• Title/Summary/Keyword: Distributing Cable Termination

Search Result 4, Processing Time 0.031 seconds

Influence of Defects on Electrical Characteristics of Distributing Cable Termination (배전급 케이블 종단부의 결점이 전기적 특성에 미치는 영향)

  • Kim, Sang-Hyun;Choi, Jae-Hyeong;Choi, Jin-Wook;Kim, Young-Seok;Kim, Sun-Gu;Baek, Seung-Myeong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.2
    • /
    • pp.190-195
    • /
    • 2009
  • This paper introduces experimental investigates of an electrical accident of the distributing cable termination with simulated a shoddy construction. We prepared two termination kites, one is built-in type, the other is heat contraction type. Also, we manufactured cable termination that have simulated defect by badness construction and investigated their insulation characteristics such as ac (35[kV], 1[min]) and impulse (95[kV], $1.2{\times}50[{\mu}s]$) withstand test. The influence of defects such as thickness decrease, the gap between stress-con of housing and semiconductor and heating time on insulating properties of the termination have been studied. The thickness decrease of an insulator decreases ac breakdown strength suddenly and the breakdown traces of the insulator that is damaged by knife displayed elliptic shape. The gap of between stress-con and semiconductor deteriorates dielectric strength of insulator seriously. In heat contraction type, the ac breakdown voltage became low when the heating time is short.

A Study on Electrical Accident of Distributing Cable Termination Considering PL Law Environment (PL법 환경을 고려한 배전 케이블 종단부의 전기적 사고 연구)

  • Kim, Sang-Hyun;Choi, Jae-Hyeong;Choi, Jin-Wook;Baek, Seung-Myeong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.2
    • /
    • pp.178-183
    • /
    • 2009
  • This paper introduces experimental investigates of an accident pattern for the distributing cross linking-polyethylene(XLPE) cable terminations considering product liability(PL) law environment. The influence of defects such as thickness and length decrease of XLPE, an impurity on XLPE and the gap between stress-con of housing and semi-conductor on insulating properties of the termination have been studied. The thickness and length decrease of XLPE decrease ac breakdown strengths. Breakdown traces of XLPE that is damaged by knife displayed ellipse shape. The gap of between stress-con and semiconductor deteriorates dielectric strength of XLPE seriously.

A Study on Electrical Accident of Distributing Cable Termination with Simulated Badness Construction (평가시공불량을 모의한 배전급 케이블 종단부의 전기적 사고 연구)

  • Choi, Jae-Hyeong;Choi, Jin-Wook;Kim, Sang-Hyun;Kim, Young-Seok;Kim, Sun-Gu;Baek, Seung-Myeong
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.11a
    • /
    • pp.465-470
    • /
    • 2008
  • This paper introduces experimental investigates of an electrical accident of the distributing cable termination with simulated badness construction. We prepared two termination kites, one is built-up type, the other is heat contraction type. Also, we manufactured cable termination that have simulated defect by badness construction and measured their insulation characteristics such as ac (35kV, 1min) and impulse (95kV, $1.2{\times}50{\mu}s$) withstand test. The influence of defects such as thickness and the gap between stress-con of housing and semi-conductor on insulating properties of the termination have been studied. The thickness decrease of insulator decreases ac breakdown strength. Dielectric breakdown traces of insulator that is damaged by knife displayed other shape. The gap of between housing and semiconductor deteriorates dielectric strength of insulator seriously.

  • PDF

A Study on Accident Pattern of Distributing Cable Termination Considering PL Law Environment (PL법 환경을 고려한 배전 케이블 종단부의 사고 유형 연구)

  • Baek, Seung-Myeong;Choi, Jae-Hyeong;Choi, Jin-Wook;Kim, Young-Seok;Kim, Sun-Gu;Kim, Sang-Hyun
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.319-322
    • /
    • 2008
  • This paper introduces experimental investigates of an accident pattern for the distributing XLPE cable terminations considering PL law environment. The influence of defects such as thickness and length decrease of XLPE, the impurity on XLPE and the gap between stress-con of housing and semi-conductor on insulating properties of the termination have been studied. The thickness and length decrease of XLPE decrease ac breakdown strengths. Dielectric breakdown traces of XLPE that is damaged by knife displayed other shape. The gap of between housing and semiconductor deteriorates dielectric strength of XLPE seriously.

  • PDF