• 제목/요약/키워드: Cross-Bond Grounding

검색결과 2건 처리시간 0.019초

방식층 보호장치의 설치에 따른 지중송전케이블 시스 유기전압 해석 (Analysis of Sheath Induced Voltage in Transmission Power Cable Connected with CCPU)

  • 이준성;이종범;김영
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권1호
    • /
    • pp.19-25
    • /
    • 2000
  • This paper describes the sheath induced voltage in underground transmission cable system which will be operated with cable cover protection unit(CCPU). Simulation was carried out to analyze the sheath induced voltage in the real cable system which was installed by 154㎸ CV cable in the case with and without CCPU. The sheath induced voltage will be also analyzed according to the change of grounding method, fault resistance and fault angle. Simulation was performed using EMTP and ATP Draw, the simulation results show whether the CCPU in necessary or not in underground transmission power cable system.

  • PDF

지중송전계통에서 절연접속함 위치 및 접지방식 변경의 효용성 평가 (Effectiveness Evaluation According to Change of IJ Joint Box Location and Grounding System in Underground Transmission System)

  • 고광만;이종범
    • 전기학회논문지
    • /
    • 제64권2호
    • /
    • pp.247-253
    • /
    • 2015
  • Dielectric breakdown accidents have been mainly occurred in the vicinity of service entrance section in underground power transmission systems. One cause among them is due to the excessive component value of sheath located around service entrance of cable. In this paper, as one of the alternative to prevent these accidents, the change of cross bond grounding system and the location change of IJ(Insulation Joint) are suggested. Also, to evaluate effectiveness of this changing system, circulating current and induced voltage of sheath were analyzed in steady and transient state. By comparison of the analytical results for the several possible changing systems, a grounding system and location of IJ which has the smallest sheath component values is proposed. In this paper, analysis to evaluate the proposed system is carried out by EMTP/ATPDraw. It can be used as a valuable operational material to prevent accident of the service entrance section in underground power transmission system.