• Title/Summary/Keyword: Digital Distance Relaying

Search Result 32, Processing Time 0.017 seconds

A Study on the Digital Distance Relaying Techniques Using Kalman Filtering (칼만필터링에 의한 디지털 거리계전 기법에 관한 연구)

  • 김철환;박남옥;신명철
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.41 no.3
    • /
    • pp.219-226
    • /
    • 1992
  • In this study, Kalman filtering theory is applied to the estimation of symmetrical components from fault voltage and current signal when it comes to faults with the power system. An algorithm for estimating fault location accurately and quickly by calculating the symmetrical components from the extracted fundamental voltage phasor and current phasor is presented. Also, to confirm the validity of digital distance relaying techniques using Kalman filtering, the experimental results obtained by using the digital simulation of power system is shown.

  • PDF

A Study on the Development of the Digital Distance Relay Simulator for Education using GUI (GUI를 이용한 교육용 디지털 거리계전기 시뮬레이터 개발에 관한 연구)

  • Kim Dong-Su;Kim Chul-Hwan;Lee Ki-Teak;Park Nam-Ok
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.8
    • /
    • pp.388-395
    • /
    • 2005
  • It has always been of great importance in the electrical power system to educate an algorithm on the digital relaying, but it is difficult to educate an algorithm of a digital distance relay on power system because of exclusiveness of the relaying algorithm on power system. Therefore, we need a digital distance relay simulator, which can simulate the algorithm of the digital relaying on transmission line. In this Paper, we extract fundamental components using digital signal processing from data which are a variety of the simulated faults by EMTP. Then this simulator represents instantaneous values, ms values and symmetrical components that are calculated by fundamental components of voltages and currents. The Simulator also represents the zones of a digital distance relay and the locus of an impedance using GUI. Consequently, the developed simulator is particularly useful for understanding of the fundamental concepts of a distance relaying algorithm from a power system engineer points of view.

A Digital Distance Relaying Algorithm using a Wavelet Transformation (Wavelet 변환을 이용한 디지털 거리계전 알고리즘)

  • Kang, Sang-Hee;Lee, Joo-Hun;Nam, Soon-Ryul;Park, Jong-Keun
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.10
    • /
    • pp.1215-1221
    • /
    • 1999
  • A high speed digital distance relaying algorithm based on a Wavelet Transformation is proposed. To obtain stable phasor values very quickly, first, a lowpass filter which has low cutoff frequency is used. Secondly, db2(Daubechies 2) Wavelet which has the data window of 4 samples is used. A FIR filter which removes the DC-offset component in current relaying signals is applied. In accordance with a series of tests, the operation time of the relaying algorithm is less than 3/4 cycles after faults in a 80 [km], 154[kV], 60[Hz] over-head transmission line system.

  • PDF

A High Speed Distance Relaying Algorithm Based on a Least Square Error Method (최소자승법을 이용한 고속 거리계전 알고리즘)

  • Gang, Sang-Hui;Gwon, Tae-Won
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.7
    • /
    • pp.855-862
    • /
    • 1999
  • A high speed digital distance relaying algorithm based on a least square error method is proposed. To obtain stable phasor values very quickly, first, a lowpass filter which has very short transient period and no overshoot is presented. Secondly, the least square error method having the data window of 3 samples is used by applying a FIR filter which removes the DC-offset component in current relaying signals. Test results show that the proposed distance relaying algorithm detects most of internal faults within a half cycle after faults in a 154[kV] overhead transmission line system.

  • PDF

A Digital Distance Relaying Algorithm Immune to Fault Resistance (고장저항의 영향을 최소화한 거리계전기법)

  • Ahn, Yong-Jin;Kang, Sang-Hee
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.286-288
    • /
    • 1998
  • A digital distance relaying algorithm immune to the effect of the fault resistance in single-phase to ground fault is proposed. The power frequency components of relaying signals are extracted by the 1 cycle DFT. To compensate the magnitude and phase of the estimated impedance, which is calculated by the general method, this algorithm uses phase difference between the zero sequence impedance of networks on both sided of the system.

  • PDF

Development of Learning Board for the Digital Relay Using DSP (DSP를 이용한 학습용 계전기 보드 개발)

  • Ahn, Yong-Jin;Choi, Young-Woo
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.187-189
    • /
    • 2002
  • A relaying board is developed for the study of digital relay, which is based on Digital Signal Processor(DSP). The present development is capable of understanding and application for digital relay hardware. To support the design of relaying hardware, first A/D convertor MMI and serial port for communication are embedded, and next a booting cables of three types are supplied. More particularly the relaying board that is convinient to test digital relaying algorithm. This paper concludes by implementing the distance relaying algorithm into a relaying board, the hardware test results show practically high performance.

  • PDF

A High Speed Distance Relaying Algorithm Based on a Least Square Error Method (최소자승법을 이용한 고속 거리계전 알고리즘)

  • Kwon, Tae-Won;Kang, Sang-Hee
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.208-210
    • /
    • 1998
  • A high speed digital distance relaying algorithm based on a modified least square error method is proposed. To obtain stable phasor values very Quickly, first, a lowpass filter which has very short transient period and no overshoot is used. Secondly, the conventional least square error method is modified to the one having the data window of 3 samples by applying a FIR filter which removes the DC-offset component in current relaying signals.

  • PDF

An Improvement of Digital Distance Relaying Algorithm on Underground Transmission Cables (지중송전케이블룡 디지털 거리계전 알고리즘 개선)

  • Ha, Che-Ung;Lee, Jong-Beom
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.12
    • /
    • pp.595-601
    • /
    • 2000
  • This paper describes the improvement method of distance relaying algorithm for the underground transmission cables. Distance relaying algorithms have been mainly developing to protect the overhead transmission lines than the underground cables. If the cable systems are directly protected using distance relaying algorithm developed for overhead line without any improvement, there will be really occurred many misoperation in cable systems, because the cable systems consist of the conductor, the sheath, several grounding method, cable cover protection units(CCPUs), and grounding wire. Accordingly, the complicated phenomena are occurred, if there is a fault in cable systems. Therefore, to develope a correct distance relaying algorithm, such cable characteristics should be taken into account. This paper presents the process to improve distance relaying algorithm which is now used. REal cable system was selected to establish modeling in EMTP and ATP Draw. It was discovered through the detailed simulation during the fault that the large error existed between impedance measured at the relay point and real impedance is due to the resistance of grounding wire in each grounding method. And also compensation factor obtained by the simulation is proposed in this paper. It is proved that the factor proposed can fairly improve the accuracy of impedance at the relay point. It is evaluated that the protective ability will be really much improved, if the algorithm proposed in this paper is applied for cable systems of utility.

  • PDF

A Recursive Distance Relaying Algorithm Immune to Fault Resistance (고장저항의 영향을 최소화한 순환형 거리계전 알고리즘)

  • Ahn, Yong-Jin;Kang, Sang-Hee;Lee, Seung-Jae
    • Proceedings of the KIEE Conference
    • /
    • 2001.05a
    • /
    • pp.259-261
    • /
    • 2001
  • An accurate digital distance relaying algorithm which is immune to the combined reactance effect of the fault resistance and the load current is proposed. The algorithm can estimate adaptively the impedance to a fault point independent of the fault resistance. To compensate the apparent impedance, this algorithm uses iteratively the angle of an impedance deviation vector improved step by step. The impedance correction algorithm for ground faults uses a current distribution factor to compensate mutual coupling effect.

  • PDF

Dynamic Response Characteristics of Distance Relay Including the Instrumental Devices (계기용 변성기를 포함한 거리계전기의 동특성 해석)

  • 김남호;박종근
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.41 no.3
    • /
    • pp.227-236
    • /
    • 1992
  • In this paper, a simulation program of relaying system including the CT and CPD ( capacitive potential device ) is developed to study the effect of its operation under various system conditions. To deal with the dynamic characteristics of relaying system, state space technique is applied, and then the state equations of CT, CPD and mho distance relay are constructed. Also the dynamic response characteristics of overall relaying system is verified by digital simulation. Since the proposed model is capable of taking arbitrary input waveforms from EMTP in analyzing its dynamic responses, the effects of CT-saturation and CPD-subsidence transient characteristics on the operating points of who distance relay can be accurately prodicted. It gives more effective results, compared with the model without considering those characteristics by checking the exprimental data.