문에서는 단상 1.9kV/127V, 2kVA 용량의 양방향 지능형 반도체 변압기의 시작품을 제작하고 그 동작특성을 실험적으로 분석한 내용을 기술하고 있다. 제작한 반도체 변압기는 3대의 LLC 컨버터를 입력 측은 직렬로 결합하고 출력 측은 병렬로 결합한 AC-DC 컨버터와 1대의 하드스위칭 양방향 2-Stage DC-AC 컨버터가 직렬로 결합되어 있다. 제안하는 반도체변압기의 회로적인 특성을 분석하기 위해 PSCAD/EMTDC 소프트웨어를 이용한 시뮬레이션을 실시하였고 분석을 통해 얻은 결과를 바탕으로 하드웨어 시작품을 제작하고 다양한 실험을 통해 그 동작과 성능을 검증하였다. 먼저 1차적으로는 정상동작에 대해 실험을 실시하고 얻은 결과를 시뮬레이션 결과와 비교 분석하였다. 2차적으로는 전력의 흐름에 따른 동작을 실험적으로 분석하였다. 그 후에는 입력전압에 외란이 발생하였을 때 보상성능을 순방향 조류와 역방향 조류 2가지 경우로 나누어 실험을 실시하고 그 결과를 실험결과와 비교 분석하였다. 분석한 결과 제안하는 반도체변압기는 양방향 전력흐름이 가능하고 입력전압에 Sag가 발생한 경우에도 이를 보상하여 수전단이나 부하에 전력공급이 가능함을 알 수 있었다. 향후 단상 반도체 변압기 2대를 더 제작하여 3상 3.3kV/380V, 6kVA 용량으로 확대하여 실험을 실시할 예정이다.

  • PDF

전자기 과도현상 해석을 위한 S 영역 등가시스템 PART I : 주파수 의존 시스템 등가 (S-Domain Equivalent System for Electromagnetic Transient Studies PART I : Frequency Dependent Network Equivalent)

  • 왕용필
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권11호
    • /
    • pp.632-638
    • /
    • 2003
  • Modern power systems are very complex and to model them completely is impractical for electromagnetic transient studies. Therefore areas outside the immediate area of interest must be represented by some form of frequency dependent equivalent. The s-domain rational function form of frequency dependent equivalent does not need refitting if the simulation time-step is changed in the electromagnetic transient program. This is because the s-domain rational function coefficients are independent of the simulation time-step, unlike the z-domain rational function coefficients. S-domain rational function fitting techniques for representing frequency dependent equivalents have been developed using Least Squares Fitting(LSF). However it does not suffer the implementation error that exited in this work as it ignored the instantaneous term. This paper Presents the formulation for developing 1 Port Frequency Dependent Network Equivalent(FDNE) with the instantaneous term in S-domain and illustrates its use. This 1 port FDNE have been applied to the CIGRE Benchmark Rectifier test AC system. The electromagnetic transient package PSCAD/EMTDC is used to assess the transient response of the 1 port (FDNE) developed with Thevenin and Norton Equivalent network. The study results have indicated the robustness and accuracy of 1 port FDNE for electromagnetic transient studies.

접지방식이 상이한 철도배전계통의 연장급전을 위한 전기적 특성분석 (Analysis of electric characteristics for extension power supply between different grounding railway distribution system)

  • 정호성;한문섭;이장무;권삼영;박현준
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2005년도 추계학술대회 논문집
    • /
    • pp.736-741
    • /
    • 2005
  • This paper presents electric characteristics analysis and safe configuration for extension power supply between existent 6.6kV ungrounded distribution system and establishment and improvement 22.9kV direct grounding distribution system. For this, we model 6.6kV ungrounded and 22.9kV direct grounding distribution system of urban underground, ground region. and rural electrical, unelectrical region using PSCAD/EMTDC and analyze voltage drop, charging current, ground and short fault through simulation. To analyze electric characteristics of extension power supply, we simulate extension power supply of overhead line of 6.6kV ungrounded system and underground line of 22.9kV direct grounding system of rural electrical region and propose operation condition for safe extension power supply through result of analysis. Characteristics of voltage drop, charging current, ground and short fault appear almost similarly with electrical characteristic of direct power supply. However, because unbalance of phases may cause relay's malfunction of ungrounded system and ground fault current of direct grounding system may demage facilities of ungrounded system, we propose safe system configuration such as impedance grounding system of neutral point.

  • PDF

Comparative Study between Two Protection Schemes for DFIG-based Wind Generator Fault Ride Through

  • Okedu, K.E.;Muyeen, S.M.;Takahashi, R.;Tamura, J.
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • 제1권1호
    • /
    • pp.8-16
    • /
    • 2012
  • Fixed speed wind turbine generators system that uses induction generator as a wind generator has the stability problem similar to a synchronous generator. On the other hand, doubly fed induction generator (DFIG) has the flexibility to control its real and reactive powers independently while being operated in variable speed mode. This paper focuses on a scheme where IG is stabilized by using DFIG during grid fault. In that case, DFIG will be heavily stressed and a remedy should be found out to protect the frequency converter as well as to allow the independent control of real and reactive powers without loosing the synchronism. For that purpose, a crowbar protection switch or DC-link protecting device can be considered. This paper presents a comparative study between two protective schemes, a crowbar circuit connected across the rotor of the DFIG and a protective device connected in the DC-link circuit of the frequency converter. Simulation analysis by using PSCAD/EMTDC shows that both schemes could effectively protect the DFIG, but the latter scheme is superior to the former, because of less circuitry involved.

제주 행원 풍력발전단지의 출력 안정화를 위한 에너지저장시스템 용량산정에 관한 연구 (A Study on the Determining ESS Capacity for Stabilizing Power Output of Haeng-won Wind Farm in Jeju)

  • 강명석;진경민;김일환;오성보;이정민
    • 한국태양에너지학회 논문집
    • /
    • 제32권1호
    • /
    • pp.25-31
    • /
    • 2012
  • This paper presents the characteristics of power generation output at Haeng-won wind farm and how to determine the optimized ESS capacity for power stabilizing. Depend on the fluctuation rate of wind power output variation, wind farm capacity and site, power stabilization will be impacted. Therefore, we need to determine proper ESS capacity. Using the actual data of Haeng-won wind farm from 2009. 3 to 2010.2., capacity of ESS was determined by moving average value. To verify the proposed algorithm, simulations are carried out with PSCAD/EMTDC program. As a result, optimal ESS capacity of Haeng-won wind farm in Jeju is estimated about 1.63 MWh.

EMTP MODELS를 이용한 거리 계전기 응동 시뮬레이션 (A Dynamic Simulation of Distance Relay Using EMTP MODELS)

  • 허정용;김철환;여상민
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제52권1호
    • /
    • pp.17-28
    • /
    • 2003
  • Digital technology has advanced very significantly over the years both in terms of software tools and hardware available. It is now applied extensively in many area of electrical engineering including protective relaying in power systems. Digital relays based on digital technology have many advantages over the traditional analog relays. The digital relay is able to do what is difficult or impossible in the analog relays. However, the complex algorithms associated with the digital relays are difficult to test and verify in real time on real power systems. Although non real-time simulators like PSCAD/EMTDC are employed to test the algorithms, such simulations have the disadvantage that they cannot test the relay dynamically. Hence, real-time simulators like RTDS are used, but the latter needs large space and it is very expensive. This paper uses EMTP MODELS to simulate the power system and the distance relay. The distance relay algorithm is constructed and the distance relay is interfaced with a test power system. The distance relays performance is then assessed interactively under various fault types, fault distances and fault inception angles. The test results show that we can simulate the distance relay effectively and we can examine the operation of the distance relay very closely including debugging by using EMTP MODELS.