• 제목/요약/키워드: District heating substation

검색결과 5건 처리시간 0.02초

급탕 2단열교환방식 지역난방 열사용시설의 급탕부하 분배에 관한 연구 (Distribution of Hot Tap Water Load for District Heating Substation with Hot Tap Water 2-Stage Heat Exchanger)

  • 정동화;김주완;백영진;이영수;정대헌
    • 설비공학논문집
    • /
    • 제23권4호
    • /
    • pp.297-302
    • /
    • 2011
  • According to the standards for district heating substation established by Korea District Heating Corporation, water heating supply systems at over 150 Mcal/h capacity must employ the 2-stage heat exchanger that improves the system efficiency by reusing the heat included in the return water of district heating system already used for space heating. In this paper, the operating characteristics of the system in accordance with the load distribution of two heat exchangers for pre-heating and re-heating cold city water are investigated. The results including mass flow rate, return temperature etc. help to manage district heating system economically.

3방 비례제어 조절밸브 개발 및 성능 연구 (Development of Three-Way Proportional Control Valve and Performance Study)

  • 이종화;정택수;조종두;김주용
    • 설비공학논문집
    • /
    • 제26권5호
    • /
    • pp.218-223
    • /
    • 2014
  • Korea District heating corp. recently give an attention to combine the district heating and supply pipes as a two pipe system that are in the present system separated with room heating and warm water supply pipe, and the two pipe system is commonly applied for heating service in European countries. In the new two pipe system, only one heat source is supplied to a house and partitioned into room heating and warm water supply by household substation. So the effective distribution of supplied heat source in accordance to user intention is very important. This paper presents the development and performance test of three-way proportional control valve for a combined heat source system in district heating. The proposed valve is controlled to partition heat source into two different directions : hot water distributor for space heating and household substation for warm water supply in response to the pressure drops of tap water caused by the user. The performance investigation is shown within 3% of error compared to the theoretical model of the three-way proportional valve and its controllability is verified.

지역난방 사용자기계실 내 열수송관 차압을 이용한 발전 및 제어 기술 (Power Generation and Control System Using Differential Pressure of District Heating Pipeline in a Substation)

  • 김경민;박성용;오문세
    • 에너지공학
    • /
    • 제26권3호
    • /
    • pp.90-96
    • /
    • 2017
  • 지역난방 열수송관을 통해 중온수를 공급할 때 고압의 중온수로부터 열사용자 설비(지역난방 열교환기)를 보호하고 온도조절을 원활히 하고 유체의 원거리 공급을 위해 차압유량조절밸브를 통해 압력을 조절하거나 압력을 감소시키고 있다. 하지만, 고압 유체 사용에 따라 압력조절밸브에서 캐비테이션이 발생하여 잦은 고장 및 오작동을 유발하여 많은 문제가 발생하고 있으며, 사업자 및 사용자 모두에게 에너지 손실 및 민원 유발 등의 원인이 되고 있다. 이러한 문제를 해결하기 위해 연구 중인 1차측 차압유량조절밸브를 수력터빈으로 대체하여 차압에너지를 전기에너지로 변환하고, 전기를 2차측 펌프의 동력으로 활용하는 에너지 절감기술을 소개하고자 한다.

엑서지를 이용한 지역난방 열요금 제도 제안 (Suggestion of New Heat Tariff Assessment for District Heating Using Exergy)

  • 문정환;이재헌;문승재;유호선
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.912-918
    • /
    • 2008
  • In this study, the exergy which could be reflected on energetic and economic value was used to assess on heat tariff of district heating system instead of enthalpy. Exergy is difficult to apply directly to present heat charge system because of complex calculation. Therefore, the difference between supply and return temperature was converted to the exergy temperature difference for easily calculating the amount of heat. As a result of exergy analysis for a DH substation, the exergy temperature difference were not affected on surrounding temperature and pressure loss. Supply temperature, maximum difference between supply temperature and return temperature had a main effect on the exergy temperature difference. The new heat charge of a DH user was slightly reduced in winter compared with previous heat charge. Heat charges in other seasons were almost same. It is thought that heat tariff using exergy will be appropriate in terms of both DH supplier and consumer.

  • PDF

엑서지를 이용한 지역난방 열요금 제도 제안 (Suggestion for a New Exergy-Based Heat-Tariff Assessment for a District-Heating System)

  • 문정환;유호선;이재헌;문승재
    • 설비공학논문집
    • /
    • 제29권4호
    • /
    • pp.202-211
    • /
    • 2017
  • In this study, the exergy that can be reflected in the energetic and economic values was used to assess the heat tariff of a district heating (DH) system instead of the enthalpy. It is difficult to directly apply the exergy to the current heat-charge system because of the complicated calculation; therefore, the difference between the supply and return temperatures was converted to the exergy-temperature difference for the ease of the heat-amount calculation. As a result of the exergy analysis for a DH substation, the exergy-temperature difference did not affect the surrounding temperature and pressure loss. The supply temperature and the maximum difference between the supply temperature and the return temperature exerted the main effect on the exergy-temperature difference. The new heat charge of a DH user was slightly reduced in winter compared with the previous charge, but the heat charges in the other seasons are almost the same. It is concluded from the assessment of the heat tariff for which the exergy is used that this tariff is more feasible for both DH suppliers and consumers compared with enthalpy.