• 제목/요약/키워드: Deflagration index

검색결과 5건 처리시간 0.019초

The Influence of Pressure, Temperature, and Addition of CO2 on the Explosion Risk of Propylene used in Industrial Processes

  • Choi, Yu-Jung;Choi, Jae-Wook
    • Korean Chemical Engineering Research
    • /
    • 제58권4호
    • /
    • pp.610-617
    • /
    • 2020
  • In process installations, chemicals operate at high temperature and high pressure. Propylene is used as a basic raw material for manufacturing synthetic materials in the petrochemical industry; However, it is a flammable substance and explosive in the gaseous state. Thus, caution is needed when handling propylene. To prevent explosions, an inert gas, carbon dioxide, was used and the changes in the extent of explosion due to changes in pressure and oxygen concentration at 25 ℃, 100 ℃, and 200 ℃ were measured. At constant temperature, the increase in explosive pressure and the rates of the explosive pressure were observed to rise as the pressure was augmented. Moreover, as the oxygen concentration decreased, the maximum explosive pressure decreased. At 25 ℃ and oxygen concentration of 21%, as the pressure increased from 1.0 barg to 2.5 bar, the gas deflagration index (Kg) increased significantly from 4.71 barg·m/s to 18.83 barg·m/s.

원료의약품 분진의 폭발 위험성 평가 (Explosion Hazard Assessment of Pharmaceutical Raw Materials Powders)

  • 이주엽;이근원;박상용;한인수
    • Korean Chemical Engineering Research
    • /
    • 제55권5호
    • /
    • pp.600-608
    • /
    • 2017
  • 산업현장에서 취급되거나 가공되는 원료의약품 분진의 폭발 위험성은 항상 존재하며, 이로 인한 폭발사고가 자주 발생되고 있다. 본 연구에서는 원료의약품 시료 3종의 분진폭발특성을 측정하였다. 주요 폭발특성 측정값은 록소프로펜산은 평균 입경이 $5.31{\mu}m$이며, $P_{max}$는 8.4 bar, 최소점화에너지는 1 mJ < MIE < 3 mJ이며 최소점화온도는 $550^{\circ}C$이다. 클로피도그렐 캄포르술폰산염은 평균 입경이 $95.63{\mu}m$이며, $P_{max}$는 7.9 bar, 최소점화에너지는 30 mJ < MIE < 100 mJ이며 최소점화온도는 $510^{\circ}C$이었다. 리팜피신은 평균 입경이 $26.48{\mu}m$이며 $P_{max}$는 7.9 bar, 최소점화에너지는 1 mJ < MIE < 3 mJ이며 최소점화온도는 $470^{\circ}C$로 나타났다. 이들 값을 적용하여 폭연지수($K_{st}$)와 폭발지수(EI)의 폭발위험등급을 구하고, 원료의약품 분진의 폭발 위험성을 비교 검토하였다. 그 결과 폭발 위험성은 록소프로펜산과 리팜피신의 폭발등급은 St 2이고 폭발위험등급은 severe이며, 클로피도그렐 캄포르술폰산염의 폭발등급은 St 1이고 폭발위험등급은 strong으로 나타났다.

화재폭발지수 개선에 대한 사례 연구 (Case Study on Advanced Fire and Explosion Index)

  • 나건문;서재민;이미정;백종배
    • 한국안전학회지
    • /
    • 제35권6호
    • /
    • pp.78-84
    • /
    • 2020
  • The F&EI technique is one of the risk assessments with many advantages. It can save time and effort compared to quantitative risk assessment (QRA). By using the evaluation result of this technique, it is possible to check the effectiveness of the investment cost. In addition, a relative risk ranking can be created and used to establish the facility management cycle and to prioritize investment. However, evaluating the target process can be evaluated more than the actual risk since the LCCF, a loss prevention measure, is too limited. In addition, calculating premiums via this method can result in excessive premiums, making it difficult to evaluate the risk precisely. Therefore, new safety guard was added to the LCCF of the F&EI risk assessment with reference to HAZOP and LOPA techniques. Newly added LCCFs are Deflagration arrester, Check valve, SIS, and Vacuum beaker, etc. As a case study, F&EI risk assessment was performed on Acetone storage tank of a API (Active pharmaceutical ingredient) plant to compare actual MPPD. The estimated loss amount was 592,558$ for the existing technique and 563,571$ for the improved technique, which was reduced by about 5% compared to the previous one.This proved that a more precise evaluation is possible and that the efforts for safety at the workplace are reflected in the evaluation results.

반응성 유기물 분진의 폭발특성과 열안정성 (Explosion Properties and Thermal Stability of Reactive Organic Dust)

  • 한우섭;한인수;최이락;이근원
    • 한국가스학회지
    • /
    • 제15권4호
    • /
    • pp.7-14
    • /
    • 2011
  • 20 L 구형 폭발시험장치와 시차주사열량계(DSC)를 사용하여 반응성 유기물 분진의 폭발 및 열분해 특성을 실험적으로 조사하였다. 그 결과 97 % Benzoyl peroxide(BPO), Phthalic anhydride(PA), 1-Hydroxybenzotri azol(HBT)의 폭발하한은 매우 낮은 농도인 10~15 g/$m^3$의 범위로 측정되어 착화위험성이 높은 것으로 나타났다. HBT, PA 및 97 % BPO의 폭발지수는 각각 251, 146, 80 [bar m/s]로서, HBT는 폭발등급 2에 해당한다. 또한 밀폐계 분진폭발의 화염전파 특성을 추정하기 위하여 용기면에의 화염도달시간과 폭발압력을 고려하여 화염전파속도를 예측하였다. 97 % BPO 및 HBT의 열분해 개시온도와 발열량은 각각 $107^{\circ}C$(1025 J/g), $214^{\circ}C$(1666 J/g)로 나타났는데, 이와같이 낮은 열분해 온도와 큰 발열량이 폭발특성에 영향을 주는 것으로 판단된다.

수평 배관의 메탄 폭발특성에 있어서 불균일성 혼합기의 영향 (Influence of Mixture Non-uniformity on Methane Explosion Characteristics in a Horizontal Duct)

  • 한우섭;최이락;김형욱;임진호
    • Korean Chemical Engineering Research
    • /
    • 제62권1호
    • /
    • pp.27-35
    • /
    • 2024
  • 메탄, 프로판 등을 주성분으로 하는 연료가스는 폭발위험장소에서 사용될 수 있으며, 누출로 인한 공정조건의 영향으로 불균일한 혼합기를 형성할 수 있다. 균일한 혼합기를 대상으로 측정된 문헌 데이터를 이용한 화재 폭발 위험성 평가, 손상 예측은 가스 누출에 의한 실제 폭발 사고와 다른 결과를 얻을 수 있다. 본 연구에서는 가스 누출시 나타날 수 있는 농도 변화에 있어서 불균일성 혼합기의 폭발압력, 화염속도 등의 폭발특성을 조사하였다. 길이 0.82 m의 스테인리스 재질의 밀폐 배관에서 수행하였으며 컬러 초고속 카메라 및 압력 센서를 사용하여 관찰하였다. 또한 배관 내의 시간에 따른 농도차이 변화에 대해 회귀분석 모델을 사용하여 불균일 혼합물의 정량화 방법을 제안하였다. 본 연구의 농도 불균일성 조건에 있어서 메탄 폭발 시 전파화염은 불균일성 농도가 높아짐에 따라 화염 면적의 증가가 관찰되었고 이는 난류 화염의 주름진 화염 구조와 유사하였다. 메탄의 최대압력까지 걸리는 소요시간은 불균일성이 클수록 감소하였고, 폭발압력은 불균일성이 클수록 증가하였다. 농도가 불균일한 메탄의 KG(폭연지수)의 범위는 1.30~1.58 [MPa·m/s]으로서 메탄의 농도가 균일성에서 불균일성로 변화하면서 17.7% 증가하였다.