• 제목/요약/키워드: Doubly fed induction generator

Search Result 151, Processing Time 0.027 seconds

Hybrid Reference Function for Stable Stepwise Inertial Control of a Doubly-Fed Induction Generator

  • Yang, Dejian;Lee, Jinsik;Hur, Kyeon;Kang, Yong Cheol
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.1
    • /
    • pp.86-92
    • /
    • 2016
  • Upon detecting a frequency event in a power system, the stepwise inertial control (SIC) of a wind turbine generator (WTG) instantly increases the power output for a preset period so as to arrest the frequency drop. Afterwards, SIC rapidly reduces the WTG output to avert over-deceleration (OD). However, such a rapid output reduction may act as a power deficit in the power system, and thereby cause a second frequency dip. In this paper, a hybrid reference function for the stable SIC of a doubly-fed induction generator is proposed to prevent OD while improving the frequency nadir (FN). To achieve this objective, a reference function is separately defined prior to and after the FN. In order to improve the FN when an event is detected, the reference is instantly increased by a constant and then maintained until the FN. This constant is determined by considering the power margin and available kinetic energy. To prevent OD, the reference decays with the rotor speed after the FN. The performance of the proposed scheme was validated under various wind speed conditions and wind power penetration levels using an EMTP-RV simulator. The results clearly demonstrate that the scheme successfully prevents OD while improving the FN at different wind conditions and wind power penetration levels. Furthermore, the scheme is adaptive to the size of a frequency event.

Stepwise Inertial Control of a Doubly-Fed Induction Generator to Prevent a Second Frequency Dip

  • Kang, Mose;Lee, Jinsik;Hur, Kyeon;Park, Sang Ho;Choy, Youngdo;Kang, Yong Cheol
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.6
    • /
    • pp.2221-2227
    • /
    • 2015
  • To arrest a frequency nadir, a stepwise inertial control (SIC) scheme generates a constant active power reference signal of a wind turbine generator (WTG) immediately after a disturbance and maintains it for the predetermined time. From that point, however, the reference of a WTG abruptly decreases to restore the rotor speed for the predefined period. The abrupt decrease of WTG output power will inevitably cause a second frequency dip. In this paper, we propose a modified SIC scheme of a doubly-fed induction generator (DFIG) that can prevent a second frequency dip. A reference value of the modified SIC scheme consists of a reference for the maximum power point tracking control and a constant value. The former is set to be proportional to the cube of the rotor speed; the latter is determined so that the rotor speed does not reach the minimum operating limit by considering the mechanical power curve of a DFIG. The performance of the modified SIC was investigated for a 100 MW aggregated DFIG-based wind power plant under various wind conditions using an EMTP-RV simulator. The results show that the proposed SIC scheme significantly increases the frequency nadir without causing a second frequency dip.

Novel DC Grid Connection Topology and Control Strategy for DFIG-based Wind Power Generation System

  • Yi, Xilu;Nian, Heng
    • Journal of international Conference on Electrical Machines and Systems
    • /
    • v.2 no.4
    • /
    • pp.466-472
    • /
    • 2013
  • The paper presents a novel DC grid connection topology and control strategy for doubly-fed induction generator (DFIG) based wind power generation system. In order to achieve the wind power conversion, the stator side converter and the rotor side converter is used to implement the DFIG control based on the indirect air-gap flux orientation, and a DC/DC converter is used for the DFIG system to DC grid connection. The maximum power point tracking and DC voltage droop control can also be implemented for the proposed DFIG system. Finally, a 4-terminal DFIG-based multi-terminal DC grid system is developed by Matlab to validate the availability of the proposed system and control strategy.

Research on Voltage Stability Boundary under Different Reactive Power Control Mode of DFIG Wind Power Plant

  • Ma, Rui;Qin, Zeyu;Yang, Wencan;Li, Mo
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.6
    • /
    • pp.1571-1581
    • /
    • 2016
  • A novel method is proposed to construct the voltage stability boundary of power system considering different Reactive Power Control Mode (RPCM) of Doubly-Fed Induction Generator (DFIG) Wind Power Plant (WPP). It can be used for reflecting the static stability status of grid operation with wind power penetration. The analytical derivation work of boundary search method can expound the mechanism and parameters relationship of different WPP RPCMs. In order to improve the load margin and find a practical method to assess the voltage security of power system, the approximate method of constructing voltage stability boundary and the critical points search algorithms under different RPCMs of DFIG WPP are explored, which can provide direct and effective reference data for operators.

A Grid-connected to Rotor Type Doubly Fed Induction Generator for Wind Turbine Systems (풍력발전 시스템용 회전자 계통연계형 이중여자 권선형 유도발전기)

  • You, Yong-Min;Lipo, Thomas Anthony;Kwon, Byung-Il
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.800-801
    • /
    • 2011
  • This paper proposes a grid-connected to rotor type doubly fed induction generator (DFIG) in which the rotor winding is connected to the grid instead of the stator winding. The stator size and weight of the proposed grid-connected to rotor type DFIG can be reduced because the proposed type can use rotor core more efficiently compared to the stator type DFIG. In order to verify the size and weight reduction of the proposed type, the loading distribution method (LDM) is utilized. As a design result, the stator outer diameter and weight of the proposed type were decreased. The equivalent circuit analysis and finite element method also performed to verify the design results and to analyze characteristics of the novel DFIG.

  • PDF

Control Strategies of Doubly Fed Induction Generator -Based Wind Turbines with Crowbar Activation (Crowbar 운전을 가지는 이중여자유도발전기 풍력발전시스템의 제어전략)

  • Justo, Jackson John;Ro, Kyoung-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.706-707
    • /
    • 2011
  • The insertion of the crowbar system in the doubly fed induction generator rotor circuit for a short period of time during grid disturbance enables a more efficient way of limiting transient rotor current and hence protecting the rotor side converter (RSC) and the DC - link capacitor. When crowbar is activated at fault occurrence and clearance time, RSC is blocked while DC -link capacitor and the grid side converter (GSC) can be controlled to provide reactive power support at the PCC and improve the voltage which helps to comply with grid codes. In this paper, control strategies for crowbar system to limit the rotor current during fault is presented with RSC and GSC controllers are modified to control PCC voltage during disturbance to enhance DFIG wind farm to comply with some strict grid codes. Model simulated on MATLAB/Simulink verify the study through simulation results presented.

  • PDF

Power System Oscillations Damping by Robust Decentralized DFIG Wind Turbines

  • Surinkaew, Tossaporn;Ngamroo, Issarachai
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.2
    • /
    • pp.487-495
    • /
    • 2015
  • This paper proposes a new robust decentralized power oscillation dampers (POD) design of doubly-fed induction generator (DFIG) wind turbine for damping of low frequency electromechanical oscillations in an interconnected power system. The POD structure is based on the practical $2^{nd}$-order lead/lag compensator with single input. Without exact mathematical model, the inverse output multiplicative perturbation is applied to represent system uncertainties such as system parameters variation, various loading conditions etc. The parameters optimization of decentralized PODs is carried out so that the stabilizing performance and robust stability margin against system uncertainties are guaranteed. The improved firefly algorithm is applied to tune the optimal POD parameters automatically. Simulation study in two-area four-machine interconnected system shows that the proposed robust POD is much superior to the conventional POD in terms of stabilizing effect and robustness.

LVRT Scheme for Doubly Fed Induction Generator Systems Based on Flux Tracking Method (자속 추종을 통한 DFIG 시스템의 LVRT 기법)

  • Park, Sun-Young;Chun, Yeong-Han;Lee, Dong-Myung
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.8
    • /
    • pp.1059-1065
    • /
    • 2013
  • Doubly Fed Induction Generator(DFIG) systems occupy the largest proportion of worldwide wind energy generation market. DFIG systems are very sensitive to grid disturbances especially to voltage dips due to the structure of the stator connected to grid. In the past, when a grid fault occurs generators are separated from grid(trip method) in order to protect the systems. Nowadays, due to the growing penetration level of wind power, many countries have made some requirements that wind turbines are required to have Low Voltage Ride Through(LVRT) capability during grid faults. In this paper, a flux tracking LVRT control strategy based on system modeling equations is proposed. The validity of the proposed strategy is verified through computer simulations.

A Study on the 2nd exitation method for CVCF Generation of doubly-fed induction Generator (권선형 유도 발전기 CVCF 발전을 위한 2차 여자 제어법에 관한 연구)

  • Ahn, Jin-Woo;Kim, Chul-Woo;Hwang, Young-Moon
    • Proceedings of the KIEE Conference
    • /
    • 1988.11a
    • /
    • pp.341-344
    • /
    • 1988
  • This paper derives a condition foe constant voltage i constant frequency generation of doubly-fed induction generator. The condition is varied by the magnitude of output voltage, load current and its power factor, slip of the machine. Magnitude of output voltage is controlled by exiting voltage which is caculated by derived equation from operating condition. frequency of output voltage is controlled by injecting slip frequency to the rotor which is the difference between wanted output frequency and rotor frequency.

  • PDF

Dynamic droop-based power smoothing of a doubly-fed induction generator (시변 드룹을 이용한 이중여자풍력발전기의 출력 평활화)

  • Hwang, Min;Lee, Jinsik;Lee, Hyewon;Kang, Yong Cheol
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.177-178
    • /
    • 2015
  • This paper proposes a power smoothing scheme of a doubly-fed induction generator. The proposed scheme aims to mitigate system frequency deviation caused by the variable wind. To achieve this, a dynamic droop loop is used and its gain changes with rate of change of frequency so that it can release a large amount of kinetic energy at the initial stage of a frequency event. The performance of the proposed scheme was investigated in a model system with high wind penetration using EMTP-RV simulator. The test results indicate that the scheme can smooth the output power by absorbing or releasing the output power under a varying wind condition.

  • PDF