• 제목/요약/키워드: Cu tube

검색결과 147건 처리시간 0.025초

흡수식냉동기용 열교환기 세관의 부식에 관한 연구 (The Study of Corrosion of Heat Exchanger Tube for Absorption Refrigeration Machine)

  • 임우조;정기철;윤병두
    • 한국마린엔지니어링학회:학술대회논문집
    • /
    • 한국마린엔지니어링학회 2002년도 춘계학술대회논문집
    • /
    • pp.147-152
    • /
    • 2002
  • This paper was studied on corrosion of heat exchanger tube for absorption refrigeration machine. In the 62 % lithium bromide solution at $60^{\circ}C$, polarization test of Cu, Al-brass, 10 % cupro nickel(90-10 % Cu-Ni) and 30 % cupronickel(70-30 % Cu-Ni) tube was carried out. And polarization behavior, polarization resistance characteristics, open circuit potential, anodic polarization of heat exchanger tube for absorption refrigeration machine were considered. The main results are as following: The open circuit potential of Al-brass tube becomes less noble than that of Cu tube, corrosion current density of that becomes lower than Cu tube. The open circuit potential of cupronickel tube is more noble than that of Cu tube, corrosion current density of that is controlled than Cu tube. The passivation critical current of 30 % Cu-Ni tube is lower than that of 10 % Cu-Ni tube, potential of passive region of that is more wide than 10 % Cu-Ni tube.

  • PDF

가스흡수식 냉온수기 열교환기용 세관의 부식특성에 관한 연구 (The Study on Corrosion Characteristics of Heat Exchanger Tube for Gas Absorption Refrigeration & Hot Water System)

  • 정기철
    • 한국가스학회지
    • /
    • 제6권1호
    • /
    • pp.92-97
    • /
    • 2002
  • 가스흡수식 냉온수기의 작동매체로 사용되고 있는 LiBr 수용액 중에서 열교환기 세관용 재료인 동 세관 및 동합금재인 큐프로니켈 세관의 부식특성에 관한 연두를 하기 위하여 $62\%$ LiBr 수용액 중에서 각 재료에 대한 전기화학적 분극실험을 실시하여 부식특성을 고찰한 결과 다음과 같은 결론을 얻었다 1) 열교환기 세관재의 분극저항은 $30\%$ 큐프로니켈 세관 > $10\%$ 큐프로니켈 세관 > 동 세관의 순으로 높게 나타난다 2) 큐프로니켈 세관의 개로전위는 동 세관보다 귀전위화되면서 부식전류밑도는 더 억제된다 3) $30\%$ 큐프로니켈 세관의 부동태 영역은 $10\%$ 큐프로니켈 세관보다 전위구간이 더 크게. 나타나면서 부동태유지 전류밀도는 더 낮아진다.

  • PDF

태양열 집열기에 사용되는 구리-유리관 접합기구 (Bonding Mechanism of Direct Copper to Glass Seal in an Evacuated Tube Solar Collector)

  • 김철영;남명식;곽희열
    • 한국세라믹학회지
    • /
    • 제38권11호
    • /
    • pp.1000-1007
    • /
    • 2001
  • 진공관형 태양열 집열기에서는 열관(heat pipe)과 붕규산염 유리관의 안정된 접합이 이를 장시간 사용하는데 매우 중요하다. 구리와 유리는 그 물리.화학적 성질에 큰 차이가 있어 접합하기가 어려움으로 구리관 표면에 유리와 화학적 결합이 용이한 산화막을 생성시켜 접합하도록 구리의 산화상태, 접합계면 및 접합강도를 XRD, SEM, EDS 및 인정시험기로 측정하였다. 순수 구리는 $600^{\circ}C$ 이하로 열처리하였을 때 Cu$_2$O 산화막을 생성하였으나 그 이상의 온도에서는 CuO 산화막을 형성하였으며 후자의 산화막은 구리와의 접합력이 매우 불량하였다. 그러나 붕사로 표면 처리를 하였을 경우에는 80$0^{\circ}C$에서도 Cu$_2$O 산화막 만이 발견되었다. Cu$_2$O 산화막을 생성시킨 구리관과 붕규산염 유리관을 Housekeeper법으로 접합하였을 경우 354.4N의 접합강도를 얻을 수 있었으며 열충격 저항성도 매우 뛰어났다.

  • PDF

원통다관형 열교환기의 침식-부식 특성에 관한 연구 (I) (Study on the Characteristics of Erosion-Corrosion for Heat Exchanger of Shell and Tube Type(I))

  • 임우조;정해규
    • 수산해양기술연구
    • /
    • 제35권2호
    • /
    • pp.196-200
    • /
    • 1999
  • In the case that erosion and corrosion occurs in machinery and structure at the same time, the synergy effect by erosion-corrosion affects fatal effect to durability of machinery and structure. Therefore, in machinery and structure which use corrosion liquid, the study of the synergy effect of erosion-corrosion which affects metal material is requested. In this paper. the flow corrosion experiment about the effect of temperature change and liquid velocity change in sea water was carried out to study the characteristics of erosion-corrosion for tube material Cu heat exchanger The main results obtained are as follows. (1) Damage appearance of tube outside by erosion-corrosion becomes dull because electrode potentials of Cu tube is higher than electrode potential of STPG38 shell. (2) In the cooling system by sea water, the weight loss rate of Cu at tube outside liquid temperature of $70^{\circ}C$ is higher than that of temperature of $20^{\circ}C$. (3) In cooling system by sea water, the weight loss rate of Cu at liquid velocity of 5.1m/s is higher than that of velocity of 1.47m/s. But as the testing time passed, the weight loss rate of Cu at velocity of 5.1m/s is almost steady and becomes dull at velocity of 1.47m/s.

  • PDF

함정용 패키지 에어콘 응축기 핀튜브(Cu-Ni 70/30) 누설파괴 원인 분석 (Failure Analysis of Condenser Fin Tubes of Package Type Air Conditioner for Navy Vessel)

  • 박형훈;황양진;이규환
    • 한국표면공학회지
    • /
    • 제49권5호
    • /
    • pp.439-446
    • /
    • 2016
  • In 2015, a fin tube (Cu-Ni 70/30 alloy) of package type heat exchanger for navy vessel was perforated through the wall which led to refrigerant leakage. This failure occurred after only one year since its installation. In this study, cause of the failure was determined based on available documents, metallographic studies and computational fluid dynamics simulation conducted on this fin tube. The results showed that dimensional gap between inserted plastic tube and inside wall of fin tube is the cause of the swirling turbulent stream of sea water. As a result of combination of swirling turbulence and continuing collision of hard solid particles in sea water, erosion corrosion has begun at the end of inserted plastic tube area. Crevice corrosion followed later in the crevice between the outer wall of plastic tube and inner wall of fin tube. It was found that other remaining tubes also showed the same corrosion phenomena. Thorough inspection and prompt replacement will have to be accomplished for the fin tubes of the same model heat exchanger.

분말시스압연법에 의해 제조된 3vol%CNT 강화 Cu기 복합재료의 미세조직 및 기계적 성질 (Microstructure and Mechanical Properties of 3vol%CNT Reinforced Cu Matrix Composite Fabricated by a Powder in Sheath Rolling Method)

  • 이성희
    • 한국재료학회지
    • /
    • 제30권3호
    • /
    • pp.149-154
    • /
    • 2020
  • A powder-in-sheath rolling method is applied to the fabrication of a carbon nano tube (CNT) reinforced copper composite. A copper tube with outer diameter of 30 mm and wall thickness of 2 mm is used as sheath material. A mixture of pure copper powder and CNTs with a volume content of 3 % is filled in a tube by tap filling and then processed to an 93.3 % reduction using multi-pass rolling after heating for 0.5 h at 400 ℃. The specimen is then sintered for 1h at 500 ℃. The relative density of the 3 vol%CNT/Cu composite fabricated using powder in sheath rolling is 98 %, while that of the Cu powder compact is 99 %. The microstructure is somewhat heterogeneous in width direction in the composite, but is relatively homogeneous in the Cu powder compact. The hardness distribution is also ununiform in the width direction for the composite. The average hardness of the composites is higher by 8Hv than that of Cu powder compact. The tensile strength of the composite is 280 MPa, which is 20 MPa higher than that of the Cu powder compact. It is concluded that the powder in sheath rolling method is an effective process for fabrication of sound CNT reinforced Cu matrix composites.

Cu-Zn Metal Fiber를 이용한 배관 스케일 방지에 관한 연구 (A Study of Prevention of Pipe Scale with Cu-Zn Metal Fiber)

  • 이상호;김종화;송주영
    • 한국응용과학기술학회지
    • /
    • 제27권1호
    • /
    • pp.70-75
    • /
    • 2010
  • Scale generation in the inside of a pipe IS restricted by reduction and oxidation(REDOX) reaction of alloyed metal of Cu-Zn. To measure the scale generating rate in the 1.67 mm of inside diameter of stainless steel tube, 300 ppm of $CaCO_3$ solution is circulated in the REDOX reactor and stainless steel tube in the order. In the case of $CaCO_3$ solution treated by REDOX reactor, flowing is maintained without plugging in the stainless steel tube, and the concentration of Cu and Zn in the circulating solution showed less than 1 ppm, which is equal to that of untreated by REDOX reactor. The crystal type of $CaCO_3$ generated by crystalline nucleus of Cu or Zn, mostly showed aragonite type.

구리 배관의 Sn 첨가에 따른 응력 및 다양한 환경에서의 부식 특성 (Corrosion characteristics in stress and various environments with Sn addition to Cu pipe)

  • 김세림;김의준;이명훈;이승효
    • 한국표면공학회지
    • /
    • 제57권3호
    • /
    • pp.192-200
    • /
    • 2024
  • Cu as a heat exchanger tube is an important component in thermal fluid transfer. However, Cu tubes are exposed to stress in certain environments, leading to stress corrosion cracking (SCC). In this study, the effect of Sn addition on microstructure and corrosion characteristics was examined. The microstructural examination revealed the presence of columnar crystal and a grain refinement due to the addition of Sn. Electrochemical measurements showed that the 5 wt.% NH3 environment was the most vulnerable environment to Cu corrosion, and the corrosion current density increased as stress increased. The immersion test exhibited the formation of Cu2O and Cu(OH)2 corrosion product in 3.5 wt.% NaCl and 5 wt.% NH3 environments, respectively. Results indicated that Sn addition to Cu was an important factor in improving the mechanical strength.

유한요소법과 최적설계기법을 활용한 히트싱크 콜드 플레이트 최적 설계 (Optimized Design of a Cold Plate Heat Sink using FEM and Optimization)

  • 홍석무;서형준;김종문;심재원;황지훈
    • 소성∙가공
    • /
    • 제23권7호
    • /
    • pp.419-424
    • /
    • 2014
  • In order to improve efficiency, an outdoor unit using a refrigerant cooling method is designed into many air conditioner systems. The heat exchanger is composed of a Cu tube and an plate. The optimal design for the cold plate is very important because the efficiency of the heat transfer depends on the contact area between the Cu tube and the cold plate. The current study focused on the design of the cold plate to obtain a uniform contact between the Cu tube and the cold plate. Both FE(finite element) analysis and optimization were used in the design. The contact area between the tube and plate was predicted and improved by 16% through the press forming simulations. The springback after press forming was also reduced when the optimized design parameters were used. To verify the validity of the optimal cold plate design, a verification test was conducted. As a result, the performance of the heat exchanger improved by 34% when compared to benchmarked products.