• 제목/요약/키워드: Cone calorimeter test

검색결과 103건 처리시간 0.033초

Cone-Calorimeter와 연기밀도챔버를 이용한 고무발포단열재의 연기밀도 비교 (Smoke Density Comparison of Rubber Foam Insulator by the test between Cone-Calorimeter and Smoke Density-Chamber)

  • 조희기;이덕희;이철규;이동우
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2005년도 추계학술대회 논문집
    • /
    • pp.941-946
    • /
    • 2005
  • Kinds of Sound & Thermal Insulator are being used for materials of railroad vehicles as a barrier of beat and noise. Glass Wool, PE foam, PP foam are such kinds of materials. In case of fire, it shows various combustion properties. In this study, we compared the Smoke Density of the Rubber Foam Insulator by test between Cone-Calorimeter and Smoke Density-Chamber. The results showed that the Rubber Foam Insulator had an important role in the insulator thickness and the test method, We forecast the smoke density by test between Cone-Calorimeter and Smoke Density-Chamber.

  • PDF

콘칼로리미터를 이용한 구조용 목재의 탄화 특성 (Charring Properties of Structural Timbers using Cone Calorimeter)

  • 홍성인;안재홍;최윤정;김병일
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2023년도 가을학술발표대회논문집
    • /
    • pp.85-86
    • /
    • 2023
  • In this study, charring properties such as charring layer and mass change of wood with temperature were investigated through cone calorimeter test on douglas-fir, which is representative of various wood structures. the results showed that ignitions at 390 degrees and a charring layer is formed.

  • PDF

콘칼로리미터를 사용한 샌드위치패널 연소특성에 대한 실험적 연구 (The Experimental Study for the Combustion-Property of Sandwich Panels using ISO 5660 Cone Calorimeter)

  • 박수영;김대회;임홍순
    • 한국화재소방학회논문지
    • /
    • 제20권4호
    • /
    • pp.33-41
    • /
    • 2006
  • 국내에서는 현재 샌드위치패널의 화재안전성능 평가를 위하여 KS F 2271(건축물의 내장재료 및 구조의 난연성 시험방법)을 사용하고 있다. 국내와 동일한 시험방법을 사용하고 있던 일본에서는 2000년 건축기준법 개정시 ISO 5660-1 시험방법을 내장재의 연소성능시험으로 채택하였다. 그에 따라 국내에서도 KS F 2271 시험방법을 보완하는 건축법 개정고시(안)을 예고하였고, 그 내용은 ISO 5660-1(Cone Calorimeter Method) 시험방법을 도입하는 것으로 알려져 있다. 본 연구에서는 샌드위치패널의 연소특성을 ISO 5660-1 콘칼로리미터 시험방법을 사용하여 검토하였다. 국내에서 일반적으로 사용되는 4종의 샌드위치패널과 4종의 심재(단열재)의 착화시간, 최대열방출율, 총 열방출량을 검토하였으며, 시험체별 시험결과를 분석하였다. 최종적으로 일본과 NBC개정안에서 제시하는 분류기준에 시험결과를 적용하였다.

조사연구-콘칼로리메타를 이용한 화재시험에 대하여

  • 이두형
    • 방재기술
    • /
    • 통권19호
    • /
    • pp.22-28
    • /
    • 1995
  • The rate of heat release is probably the single most important measure of fire hazard. Several tech-niques were developed for the measurement of rate of heat release, but were not suitable for fire test-ing purpose. Recently the application of oxygen consumption principle made it possible to development of well-characterized heat release rate measurement apparatus, the furniture calorimeter for large-scale fire tests and the cone calorimeter for bench-scale fire tests. The cone calorimeter can be used to determine the ignitability as well as heat release rate and smoke development, mass loss rate, combustion gas production etc. from burning materials. Thus, test method using cone calorimeter, an internationally recognized and accepted for the evalua-tion of fire properties, is a very promising tool for combustion study on various kind of materials and products.

  • PDF

FDS 열분해 모델을 이용한 콘칼로리미터(ISO 5660) 화재 시뮬레이션 (Fire Simulation by Pyrolysis Method of FDS for the Small Cone Calorimeter (ISO 5660))

  • 양성진;장정훈;강찬용
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2009년도 춘계학술대회 논문집
    • /
    • pp.206-212
    • /
    • 2009
  • Chemical behaviors of each surface material for interior facilities affect to fire initiation and growth in general fire situation. These chemical behaviors were characterized by thermal properties (Heat release rate, Pyrolysis rate, specific heat, etc) which could be derived from experimental test. Especially, Heat release rate which indicates aspect of fire size is one of the most important property to asses fire hazard and protection needs. The cone calorimeter test (ISO 5660) has recently assumed to a dominant role in bench scale fire testing to obtain the Heat release rate of materials. This value could be calculated by the 'Oxygen Consumption Method' under various producing irradiances to each surface of materials. In this study, Process of the cone calorimeter test was simulated by Pyrolysis model of FDS (Fire Dynamics Simulator by NIST) base on the ISO 5660 international standard. Then, we could estimate the simulation method of FDS in case of single materials through the comparative study with test results.

  • PDF

건축물내 통신용 케이블의 화재위험성 분석에 관한 실험연구 (A Experimental Study on the Fire Hazard Analysis For Communication Cable in Buildings)

  • 홍성호;최문수
    • 한국안전학회지
    • /
    • 제26권6호
    • /
    • pp.20-25
    • /
    • 2011
  • This study presents on the fire hazard analysis of communication cable in buildings. In order to analyze fire hazards for communication cable IEC 60332-1, UL 94 and cone calorimeter test are conducted. The number of cable used to experiment is 10 communication cable which are generally applied to data communication in buildings. The results show that 9 cables do meet the performance requirement of IEC 60332-1 and 8 cables are V-0 classification. IEC 60332-1 and UL 94 test are inadequate for fire hazard classification. The various parameters obtained by cone calorimeter test such as HRR, peak HRR, smoke production rate and so on. Also it is able to evaluate multiply fire hazard for communication cable with cone calorimeter test results.

콘칼로리미터 연소가스 FT-IR 분석을 위한 국제표준 초안의 비교시험 결과분석 (Results of a Round-Robin Test for the Draft International Standard on FT-IR Gas Analysis of Fire Effluents from a Cone Calorimeter)

  • 최정민;박계원;정재군
    • 한국화재소방학회논문지
    • /
    • 제33권3호
    • /
    • pp.1-8
    • /
    • 2019
  • ISO TC 92에서는 콘칼로리미터의 연소가스를 FT-IR 방식의 가스분석기로 분석하기 위한 표준을 개발하고 있다. 2018년에는 표준 초안(WD 21397)의 절차에 따라 6개 기관이 참여하여 표준 초안의 반복성 및 재현성을 평가하였다. 시험대상 시료는 polymethyl methacrylate (PMMA), 경질 폴리우레탄 보드 및 PVC 장판이었고 콘칼로리미터 시험결과 중 착화시간(s), 최대 열방출률(kW·m-2), 총 방출열량(MJ·m-2) 및 유효연소열(MJ·m-2·kg-1)을, 그리고 FT-IR 가스분석결과 중 독성가스의 최대 농도(µL·L-1), 가스 발생량(g) 및 가스 수율(g·g-1)을 ISO 5725-2에 따라 통계 분석하여 정밀도를 평가하였다. 이상치(outlier)는 발견되지 않았으며 콘칼로리미터 시험의 반복성(sr/m)은 1.5%, 재현성(sR/m)은 9.8%로 나타났고 FT-IR 가스분석의 반복성은 12.9%, 재현성은 27.9%로 나타났다.

콘칼로리미터를 이용한 건축용 막재의 내화 특성 연구 (A Fire Resistance Property Study of Architectural Fabric using Cone Calorimeter)

  • 김지현;신현욱;송훈
    • 한국건축시공학회:학술대회논문집
    • /
    • 한국건축시공학회 2015년도 추계 학술논문 발표대회
    • /
    • pp.158-159
    • /
    • 2015
  • Architectural fabrics are now used in membrane structure with the merits of free shape, lightness and opened up new possibility for the design of new building structures. Recently PVC, PVF, PVDF, PTFE coated fabric for using the membrane structures. However, clear standards for the design and construction is not exist because of the lack of Architectural fabric research. In this paper, Flammable properties of PVDF, PTFE coated fabrics are obtained through the Flammability test using the Cone Calorimeter. Based on these results, identify the fire resistance property of the Architectural fabric.

  • PDF

합성목재의 연소특성에 관한 연구 (A Study on Combustion Characteristics of Wood-Plastic Composites)

  • 신백우;송영호;이동호;정국삼
    • 한국화재소방학회논문지
    • /
    • 제24권6호
    • /
    • pp.120-125
    • /
    • 2010
  • 주거 건축 및 가구산업의 자재로써 합성목재(Wood-Plastic Composites)는 점차 각광받고 있다. 본 연구에서는 합성목재의 연소특성을 살펴보기 위하여 한계산소지수 측정(ASTM D 2863) 및 콘칼로리미터 시험(ISO 5660-1)을 실시하였으며 또한 일반목재인 적송과 방부 처리를 한 방부목에 대하여도 동일한 시험을 통하여 합성목재와의 연소특성을 비교.검토하였다. 한계산소지수 측정결과 합성목재가 적송 및 방부목에 비해 낮게 측정되었다. 콘칼로리미터 시험결과 합성목재의 열방출률이 가장 높았고 또한, 최대 열방출률 및 평균 열방출률, 총 방출열량도 적송 및 방부목에 비해 높게 나타났다.