• Title/Summary/Keyword: DGs Installation

Search Result 21, Processing Time 0.023 seconds

Power Control and Ground Fault Simulations for a Distribution System with a Fuel Cell Power Plant

  • Hwang, Jin-Kwon;Choi, Tae-Il
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.7
    • /
    • pp.9-19
    • /
    • 2010
  • Fuel cell (FC) distributed generation (DG) is gradually becoming more attractive to mainstream electricity users as capacity improves and costs decrease. New technologies including inverters are becoming available to provide a uniform standard interconnection of DGs with an electric power system. Some of the operating conflicts and the effect of DG on power quality are addressed and investigated through simulations on a real distribution network with an FC power plant. The results of these simulations have proved load tracking capability following the real and reactive power change of the load and have shown the flow of overcurrent from an FC power plant during the ground fault of a distribution line.

Application of Directional Over Current Protection Schemes Considering the Fault Characteristics in the Distribution System with Dispersed Generation (분산전원이 연계된 배전계통의 고장특성을 고려한 방향성 보호계전 방식 적용 연구)

  • Jung, Won-Wook;Lee, Hak-Ju;Kwon, Seong-Chul;Chae, Woo-Kyu
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.9
    • /
    • pp.97-107
    • /
    • 2010
  • Penetration of distributed generator(DG) to power distribution system can cause malfunction of existing protection schemes. Because grid interconnected DG can contribute fault currents and make bidirectional current flows on the system, fault contributions from DG can cause an interference of protection relay operation. Therefore, over current protection device of the distribution system with DGs need directional protection schemes. In this paper, improved directional protection algorithms are proposed for the distribution system with DG considering their fault characteristics. And than, these directional protection algorithms are tested and validated in various fault conditions. From the simulation results, it can be seen that the proposed directional protection algorithms are practically efficient for the radial distribution system with DG.

Placement and Operation of DG System for Reliability Improvement in Distribution Systems (배전계통의 신뢰도 향상을 위한 분산형전원의 설치 및 운영)

  • Kim Kyu Ho;Lee Sang Keun;Kim Jin O;Kim Tae Kyun;Jeon Dong Hun;Cha Seung Tae
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.348-350
    • /
    • 2004
  • This paper presents the scheme for reliability improvement by dispersed generation system (US) installation and operation in distribution systems. The objective functions such as power losses cost, operation cost of DGS, power buy cost and interruption cost are minimized for reliability improvement. The original objective functions and constraints are transformed into the equivalent multiple objective functions with fuzzy sets to evaluate their imprecise nature. The several indices for reliability evaluation are improved by dispersed generation system installation.

  • PDF

Configurations of AC and DC-type Quality Control Center for a New Distribution System FRIENDS

  • Hayashi Yusuke;Saisyo Masaki;Ise Toshifumi;Tsuji Kiichiro
    • Proceedings of the KIPE Conference
    • /
    • 2001.10a
    • /
    • pp.497-501
    • /
    • 2001
  • Unbundled power quality service is paid much attention under the circumstances of deregulation and diversification of needs of customers for quality and price of electric power. Moreover, distributed generators (DGs) such as photovoltaic generations and wind turbines will be introduced to distribution system more and more, and reverse flow of active power has possibility to cause new problems in the distribution system such as voltage rise of distribution line and protection problem. Flexible, Reliable and Intelligent Electrical eNergy Delivery System, which is called FRIENDS, has been proposed as one of promising distribution system for such requirements, and intensive studies are under way. One of features of the system is introducing Quality Control Center (QCC) into the system for unbundled power quality service and easy installation of DGs. Two types of QCCs for such purposes are proposed, and simulation results are shown in this paper.

  • PDF

Development of a Transmission/Distribution Integrated Analysis Hybrid Algorithm for System Operation Platform Including Distributed Generation (분산전원을 포함하는 시스템 운용 플랫폼을 위한 송배전 통합 해석 하이브리드 알고리즘 개발)

  • Song, Chong-Suk;Suh, Jae-Wan;Jang, Moon-Jong;Jang, Gil-Soo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.1
    • /
    • pp.35-45
    • /
    • 2013
  • Owing to the increase in the penetration of distributed generation the DGs connected to the distribution system have an effect on the system conditions of the transmission system and neighboring distribution systems. This makes the separate analysis of the transmission and distribution system no longer valid and requires the consideration of both the system in the analysis process. This paper proposes a transmission/distribution integrated analysis hybrid algorithm that would ensure the accurate analysis of the system by reflecting the results of the transmission and distribution system analysis on each other. Different scenarios are being analysed in order to verify the effectiveness of the hybrid algorithm by observing the effects of the DG connected distribution system on the transmission system and neighboring distribution systems. The algorithm and simulations performed are being conducted by MATLAB and the IEEE 30 bus system and a test distribution system has been utilized for the transmission and distribution systems respectively.

Phasor Discrete Particle Swarm Optimization Algorithm to Configure Community Energy Systems (구역전기사업자 구성을 위한 Phasor Discrete Particle Swarm Optimization 알고리즘)

  • Bae, In-Su;Kim, Jin-O
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.9
    • /
    • pp.55-61
    • /
    • 2009
  • This paper presents a modified Phasor Discrete Particle Swarm Optimization (PDPSO) algorithm to configure Community Energy Systems(CESs) in the distribution system. The CES obtains electric power from its own Distributed Generations(DGs) and purchases insufficient power from the competitive power market, to supply power for customers contracted with the CES. When there are two or more CESs in a network, the CESs will continue the competitive expansion to reduce the total operation cost. The particles of the proposed PDPSO algorithm have magnitude and phase angle values, and move within a circle area. In the case study, the results by PDPSO algorithm was compared with that by the conventional DPSO algorithm.

Optimal Coordination of Overcurrent Relays in the Presence of Distributed Generation Using an Adaptive Method

  • Mohammadi, Reza;Farrokhifar, Meysam;Abyaneh, Hossein Askarian;Khoob, Ehsan
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.6
    • /
    • pp.1590-1599
    • /
    • 2016
  • The installation of distributed generation (DG) in the electrical networks has numerous advantages. However, connecting and disconnecting of DGs (CADD) leads to some problems in coordination of protection devices due to the changes in the short circuit levels in the different points of network. In this paper, an adaptive method is proposed based on available setting groups (SG) of relays. Since the number of available SG is less than possible CADD states, a classifying index (CI) is defined to categorize the several states in restricted setting groups. Genetic algorithm (GA) with a suitable objective function (OF) is used as an optimization method for the classification. After grouping, a modified coordination method is applied to achieve optimal coordination for each group. The efficiency of the proposed technique is demonstrated by simulation results.

Reliability estimation and optimal capacity and allocation by distributed generation installation (분산전원 설치에 따른 신뢰도 평가와 최적용량과 위치결정)

  • Park, Jung-Hoon;Shin, Dong-Suk;Kim, Jin-O;Kim, Kyu-Ho;Cho, Jong-Man
    • Proceedings of the KIEE Conference
    • /
    • 2003.11a
    • /
    • pp.151-153
    • /
    • 2003
  • This paper proposes determining a optimal number, size and allocation of DGs(Distributed Generations) needed to minimize operation cost of distribution system, obtains economic benefit in operation planning of DG and improves system reliability. System reliability is assessed whether DG install and reliability cost consider. DG optimal allocations are determined to minimize total cost with power buying cost, operation cost of DG, loss cost and outage cost using GA(Genetic Algorithm). And it was determined installed load-point and order.

  • PDF

A Study of the Mitigating Effect Comparison of Voltage Sags by WTG Types Based on the Concept of Area of Vulnerability (타입별 풍력 발전기 설치에 따른 민감 부하의 순간전압강하 저감 효과 비교 분석 연구)

  • Park, Se-Jun;Yoon, Min-Han
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.66 no.12
    • /
    • pp.1682-1688
    • /
    • 2017
  • In modern society, the number of industrial customers using equipment sensitive particularly to voltage sags is rapidly increasing. As voltage sags can cause loss of information as well as false operation of the control device, it results in the vast economic damage in industrial processes. One way to mitigate voltage sags in the sensitive loads is the installation of distributed generation (DGs) on the periphery of these loads. In addition, renewable energy sources are currently in the spot light as the potential solution for the energy crisis and environmental issues. In particular, wind power generation which is connected to a grid is rising rapidly because it is energy efficient and also economically feasible compared to other renewable energy sources. On the basis of the above information, in this paper, with Wind Turbine Generators (WTGs) installed nearby the sensitive load, the analysis of the mitigating effect comparison by types of WTGs is performed using voltage sag assessment on the IEEE-30 bus test system. That is, the areas of vulnerability according to types of WTGs are expected to be different by how much reactive power is produced or consumed as WTG reactive power capability is related to the types of WTGs. Using the concept of 'Vulnerable area' with the failure rate for buses and lines, the annual number of voltage sags at the sensitive load with the installation of WTGs per type is studied. This research will be anticipated to be useful data when determining the interconnection of wind power generation in the power system with the consideration of voltage sags.

A Study on SFCL with IGBT Based DC Circuit Breaker in Electric Power Grid

  • Bae, SunHo;Kim, Hongrae;Park, Jung-Wook;Lee, Soo Hyoung
    • Journal of Electrical Engineering and Technology
    • /
    • v.12 no.5
    • /
    • pp.1805-1811
    • /
    • 2017
  • Recently, DC systems are considered as efficient electric power systems for renewable energy based clean power generators. This discloses several critical issues that are required to be considered before the installation of the DC systems. First of all, voltage/current switching stress, which is aggravated by large fault current, might damage DC circuit breakers. This problem can be simply solved by applying a superconducting fault current limiter (SFCL) as proposed in this study. It allows a simple use of insulated-gate bipolar transistors (IGBTs) as a DC circuit breaker. To evaluate the proposed resistive type SFCL application to the DC circuit breaker, a DC distribution system is composed of the practical line impedances from the real distribution system in Do-gok area, Korea. Also, to reflect the distributed generation (DG) effects, several DC-to-DC converters are applied. The locations and sizes of the DGs are optimally selected according to the results of previous studies on DG optimization. The performance of the resistive type SFCL applied DC circuit breaker is verified by a time-domain simulation based case study using the power systems computer aided design/electromagnetic transients including DC (PSCAD/ EMTDC(R)).