• Title/Summary/Keyword: DC railway

Search Result 243, Processing Time 0.031 seconds

An Experimental Study on Operation Setting Optimization of Circuit Breaker for Improving Safety on DC Railroad Feeder System (직류철도 급전계통의 안전성 향상을 위한 차단기 동작 최적 설정의 실험적 고찰)

  • Lee, Jae-Bong;Jung, No-Geon;Kim, Jae-Moon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.3
    • /
    • pp.526-531
    • /
    • 2016
  • This paper presents an experimental study on the optimal settings for the selected DC fault relay (50F) to improve the operating performance for the high-speed circuit breaker on DC feeding system which ensure safety within rolling stock maintenance depot. In this study, current supplied to overhead contact wire was calculated on 1 ms interval to analyze the correction values of DC fault selective relay for the operation of current supply cutout. Particularly, standards for the accurate detection of accidents between an electric railway vehicle and the electric power facilities are shown by investigating the optimal correction values for detection of fault current, and the results indicated that it takes about 213 ms for the DC fault selective relay(50F) to fully open. In the future, the correction values of DC fault selective relay suggested in this paper will be used as the reference values of protective relay for the safe operation of DC electric railroad system such as urban railway.

Derivation of Real-time Monitoring System for Power Supply System in Metro Substation (도시철도 변전소 전력설비 실시간 모니터링 방안 도출)

  • Jung, Ho-Sung;Park, Young;Oeu, Soo-Young
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.23 no.4
    • /
    • pp.333-337
    • /
    • 2010
  • This paper introduces an overall system design of a real-time monitoring system that monitors condition of urban railway AC/DC transformers, disconnecting switches, circuit breakers, regulators, and GIS (gas insulated switchgear). For effective diagnosis of urban railway facilities we developed optimized sensors and application technology. The proposed system is combined with wireless technology, implementing remote real-time monitoring of urban railway facilities. The derived real-time monitoring system for power facilities in urban railway substations will be applied not only to diagnose low voltage DC (direct current) railways but also to diagnose design of small power facilities of skyscrapers and apartments.

Comparison Analysis of Field Test Methods Based on Technical Criteria of Electrolytic Corrosion Protection in Urban Railway (도시철도 전식방지 기술기준에 따른 시험방법 비교분석)

  • Kim, Jae-Moon;Jung, Ho-Sung
    • Proceedings of the KSR Conference
    • /
    • 2010.06a
    • /
    • pp.1885-1891
    • /
    • 2010
  • Recently metropolitan local governments is actively introducing urban railway's expand and light rail transit as a means of new transport system. DC electricity feeder system operating in the domestic urban railway is typically a feedback circuit consisted of the contact wire and electric railway vehicle via rail. But stray current is to be defined as a current flowing on a structure that is not part of the intended electrical circuit with respect to a given structure. Stray current is generally results from the leakage of return currents from large DC traction systems that are grounded or have a bad earth-insulated return path. At the place where the current leaves the rail and metallic structures, electrolytic corrosion may take place. This paper presents comparison analysis of field test methods based on criteria of electrolytic corrosion protection of buried metallic structures adjacent to DC traction systems.

  • PDF

A Study on Peak Power Reduction using Regenerative Energy in Railway Systems through DC Subsystem Interconnection

  • Jung, Seungmin;Lee, Hansang;Kim, Kisuk;Jung, Hosung;Kim, Hyungchul;Jang, Gilsoo
    • Journal of Electrical Engineering and Technology
    • /
    • v.8 no.5
    • /
    • pp.1070-1077
    • /
    • 2013
  • Owing to the consistent increase in energy efficiency issues, studies for improving regenerative energy utilization have been receiving attention in the Urban DC railway systems, where currently, the utilization of regenerative energy is low due to the lack of a specific plan for using this energy. The regenerative energy in railway systems has a low efficiency problem which results in the increase of the catenary voltage and a possibility to create problems to the electrical devices connected to the system. This paper deals with the power integration of large urban railway subsystems to improve regenerative energy utilization where the railway subsystems are integrated with other railway subsystems to improve the energy efficiency. Through the case studies, to find the realistic effect of integrated operation, the Seoul Metro subsystems, namely Line 5 and Line 7, has been applied. Also, evaluation for the electricity cost saving has been performed by using KEPCO electricity cost table.

Comparison and Analysis of Boost Converter Topologies for the DC/DC Converter in Hydrogen Fuel Cell Hybrid Railway Vehicle (수소연료전지 하이브리드 철도차량용 DC/DC 컨버터를 위한 부스트 컨버터 토폴로지 비교 및 분석)

  • Kang, Dong-Hun;Lee, Il-Oun;Lee, Woo-Seok;Yun, Duk-Hyeon
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.25 no.4
    • /
    • pp.269-278
    • /
    • 2020
  • In this paper, two types of DC/DC converters in a hydrogen fuel cell hybrid railway vehicle system, which serve to charge high-voltage battery and supply power to an inverter for driving a driving motor, were compared and analyzed. A two-level interleaving boost converter and a three-level boost converter were compared and analyzed, and a theoretical design method was proposed to have an efficiency characteristic of over 95%. In addition, a digital controller design method considering the digital phase delay component of DSP (TMS320F28335) is presented. Finally, the validity of the theoretical design of the converter with 20kW power was verified through static and dynamic experiments respectively.

Direction for Development of Energy Regeneration Device for DC Electric Railway System (DC전철구간의 에너지회생장치 개발 방향)

  • Kim, Yong-Ki;Bae, Chang-Han;Han, Moon-Seob;Yang, Young-Chul;Jang, Su-Jin
    • Proceedings of the KSR Conference
    • /
    • 2007.05a
    • /
    • pp.804-808
    • /
    • 2007
  • when electric traction system used DC 1500V runs on decline of rail road track and slows down, Dc voltage goes beyond regular voltage. In this case extra power is forcibly wasted by resister because rectifier of substation and electric train including power converter and so on are out of order. This paper described a DC electric railway system, which can generate the excessive DC power form DC bus line to AC source in substation for traction system. The proposed regeneration inverter system for DC traction can be used as both an inverter and an active power filter(APF). As a regeneration inverter mode, it can recycle regenerative energy caused by decelerating tractions and as an active power filter mode, it can compensate for harmonic distortion produced by the rectifier substation. In addition, electric traction system products harmonic current and voltage distortion and reactive power because power converter is used so regeneration inverter normally runs such as active power filter(APF) for improving power quality. From the viewpoint of both power capacity and switching losses, the system is designed on the basis of three phase PWM inverters and composed of parallel inverters, output transformers, and an LCL filter.

  • PDF

The design of adaptive Controller for the Voltage Bus Conditioner for the improvement of the Power Quality in the DC Power Distribution System (DC 배전시스템의 품질향상을 위한 VBC 적응제어)

  • Woo, Hyun-Min;Lee, Byung-Hun;Chang, Han-Sol;La, Jae-Du;Kim, Young-Seok
    • Proceedings of the KSR Conference
    • /
    • 2011.10a
    • /
    • pp.2348-2356
    • /
    • 2011
  • In recent years, many researches for DC power distributed system (PDS) are being preformed and the importance of the DC PDS is more and more emphasized. Furthermore, in the railway system, the DC PDS is used in subway station lighting, facilities, etc. In the DC PDS, DC bus voltage instability may be occurred by the operation of multiple parallel loads such as pulsed power load, motor drive system, and constant power loads. Thus, good quality and high reliability for electric power are required and voltage bus conditioner (VBC) may be used the DC PDS. The VBC is a DC/DC converter for mitigation of the bus transients. In this paper, adaptive controller is designed. The simulation results by PSIM are presented for validating the proposed control algorithm.

  • PDF

A Main Power Supply for Railway Vehicles using 3-level converters (3레벨 컨버터를 이용한 철도차량용 주 전력변환장치)

  • Rho Sung-Chan;Kim Yoon-Ho
    • Proceedings of the KSR Conference
    • /
    • 2003.10c
    • /
    • pp.646-652
    • /
    • 2003
  • AS a main Power Supply of the Railroad Vehicles, a three-Level ZVZCS DC/DC Converter is proposed in this paper. The proposed three-Level DC/DC Converter achieves zero voltage and zero current switching for the main switches. Its attribute is that the voltage across the switches is half the value of the input voltage. Also. using a diode and secondary side of the transformer, and simple auxiliary circuits it achieves zero current switching of the auxiliary switches. The principle operation and simulation results are included.

  • PDF

A Fault Detection and Location Algorithm Using a Time Constant for DC Railway Systems (시정수를 이용한 직류철도급전계통에서의 고장판단 및 고장점표정 알고리즘)

  • 양언필;강상희;권영진
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.10
    • /
    • pp.563-570
    • /
    • 2003
  • When a fault occurs on railway feeders it is very important to detect the fault to protect trains and facilities. Because a DC railway system has low feeder voltage, The fault current can be smaller than the current of load starting. So it is important to discriminate between the small fault current and the load starting current. The load starting current increases step by step but the fault current increases at one time. So the type of $\Delta$I/ relay(50F) was developed using the different characteristics between the load starting current and the fault current. The load starting current increases step by step so the time constant of each step is much smaller than that of the fault current. First, to detect faults in DC railway systems, an algorithm using the time constant calculated by the method of least squares is presented in this paper. If a fault occurs on DC railway systems it is necessary to find a fault location to repair the faulted system as soon as possible. The second aim of the paper is to calculate the accurate fault location using Kirchhoff's voltage law.

Performance Evaluation of SHF Sensor for Partial Discharge Signal Detection on DC Rectifier (DC 정류기 부분방전 신호검출을 위한 SHF 센서의 성능평가)

  • Jung, Ho-Sung;Park, Young;Na, Hee-Seung;Jang, Soon-Ho
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.7
    • /
    • pp.1056-1060
    • /
    • 2012
  • Online monitoring system is becoming an essential element of railway traction system for utilized to condition based malignance management and various techniques currently employed in railway traction system. Among the various techniques, it is efficient to detect partial discharge signals by electromagnetic wave detection in order to detect insulation fault of rectifier. Although VHF (Very High Frequency), UHF (Ultra High Frequency) sensors were adopted to detect partial discharge of power facilities, due to characteristics of urban railway, excessive noise occurs from 500 MHz to 1.5 GHz on UHF bandwidth. In this paper a new measurement system able to monitoring the conditions of power facilities on DC substation in metro was studied and set up. The system uses UHF sensors to measure the partial discharge of the rectifier due to electric faulting and dielectric breakdown. Comparison and estimation for performance of SHF sensor which had devised to detect partial discharge signal of urban railway rectifier has conducted. In order to estimate performance of SHF sensor, we have compared the sensor with existing UHF sensor on sensitivity upon frequency bandwidth generated by pulse generator, and also we have verified performance of the SHF sensor by detection results of partial discharge signal from urban railway rectifier.