전력케이블 열화 감시방안에 관한 연구 (A Study on Monitoring Means of Insulation deterioration of Electric Power Cable)

  • 한학수;민경윤;유기선
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2007년도 추계학술대회 논문집
    • /
    • pp.1522-1528
    • /
    • 2007
  • Electric Power cable is the apparatus that receives electric power from the Korea Electric Power Corporation and supplies electric power to electric train and annex facilities of each railway station. With substantial ripple effect during power blackout accidents, such power blackout accidents must be coped with by discriminating the status of insulation deterioration of electric power cable in advance. Discrimination of insulation deterioration of the electric power cable is normally executed while the power is disconnected and it is very difficult to discover, at early stage, the insulation deterioration of the power cable in operational state since the duration of inspection is limited. This research aims to consider method of diagnosing the insulation deterioration of electric power cable in On-Line state rather than diagnosis in Off-Line state in order to secure reliability of power supply by reducing duration of power blackout (accidental blackout and blackout during works) and by seeking reduction in equipment and manpower used in diagnosis of deterioration through prevention of the accident itself prior to occurrence through early restoration of accident due to insulation deterioration of the electric power cable and assessment of performance of the cable under operation.

  • PDF

전기철도 교/직 절연구분장치의 절연열화 현상 (Insulation Deterioration of AC/DC Section Insulators for Electric Railroad Catenary.)

  • 최규형
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제52권1호
    • /
    • pp.16-22
    • /
    • 2003
  • While passing through the AC/DC section insulators installed at electric railroad catenary, some electric trains undergo mis-operation of main circuit breaker after AC/DC change-over operation. This paper provides insulation resistance measurements of AC/DC section insulators, which confirm the insulation levels of section insulators are below the standard of insulators. The insulation deterioration and pantograph arrangement on the electric train can produce voltage impression on section insulator which induces mis-operation of main circuit breaker To mitigate the insulation deterioration of the section insulator installed at underground railroads, the section insulators have been cleaned periodically, but section insulator structure should be modified to make the section insulator performance perfect. Based on the above analysis, effective modification method of AC/DC section insulator is provided.

고압전동기 고정자 권선의 절연열화 평가 (Assessment of Insulation Deterioration in Stator Windings of High Voltage Motor)

  • 김희동;공태식
    • 전기학회논문지
    • /
    • 제61권5호
    • /
    • pp.711-716
    • /
    • 2012
  • To assess the insulation deterioration of stator windings, diagnostic and AC breakdown tests were performed on the eleven high voltage (HV) motors rated at 6kV. After completing the diagnostic tests, the AC overvoltage test was performed by gradually increasing the voltage applied to the stator windings until electrical insulation failure occurred, to obtain the breakdown voltage. Stator winding of motors 1, 3, and 8 failed at above rated voltage at 14 kV, 13.8kV, and 16.4kV, respectively. The breakdown voltage of three motors was higher than expected for good quality windings in 6kV motors. Based on deterioration evaluation criteria, the stator winding insulation of eleven HV motors are confirmed to be in good condition. The turning point of the current, $P_{i2}$, in the AC current vs. voltage characteristics occurred between 5kV and 6kV, and the breakdown voltage was low between 13.8kV and 16.4kV. There was a strong correlation between the breakdown voltage and various electrical characteristics in diagnostic tests including Pi2.

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

  • Kim, Hee-Dong
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권1호
    • /
    • pp.280-285
    • /
    • 2014
  • In order to evaluate the insulation deterioration in the stator windings of five gas turbine generators(137 MVA, 13.8 kV) which has been operated for more than 13 years, diagnostic test and AC dielectric breakdown test were performed at phases A, B and C. These tests included measurements of AC current, dissipation factor, partial discharge (PD) magnitude and capacitance. ${\Delta}I$ and ${\Delta}tan{\delta}$ in all three phases (A, B and C) of No. 1 generator stator windings showed that they were in good condition but PD magnitude indicated marginally serviceable and bad level to the insulation condition. Overall analysis of the results suggested that the generator stator windings were indicated serious insulation deterioration and patterns of the PD in all three phases were analyzed to be internal, slot and spark discharges. After the diagnostic test, an AC overvoltage test was performed by gradually increasing the voltage applied to the generator stator windings until electrical insulation failure occurred, in order to determine the breakdown voltage. The breakdown voltage at phases A, B and C of No. 1 generator stator windings failed at 28.0 kV, 17.9 kV, and 21.3 kV, respectively. The breakdown voltage was lower than that expected for good-quality windings (28.6 kV) in a 13.8kV class generator. In the AC dielectric breakdown and diagnostic tests, there was a strong correlation between the breakdown voltage and the voltage at which charging current increases abruptly ($P_{i1}$, $P_{i2}$).

Analysis of Insulation Quality in Large Generator Stator Windings

  • Kim, Hee-Dong;Kong, Tae-Sik;Ju, Young-Ho;Kim, Byong-Han
    • Journal of Electrical Engineering and Technology
    • /
    • 제6권3호
    • /
    • pp.384-390
    • /
    • 2011
  • To evaluate the condition of stator winding insulation in generators that have been operated for a long period of time, diagnostic tests were performed on the stator bars of a 500 MW, 22 kV generator under accelerated thermal and electrical aging procedures. The tests included measurements of AC current (${\Delta}I$), dissipation factor ($tan{\delta}$), partial discharge (PD) magnitude, and capacitance (C). In addition, the AC current test was performed on the stator winding of a 350 MW, 24 kV generator under operation to confirm insulation deterioration. The values of ${\Delta}I$, ${\Delta}tan{\delta}$, and PD magnitude in one stator bar indicated serious insulation deterioration. In another stator bar, the ${\Delta}I$ measurements showed that the insulation was in good condition, whereas the values of ${\Delta}tan{\delta}$ and PD magnitude indicated an incipient stage of insulation deterioration. Measurements of ${\Delta}I$ and PD magnitude in all three phases (A, B, C) of the remaining generator stator windings showed that they were in good condition, although the ${\Delta}tan{\delta}$ measurements suggested that the condition of the insulation should be monitored carefully. Overall analysis of the results suggested that the generator stator windings were in good condition. The patterns of PD magnitude in all three phases (A, B, C) were attributed to internal discharge.

고압회전기 절연열화진단의 현장적용기술연구 (A Study on Site Application Techniques for Insulation Reliability of Rotating Machine)

  • 김길용;조경해;김택수;한상욱;이현수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1991년도 하계학술대회 논문집
    • /
    • pp.286-291
    • /
    • 1991
  • Most of the failures of rotating machine are stator coil insulation failures. The insulation diagnostic testing for high voltage motors and generators are only megger test and P. I Test which is applied DC voltage until now. But it was impossible to judge insulation deterioration status of high voltage rotating machinery by above testing. In other words, even though the megger measurement values are fairly high, they used to be failed from time to time. Therefore in order to excute reliable and detailed diagnosis of insulation deterioration for rotating machinery, the tangent delta test, the alternating current test and the partial discharge test shall be applied to the insulation diagnostic testing on site.

  • PDF

수력발전기 고정자권선의 절연열화 분석 (A study on the Analysis of Insulation Aging for Generator stator windings)

  • 변두균;오봉근;강동식;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2072-2074
    • /
    • 2005
  • This test was performed to assess the insulation condition of the stator winding of 3.45kV hydro generator in insulation deterioration condition which was due to long service period(30years) since installed We extracted 12 stator wingdings from the hydro generator core, cut the stator windings into three parts(Middle winding part, slot winding part, end wingding part), and evaluated the insulation condition to know the deterioration condition of each parts. This insulation diagnostic tests include AC current, dissipation factor, and partial discharg test.

  • PDF

직류전압 감쇄성분 측정에 관한 CV케이블의 절연열화 예측 (Diagnostic method of Insulation Deterioration for CV cable Using D.C. Potential Decay Components)

  • 유명호;한민구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1989년도 하계종합학술대회 논문집
    • /
    • pp.323-328
    • /
    • 1989
  • In this paper, we studied the diagnostic method of insulation deterioration for 22.9kV CNCV cable using D.C potential decay component. At first, arbitrary D.C high voltage is appeied the CNCV cable for two minutes and switched off in vacuum. And then D.C potential decay components is measured for ten minutes. It is detecting source for cable insulation deterioration that its gradient is. Provisionally, we decided the criterion voltage and select the high voltage meter and S.W.

  • PDF

방전신호 검출에 의한 히팅 케이블의 상태감시기술 (Condition Monitoring Technique for Heating Cables by Detecting Discharge Signal)

  • 김동언;김남훈;임승현;길경석
    • 한국전기전자재료학회논문지
    • /
    • 제34권2호
    • /
    • pp.136-141
    • /
    • 2021
  • Heating cables, widely used in office buildings, factories, streets and railways, deteriorate in electrical insulation during operation. The insulation deterioration of heating cables leads to electric discharges that can cause electrical fires. With this background, this paper dealt with a condition monitoring technique for heating cables by the analysis of discharge signals to prevent electrical fires. Insulation deterioration was simulated using an arc generator specified in UL1699 under AC operation, and the characteristic and propagation of discharge signals were analyzed on a 100 meter-long heating cable. Discharge signals produced by insulation deterioration were detected as a voltage pulse because they are as small as a few mV and they are attenuated through propagation path. The frequency spectrum of discharge signals mainly existed in the range from 70 kHz to 110 kHz, and the maximum attenuation of the signal was 84.8% at 100 meters away from the discharge point. Based on the experimental results, a monitoring device, which is composed of a high pass filter with the cut-off frequency of 70 kHz, a comparator, a wave shaper and a microprocessor, was designed and fabricated. Also, an algorithm was designed to discriminate the discharge signal in the presence of noise, compared with the pulse repetition period and the number of pulse counts per 100ms. In the experiment, the result showed that the prototype monitoring device could detect and discriminate the discharge signals produced at every discharge point on a heating cable.

22.9kV 케이블 단말 부위 소손 사고의 원인에 관한 고찰 (A Consideration on the Causes of 22.9kV Cable Terminal Burning Accident)

  • 심헌
    • 사물인터넷융복합논문지
    • /
    • 제8권2호
    • /
    • pp.7-12
    • /
    • 2022
  • 케이블 사고의 주요 원인은 케이블 자체 또는 내·외적으로 전기적, 기계적, 화학적, 열적, 수분침입 등으로 인한 열화의 가속화로 절연성능 감소되고 절연파괴가 발생하여 케이블 사고를 유발하게 된다. 케이블 사고는 과전압, 과전류의 영향으로 절연이 불량한 부분에서 발생할 수 있으므로, 변압기, 차단기의 이상여부, 상간불평형에 의한 지락사고 등을 종합적으로 분석할 필요성이 있다. 케이블의 절연파괴에 의한 지락사고는 케이블 자체의 결함, 케이블 시공불량 뿐만 아니라 운영상의 영향, 전기설비(개폐기, 차단기 등)의 운전 시 아크 등에 의해 발생할 수 있어 사고시점을 전후로 운전 데이터 및 사고 이력에 대한 분석이 필요하다. 이 연구에서는 국내의 한 공장에서 발생한 케이블 사고의 분석을 통하여 케이블 사고의 원인을 고찰하고자 한다.