• Title/Summary/Keyword: Dissolved gas

Search Result 375, Processing Time 0.022 seconds

A Study on the Reliability of Failure Diagnosis Methods of Oil Filled Transformer using Actual Dissolved Gas Concentration (유중가스농도를 이용한 유입식 변압기 고장진단 기법의 신뢰성에 관한 연구)

  • Park, Jin-Yeub;Chin, Soo-Hwan;Park, In-Kyoo
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.60 no.3
    • /
    • pp.114-119
    • /
    • 2011
  • Large Power transformer is a complex and critical component of power plant and consists of cellulosic paper, insulation oil, core, coil etc. Insulation materials of transformer and related equipment break down to liberate dissolved gas due to corona, partial discharge, pyrolysis or thermal decomposition. The dissolved gas kinds can be related to the type of electrical faults, and the rate of gas generation can indicate the severity of the fault. The identities of gases being generated are using very useful to decide the condition of transformation status. Therefore dissolved gas analysis is one of the best condition monitoring methods for power transformer. Also, on-line multi-gas analyzer has been developed and installed to monitor the condition of critical transformers. Rogers method, IEC method, key gas method and Duval Triangle method are used to failure diagnosis typically, and those methods are using the ratio or kinds of dissolved gas to evaluate the condition of transformer. This paper analyzes the reliability of transformer diagnostic methods considering actual dissolved gas concentration. Fault diagnosis is performed based on the dissolved gas of five transformers which experienced various fault respectively in the field, and the diagnosis result is compared with the actual off-line fault analysis. In this comparison result, Diagnostic methods using dissolved gas ratio like Rogers method, IEC method are sometimes fall outside the ratio code and no diagnosis but Duval triangle method and Key gas method is correct comparatively.

Review on the Relationship of Dissolved Gas Analysis and Internal Inspection of Transformer (변압기 절연재료 분석과 내부점검 결과와의 상관성 연구)

  • Park, Hyun-Joo;Nam, Chang-Hyun;Jung, Nyun-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.59 no.10
    • /
    • pp.1869-1873
    • /
    • 2010
  • For reliable operation of oil-filled electrical equipment, monitoring and maintenance of insulating oil is essential. Dissolved gas analysis(DGA) is widely used for monitoring faults in high voltage electrical equipment in service. Therefore, oil analysis should be monitored regularly during its service life. KEPCO has investigated thousands of dissolved gas analysis data since 1985, and conducted studies on the relationship of gas in oil analysis and internal inspection results of transformer. As the results, KEPCO revised criteria for transformer diagnosis and has applied it since 2008. Almost of 100 cases of internal inspection results since 2001 have been investigated. This paper presents the correlation of the fault-identifying gases with faults found in actual transformers and how should we approach to internal inspection of transformer by dissolved gas analysis.

Production of high dissolved O2/O3 with rotating wheel entraining gas method for environmental application

  • Li, Haitao;Xie, Bo;Hui, Mizhou
    • Advances in environmental research
    • /
    • v.2 no.1
    • /
    • pp.1-8
    • /
    • 2013
  • There is a significant demand to make various dissolved gases in water. However, the conventional aeration method shows low gas mass transfer rate and gas utilization efficiency. In this study, a novel rotating wheel entraining gas method was developed for making high dissolved $O_2$ and $O_3$ in water. It produced higher concentration and higher transfer rate of dissolved $O_2$ and $O_3$ than conventional bubble aeration method, especially almost 100% of gas transfer efficiency was achieved for $O_3$ in enclosed reactor. For application of rotating wheel entraining gas method, aerobic bio-reactor and membrane bio-reactor (MBR) were successfully used for treatment of domestic and pharmaceutical wastewater, respectively; and vacuum ultraviolet $(VUV)/UV+O_3/O_2$ reactors were well used for sterilization in air/water, removal of dust particles and toxic gases in air, and degradation of pesticide residue and sterilization on fruits and vegetables.

Neural Network Based Dissolved Gas Analysis Using Gas Composition Patterns Against Fault Causes

  • J. H. Sun;Kim, K. H.;P. B. Ha
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.3C no.4
    • /
    • pp.130-135
    • /
    • 2003
  • This study describes neural network based dissolved gas analysis using composition patterns of gas concentrations for transformer fault diagnosis. DGA samples were gathered from related literatures and classified into six types of faults and then a neural network was trained using the DGA samples. Diagnosis tests were performed by the trained neural network with DGA samples of serviced transformers, fault causes of which were identified by actual inspection. Diagnosis results by the neural network were in good agreement with actual faults.

Dissolved Gas Analysis of Environment-Friendly Vegetable Insulating Oils (친환경 식물성 절연유의 유중가스 분석)

  • Choi, Sun-Ho;Kim, Kwan-Sik;Huh, Chang-Su
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.28 no.4
    • /
    • pp.238-243
    • /
    • 2015
  • The vegetable insulating oils are substitute for the mineral oil in power transformer. Vegetable insulating oils has higher flash/fire point and biodegradability than conventional mineral oils. In this paper, we investigated the dissolved gas analysis of vegetable oils. In the experiment, I had to accelerated aging under the same conditions mineral oil and vegetable oils. Accelerated aging proceeded to about 100% of the life of oil-filled transformer. In addition, we performed gas analysis of insulating oil of accelerated aging progress. The experiment results of the five gases was measured with the exception of Hydrogen and Acetylene. The mineral oil and vegetable oils gas is generated in a similar tendency depending on the accelerated aging. As a result, vegetable oils, can be dissolved gas analysis by method such as mineral oil.

Measurement Technology of the Dissolved Hydrogen Gas Due to Partial Discharge in Oil using Gas Sensor (가스센서를 이용한 부분방전특성에 따른 유중수소가스 측정연구)

  • Heo, Jong-Cheol;Sun, Jong-Ho;Kang, Dong-Sik;Jeong, Joo-Young;Choo, Y.B.;Park, Jung-Hoo
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.9
    • /
    • pp.1784-1789
    • /
    • 2009
  • This paper describes the measurement technology of the dissolved hydrogen gas due to partial discharge in oil using gas sensor. For higher resolution and less error in measurement of the dissolved hydrogen gas in oil, the sensor outputs with ambient temperature which affect the sensor output characteristics should be considered. The sensor output trends with ambient temperature and the properties of the dissolved hydrogen gas in oil with partial discharge characteristic were analyzed through the test results. It was indicated that the sensor peak and the base voltage with measuring time were affected by ambient temperature and the measurement errors of the sensor output by temperature were reduced by using the difference between the peak and the base voltage rather than just the peak voltage. In addition, the hydrogen gas sensor outputs were increased with the increase of partial discharge energy.

Study on the Criterion and Algorithm for On-line Dissolved Gas of a Power Transformer (전력용 변압기 온라인 유중가스 진단기준치 및 알고리즘에 관한 연구)

  • Kweon Dongjin;Kwak Joosik;Kwak Heero;Kim Jaechul;Chin Sunbm
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.5
    • /
    • pp.206-212
    • /
    • 2005
  • In this paper, criterion and algorithm for on-line dissolved gas of a Power transformer are studied. For the initial diagnosis of a power transformer, the on-line dissolved gas analysis is one of the most important and acceptable item to preventively diagnose a power transformer. But the criterion and algorithm of this item are not established yet in korea. In this paper, criterion and alarm level of the on-line dissolved gas analysis are based on the analysis of on-line data of operating transformers, Korea industrial standard and operation manual for a power transformer as well as accumulated data of the preventive diagnosis systems which have been operated at nine substations of Korea Electric Power Co.(KEPCO) since 1997, Therefore, the criterion and alarm level proposed in this paper are to be well suitable and are adaptable for the domestic operational environments and conditions of the power transformer. Considering that the conventional diagnosis system is capable only of accumulating and monitoring data of the power transformer operation, the criteria and the algorithms make it possible to accomplish an ultimate goal of the preventive diagnosis system. It is expected, therefore, that they will have a beneficial effect on broad applications of the preventive diagnosis system and the achievement of manless substation system in the future.

Dissolved Gas Analysis Using the Dempster-Shafer Rule of Combination (Dempster-Shafer 결합 규칙을 이용한 유중 가스 분석법)

  • Yoon, Yong-Han;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.301-303
    • /
    • 1998
  • This paper presents a new approach to diagnose and detect faults in oil-filled power transformers based on various dissolved gas analyses. A theoretic fuzzy information model is introduced, An inference scheme which yields the 'most' consistent conclusion proposed. A framework is established that allows various dissolved gas analyses to be combined in a systematic way such as the Dempster-Shafer rule. Good diagnosis accuracy is obtained with the proposed approach.

  • PDF

Study on $H_2$ Sensing Characteristics of Gas Extractor for Dissolved Gas in Oil (유중 가스 검출장치의 수소 가스 감지 특성에 관한 연구)

  • Hwang, Kyu-Hyun;Seo, Ho-Joon;Rhie, Dong-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1162-1165
    • /
    • 2004
  • In oil-filled enuipment such as transformers, partial discharge or local overheating will precede a final shutdown. Accompanied with such problems is a decomposition of insulating material into gases, which are dissolved into the transformer oil. The gases dissolved in oil can be separated with some membranes based on the differences in permeability of membranes to different gases. This paper discuss the permeability characteristics of several membranes for separation hydrogen gas in oil. With result of this paper, it may become possible to detect fault-related gases from transformer oil and predict incipient failures in the future.

  • PDF

Separation of dissolved gases from water using synthesized gases based on exhalation characteristics

  • Heo, Pil Woo;Park, In Sub
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.38 no.10
    • /
    • pp.1347-1353
    • /
    • 2014
  • It's possible for a human to breathe under water, if dissolved oxygen is effectively used. Fish can stay under water using the gill which extracts dissolved oxygen from water. Water includes small amounts of oxygen, so a human needs larger amounts of water to acquire oxygen enough for underwater breathing. The exhalation gas from a human is another method to get higher amounts of oxygen under water. It mainly composes of oxygen, nitrogen and carbon dioxide. So, if only carbon dioxide is decreased, the exhalation gas has good characteristics for breathing of a human under water. In this paper, composition of the exhalation gas from a human was analyzed using GC. Based on these results, the synthesized gas was prepared and mixed into water which was used for experimental devices to analyze separation characteristics of dissolved gases from water. Experimental devices included a water pump, a hollow fiber membrane module and a vacuum pump. The effects of pressure and water flow on separation characteristics of synthesized gas were investigated. The compositions of gases separated from water using synthesized gas were investigated using GC. These results expect to be applied to the development of underwater breathing technology for a human.