• 제목/요약/키워드: Defect of insulation

검색결과 103건 처리시간 0.023초

수력발전기 고정자 노후권선의 모의결함 시편에 대한 부분방전 파라미터 변화 분석 (Analysis of Parameters on Partial Discharges from Insulation Defects of used Hydro Generator Stator Windings)

  • 오봉근;김현일;강성화;임기조
    • 한국전기전자재료학회논문지
    • /
    • 제20권7호
    • /
    • pp.645-649
    • /
    • 2007
  • Partial discharge(PD) test for simulated insulation defects of used hydro generator stator winding was conducted to analyze the PD Parameters. Simulated insulation defects are classified by 5 types corona, slot, internal, multi and aging defect. Phase resolved partial discharge, statistical parameter (skewness, kurtosis), PD magnitude as a function of the test voltage(Q-V curve) and PD magnitude change under test voltage for 2 minutes are used as PD parameters. The analysis of PD parameters by 4 types are proved to be useful methods. In particular, PD parameter characteristics of aging defect could help to assess the aging condition of stator winding because aging defect has more weak insulation strength than other insulation defects : PD distribution is wide and flat, PD rises rapidly near $0^{\circ}\;and\;180^{\circ}$ and Q-V curve rises sharply and then gently drops.

견인전동기 고정자 권선의 절연상태 분석 (Analysis of Insulation Condition in Traction Motor Stator Windings)

  • 김희동;박영
    • 한국전기전자재료학회논문지
    • /
    • 제20권7호
    • /
    • pp.631-635
    • /
    • 2007
  • Diagnostic, surge and ac breakdown tests are widely used to evaluate the insulation condition of stator winding in traction motor. Diagnostic test included ac current, tan delta and maximum partial discharge. The result of diagnostic test indicates that five kinds of stator windings are good condition. Surge test was peformed to confirm the healthy of turn insulation in stator windings. This test is very easy to detect the turn insulation failure between normal and defect stator windings. After completing the diagnostic test, ac breakdown test has conducted gradually increasing ac voltage, until the stator winding punctured. No. 5 stator windings failed near rated voltage of 18.9 kV The breakdown voltage of No. 1 stator windings was 13.0 kV The ac breakdown voltage of normal winding is about 1.45 times higher than that of defect windings. The failure was located in a line-end coil at the exit from the core slot.

고체절연체의 내부결함에 따른 부분방전 특성과 패턴분류 (Properties of PD and Classification of Defect Patterns in Solid Insulation)

  • 강성화;박영국;이광우;김완수;이용희;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 D
    • /
    • pp.1624-1626
    • /
    • 1999
  • PD in defect of solid insulation system is very harmful since It often leads to deterioration of insulation by the combined action of the discharge ions bombarding the surface and the action of chemical compounds that are formed by the discharge. PD can indicate incipient failure, so it has been used to determine degradation of insulation. In this paper. we investigated PD in defects of solid insulation by using statical method and classified PD patterns with surface discharge, electrical tree and void discharge by using Kohonen network. we used peak charge, average discharge power, average discharge current, repetition rate, skewness, kurtosis, QN of the max pulse height vs. repetition rate $H_q(n)$ for analysis and classification.

  • PDF

펄스 Nd:YAG 레이저를 이용한 모터용 스테이터 적층코어의 용접특성 [II] - 용접결함의 형성 메커니즘 규명 - (The Weldability of Laminated Stator Core for Motor by Pulsed Nd:YAG Laser [II] - Investigation of Mechanism on Formation of Weld Defect -)

  • 김종도;길병래;이창제
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제30권5호
    • /
    • pp.636-644
    • /
    • 2006
  • Recently, there were some successful examples that the laser welding was introduced into production line. However, the spread of laser welding is not sufficient in many industries. There are several reasons why it is difficult to penetrate the laser welding into production lines. Because it is different from reflection, absorption and permeation of laser beam according to material and surface condition. Moreover, there are significant problems in processing such as absorption and scattering of beam by the induced plasma or plume. Therefore, understanding of mechanism on formation of weld defect in laser welding of the laminated core for motor is very important. In this paper, it was analyzed in terms of materials which was source of defect in laser welding and conventional arc welding. As a results of analysis, insulation coating film of the laminated core was judged to main factor of weld defect. it could be well aware as tracing carbon volume, and it was deduced that weld defect by insulation coating film was caused by difference of mechanism between the two heat sources.

적외선 열화상을 이용한 공동주택 단열성능 평가 : TDR(온도차비율)을 중심으로 (Thermal Performance Evaluation of Apartment Housing Using Infra-red Camera)

  • 최경석;손장열
    • 설비공학논문집
    • /
    • 제22권6호
    • /
    • pp.404-412
    • /
    • 2010
  • The purpose of this study is to accomplished an in-site evaluation method for existing building insulation status using Infra-red camera and to consider improvement performance to prevent condensation and draw the optimum insulation design method for building using simulation tool. The research contents of this study are to evaluate validity and suitability of building insulation defect survey using Infra-red camera for apartment housing with temperature and heat flow pattern analyze method. Based on this research, the three corners, weak part in condensation, were selected in apartment building and conducted simulation by three-dimensional steady state. From the results, it is required to strengthen insulation design, and it is founded that existing insulation system typically applied to most Korean apartment housings have serious insulation defect that insulation is disconnected by structural components at the joints of wall-slab and wall-wall in envelope. Thus, it is considerate to need a concrete technology improvement.

절연계의 결함별 부분방전 패턴분석 (Analysis of PD Patterns Depending on Defect Types in Insulation System)

  • 박찬용;김황국;김성욱;지홍근;길경석
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2009년도 춘계학술대회 논문집
    • /
    • pp.912-918
    • /
    • 2009
  • In this paper, we carried out a comparative analysis of partial discharge(PD) patterns caused by deterioration of cast-resin and oil insulation systems. Various electrode systems were fabricated such as needle-needle, needle-plane and plane-plane to simulate defects that may exist in the insulation system of transformers. A low-noise amplifier which has a gain of 40 dB and a frequency bandwidth of 500 kHz $\sim$ 30 MHz (-3 dB) was designed to detect small PD signals. From the analysis of acquired PD signals, we could find that a unique PD pattern is formed according to types of defect. These data will be applied usefully to diagnose insulation condition of transformers.

  • PDF

에폭시/고무 계면에서의 결함에 따른 부분방전 특성 (Chracteristics of Partial Discharge Patterns Subjected to Different Defects at the Epoxy/Rubber Interface)

  • 김동욱;김정년;백주흠
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제51권5호
    • /
    • pp.199-204
    • /
    • 2002
  • In order to recognize the deterioration of insulation system by partial discharge (PD), the characteristics of PD patterns which are occurring at the interface between epoxy and rubber materials in extra high voltage cable joints, have been investigated. The artificial defects such as voids, metal particles, insulation fiber and water impregnated insulation fiber are planted between the interfaces. A high frequency partial discharge detection system was used for measuring PD signals. An analysis of the PD patterns is focused on the shape of PD pattern, phase, width and time-dependence for each artificial defect. The PD Patterns in each defect show the different behaviors and it is suggested that the precise discrimination of PD patterns could be used for the diagnosis of deterioration in the insulation systems.

부분방전 패턴을 이용한 가교폴리에틸렌에서의 트리성장에 관한 연구 (The Study on tree growth in XLPE using PD patterns)

  • 강대용;오광영;신창면;박명섭;조규복;황보승;박대희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.941-943
    • /
    • 1998
  • Exploitation of equipment with cross linked polyethylene (XLPE) insulation requires its condition monitoring and diagnostic. Traditionally diagnostics of insulation is carried out by means of partial discharge detection. Many researchers have developed a lot of methods to identify the defect by the PD form. However, such identification of a defect, for example, void, inclusion or treeing, does not say about its danger from a point of view of full insulation gap breakdown and insulation construction failure. The information about the form and size of formed upon high voltage treeing is necessary for prediction of the remained resource of XLPE insulation. For this purpose we carry out experimental research for determination of the dependencies between PD characteristics in XLPE upon time and three dimension PD patterns of corresponding treeing. The investigations were carried out by means of electrical measurement of PD current and simultaneous optical recording of treeing image. Test results show that the PD patterns can be applied for detecting tree growth well.

  • PDF

Partial Discharge Pattern Recognition of Cast Resin Current Transformers Using Radial Basis Function Neural Network

  • Chang, Wen-Yeau
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권1호
    • /
    • pp.293-300
    • /
    • 2014
  • This paper proposes a novel pattern recognition approach based on the radial basis function (RBF) neural network for identifying insulation defects of high-voltage electrical apparatus arising from partial discharge (PD). Pattern recognition of PD is used for identifying defects causing the PD, such as internal discharge, external discharge, corona, etc. This information is vital for estimating the harmfulness of the discharge in the insulation. Since an insulation defect, such as one resulting from PD, would have a corresponding particular pattern, pattern recognition of PD is significant means to discriminate insulation conditions of high-voltage electrical apparatus. To verify the proposed approach, experiments were conducted to demonstrate the field-test PD pattern recognition of cast resin current transformer (CRCT) models. These tests used artificial defects created in order to produce the common PD activities of CRCTs by using feature vectors of field-test PD patterns. The significant features are extracted by using nonlinear principal component analysis (NLPCA) method. The experimental data are found to be in close agreement with the recognized data. The test results show that the proposed approach is efficient and reliable.

전력케이블 절연재료의 내부결함에 따른 전기적 특성 (Electrical Characteristics due to Inner Defect of Insulating Materials for Power Cable.)

  • 최상기;김탁용;김왕곤;홍진웅
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 추계학술대회 논문집 Vol.16
    • /
    • pp.27-30
    • /
    • 2003
  • Recently, on power system, it is used to high voltage of transmission and distribution due to safe power supply and have high quality and insulation in order to satisfy excellent insulator. Thus, according to underground of high voltage cable, is occurred break down by ground short. Therefore, it is used to high quality XLPE power cable to interrupt instantaneous voltage drop. If it appear inner defect for cable whose have high quality and insulation, it is reduced rapidly due to concentration of electrical field. After assemble to manufacture, in order to inspect cable condition, it is decided much inspection standard. In this paper, In inner defect of assembling cable at manufacture, for measure the variation of insulation condition by void. it tested the variation of insulating characteristics, using $\phi$-q-n distribution variation in partial discharge experiment.

  • PDF