• 제목/요약/키워드: Dielectric diagnosis

검색결과 49건 처리시간 0.025초

배전케이블 진단결과와 교류절연파괴강도의 상관성 (Relation between Dielectric Diagnosis and ACBD Strength in URD Cables)

  • 한재홍;김주용;김동명;이병성;정년호
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 추계학술대회 논문집
    • /
    • pp.484-487
    • /
    • 2000
  • This study is for assessing a reliability of diagnostic device through comparing diagnostic results to ACDB strength. The dielectric diagnosis using IRC (isothermal relaxation current) measurement was carried on service-aged cables. From this study, there was little correlation between dielectric diagnosis and ACBD strength in long distance cables. But the correlation between them showed in short distance below 200 m. Therefore, it is desirable to diagnose the URD cables in short distance.

  • PDF

Partial Discharge Measurements of Artificial Defects in HTS Transformer Model using HFCT

  • Lee, S.H.;Shin, W.J.;Park, T.G.;Koo, J.Y.;Lee, B.W.
    • Progress in Superconductivity
    • /
    • 제11권1호
    • /
    • pp.13-18
    • /
    • 2009
  • Partial discharge measurements in cryogenic dielectric materials of HTS transformer are very important because partial discharge was regarded as primary source for ageing and breakdown of cryogenic materials. But, partial discharge measurement techniques and its effects in low temperature high voltage environments were not suggested and there exist only a few reports on this research fields. Therefore, in order to implement reliable HTS transformers, partial discharge diagnosis techniques for cryogenic materials of HTS transformers were investigated using partial discharge (PD) pattern analysis methods. In this works, four different types of artificial defects including turn to turn insulation, free moving particle, void and protrusion, have been fabricated since it was commonly regarded that they might cause the sudden service failures of the power apparatus. For this purpose, these defects are installed into the dielectric materials in liquid nitrogen and experimental investigations have been carried out for the diagnosis of HTS transformer. And various PD patterns caused by the amount of quench of superconductors were analyzed. Throughout this works, the different PD patterns in cryogenic dielectric materials in liquid nitrogen, and PD measuring technique could be the fundamental steps to establish diagnosis technologies of HTS transformer for power applications.

  • PDF

6.6 kV 전동기 고정자 권선의 절연진단과 절연내력 평가 (Estimation of Insulation Diagnosis and Dielectric Strength in 6.6 kV Motor Stator Windings)

  • 김희동;공태식
    • 전기학회논문지
    • /
    • 제63권6호
    • /
    • pp.780-785
    • /
    • 2014
  • To assess the deterioration condition of stator insulation, diagnostic and AC dielectric strength tests were performed on five high voltage (HV) motors (2,000 HP, 6.6 kV) for boiler feed-water pump (BFP). Two HV motors for BFP were installed per unit. Following the long term rewinding program, the diagnostic test was performed on five 6.6 kV motors during the planning maintenance period. After completing diagnostic test, AC dielectric strength test was done on the stator windings of HV motors. The AC dielectric strength test was conducted at 15 kV for one minute. Dielectric strength test and diagnostics test results confirmed that the stator insulation was judged to be in serviceable condition in the five 6.6 kV motors.

22.9kV급 케이블 결함 검출을 위한 초저주파 실험 및 현장 진단 분석 (Analysis of Diagnosis and Very Low Frequency Experiment to Detect of Fault on 22.9kV Class Cable)

  • 김영석;김택희;김종민;송길목
    • 전기학회논문지
    • /
    • 제65권10호
    • /
    • pp.1780-1785
    • /
    • 2016
  • This paper presents few case studies of state diagnosis of XLPE cables using very low frequency techniques. The power cables of 22.9kV which have installation fault were assessed using VLF technique in addition to other techniques like insulation resistance and DC voltage withstand test. From the experimental results, The dielectric loss($tan{\delta}$) values of degradation of the cable(joint, knife, needle) at $U_0$ were 5.839, 5.526 and 6.251, respectively and all values were "further study advised". VLF PD measurement was also found defective portion. These method was effective in defect to fault in the degradation of the cable. However, the breakdown did not occur in the degradation of the cable because of properties of XLPE insulation. Few case studies of using VLF $tan{\delta}$ diagnosis for fault are measured and analyzed. The $tan{\delta}$ values at $U_0$ were "further study advised" or "action required".

표면온도분포 분석을 이용한 몰드 변압기 진단 (Diagnosis of Cast Resin Transformer Using Analysis of Surface Temperature Distribution)

  • 임용배;천종철
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 하계학술대회 논문집 Vol.4 No.1
    • /
    • pp.444-447
    • /
    • 2003
  • All objects with some temperature above absolute zero radiate in the infrared. The intensity of the infrared radiated from a object defends on the condition and temperature on the surface of the one. The present, these techniques are frequently adopted into diagnosis for electricity equipments. Simply, however, the applied techniques are passive thermal testing for the detection of loosened terminals and overcurrent. In this paper, a infrared thermal imager was applied to high voltage windings of cast resin transformers, and the accumulated value of the result temperatures was used for evaluating remained lifetime of them. At each aging level, dielectric loss tangent test was carried out. The results offered capabilities for deciding the condition of the transformers suffering difficulties to diagnose.

  • PDF

견인전동기의 고강예측 및 신뢰성 평가를 위한 복합가속열화 상태진단 - 고전압 인가에 따른 유전손실 및 부분방전 특성 연구 (Condition Diagnosis by the Complex Accelerating Degradation for Fault Prediction & Estimation of Reliability on the Traction Motor - Dielectric loss and PD Properties according to High Voltage)

  • 왕종배;백종현;변윤섭;박현준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 B
    • /
    • pp.1371-1373
    • /
    • 2000
  • In this paper, the complex accelerating degradation of traction motor driven with VVVF controlled inverter were performed on the form coil samples with the 200 Class insulation system. in order to evaluate the reliability and the long-term life. After aging, the dielectric and PD properties were investigated on the 10 cycles aging sample in the range of $20{\sim}160[^{\circ}C]$ and AC $250{\sim}2250[V]$ to diagnosis the condition of end-life and find the dominative factors of degradation.

  • PDF

전기절연유의 열화진단을 위한 정전용량 센서개발 (Development of Capacitive Sensor for the Diagnosis of Electrical Insulating Oil)

  • 최남호;김한준;김주한;김호수;한상욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1609-1611
    • /
    • 2003
  • This paper presents the results on the development of capacitive sensor for the diagnosis of electrical insulating oil, widely used for power transformer. To survey the dielectric properties of the new and used mineral insulating oil, we utilized the highly precise measuring system of KRISS. And the results were used to determine the design factors of the sensor. To evaluate the operational and the hysteresis characteristics of the sensor, we constructed a test chamber, including dielectric property measuring system. Through the results we could confirm the superior characteristics of the newly developed sensor.

  • PDF

In-situ Process Monitoring Data from 30-Paired Oxide-Nitride Dielectric Stack Deposition for 3D-NAND Memory Fabrication

  • Min Ho Kim;Hyun Ken Park;Sang Jeen Hong
    • 반도체디스플레이기술학회지
    • /
    • 제22권4호
    • /
    • pp.53-58
    • /
    • 2023
  • The storage capacity of 3D-NAND flash memory has been enhanced by the multi-layer dielectrics. The deposition process has become more challenging due to the tight process margin and the demand for accurate process control. To reduce product costs and ensure successful processes, process diagnosis techniques incorporating artificial intelligence (AI) have been adopted in semiconductor manufacturing. Recently there is a growing interest in process diagnosis, and numerous studies have been conducted in this field. For higher model accuracy, various process and sensor data are required, such as optical emission spectroscopy (OES), quadrupole mass spectrometer (QMS), and equipment control state. Among them, OES is usually used for plasma diagnostic. However, OES data can be distorted by viewport contamination, leading to misunderstandings in plasma diagnosis. This issue is particularly emphasized in multi-dielectric deposition processes, such as oxide and nitride (ON) stack. Thus, it is crucial to understand the potential misunderstandings related to OES data distortion due to viewport contamination. This paper explores the potential for misunderstanding OES data due to data distortion in the ON stack process. It suggests the possibility of excessively evaluating process drift through comparisons with a QMS. This understanding can be utilized to develop diagnostic models and identify the effects of viewport contamination in ON stack processes.

  • PDF

이종 비유전율에서 TDR을 이용한 PD발생 위치 추적방법 (Using the TDR in Dielectric for Partial Discharge Signals Detection Method)

  • 최문규;차한주
    • 전기학회논문지
    • /
    • 제64권9호
    • /
    • pp.1374-1379
    • /
    • 2015
  • Time Domain Reflectometry(TDR) using microwave bands, including broadband spectrum that occurs at the range of rates that start between partial discharge position it easier to make the techniques that could be measured. Partial discharge in the Gas Insulated Switchgear(GIS), the dielectric constant in the band more than GHz different the insulating material if you want to organize, and the insulating material regardless of how partial discharge position in the SF6 gas Partial Discharge by applying the heritability estimated its position, but the position error occurred about 23 percent of the existing way, correct in not suitable location tracking the outbreak PD. This technique the rate of other dielectric that make up the power apparatus heterology is measured at the function to slow the progression of the electromagnetic waves apart by calculating the partial discharge as the location, A simple way to track. Dielectric using other methods proposed new structure can calculate the speed of heritability PD is occurring can measure.

철도차량 견인전동기의 상태진단 및 상시감시 기술 (Condition Diagnosis & On-line Monitoring Technology on the Traction Motor for Railway Rolling Stock)

  • 왕종배;변윤섭;백종현
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 제2회 학술대회 논문집 일렉트렛트 및 응용기술전문연구회
    • /
    • pp.36-39
    • /
    • 2000
  • This paper presents the technology of condition diagnosis & life estimation on insulation system of the traction motor. In the non-destructive methods for diagnosis of coil insulation state, residual dielectric strength is estimated by the D-map which consist of the partial discharge quantity Q and average degradation degree $\Delta$. In the operating history of machine, the N-Y life estimation method is based on the stop-starting numbers and operating times with considering each degradation factor by the thermal, electrical and heat-cycle stress. With the on-line conditioning monitoring on the currents of traction motors, detecting the abnormal operating state due to bearing faults, stator or armature faults, eccentricity related faults and broken rotor bars can be performed.

  • PDF