• 제목/요약/키워드: Conductor Sleeve

검색결과 16건 처리시간 0.036초

220kV XLPE CABLE 접속함용 Al-Cu 이종접속슬리브 개발 (Development of Friction Welded Al to Cn Bimetallic Sleeve for 220kV XLPE Cable Termination & Joint)

  • 김현주;박정기;박성민
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.93-93
    • /
    • 2010
  • We developed friction welded bimetallic sleeve for 220kV aluminum conductor XLPE cable. Not only friction welded bimetallic sleeve for Termination(EB-A, EB-G) but also friction welded sleeve for Joint of Al to Cu conductor was developed regardless of this project. Generally, friction welded sleeve used to connect Al conductor cable to Cu conductor cable and used for improvement of mechanical property of terminal by offer the copper side of friction welded bimetallic sleeve at the Termination. Connection method for Al-Cu conductor has mainly used friction welding at the solid state, because it is difficult to connect by using conventional welding method. this investigation introduces development of friction welded bimetallic sleeve by friction welding and test result of 220kV Al conductor XLPE cable and accessories using friction welded sleeve.

  • PDF

송배전 접속 금구류의 도전 열특성에 관한 연구 (Heat Characteristics of Electric Fittings for Power Transmission Line)

  • 이창식;진양덕
    • 대한기계학회논문집
    • /
    • 제13권4호
    • /
    • pp.697-702
    • /
    • 1989
  • 본 연구에서는 도체의 접속 금구류의 도전 열특성을 규명하기 위한 연구의 일환으로 접속 금구류 중 접속 슬리브커넥터의 적절한 허용 전류, 통전시에 발생하는 승온 특성 및 전기 저항 특성 등을 실험적으로 구하고 접속 금구류의 설계에 필요한 도전 열특성을 실험적으로 규명하는 것을 목적으로 한다.

노후 송전선로의 가공송전선 직선 슬리브 분석 연구 (The Study on Aged Sleeves for Old Transmission Lines)

  • 김병걸;김상수;손홍관;박인표;장태인;김진한
    • 한국전기전자재료학회논문지
    • /
    • 제20권11호
    • /
    • pp.1009-1014
    • /
    • 2007
  • A detailed study on aged sleeves for old transmission lines was carried out to clarify the deterioration of sleeves and the condition of installation. A lot of removed aged sleeves from transmission lines were investigated. Many biased installed cases and corrosion of steel sleeve part were found. These defects can cause a serious accident such as blackout during operating. The temperature distribution within sleeve of ACSR conductor was precisely measured and examined, conducted as part of series of studies on large currents in transmission lines. According to measurements of the conductor temperature near a joint(sleeve and clamp), the electrical resistance of joint is lower than that of the same length conductor. The detailed results were presented in the text.

강 슬리브 파단 직선 슬리브의 장력 및 열적 특성 분석 연구 (Study on Tension and Thermal Properties of Corrosive-fractured Steel Sleeve)

  • 안상현;김병걸;김상수;손홍관;박인표;김성규
    • 한국전기전자재료학회논문지
    • /
    • 제21권11호
    • /
    • pp.1036-1041
    • /
    • 2008
  • According to previous report, aged sleeves of old transmission line showed several defaulted installation patterns, which was biased or corrosive-fractured of steel sleeve installed cases. These defects can cause serious accidents such as rapid increasing of sag or falling out of overhead conductor from sleeves. Consequently, the defects lead to the major power outage. Corrosion of steel sleeve is a typical defect by aging of sleeves. And it occupied almost 25 percent of investigated aged sleeves. This paper studied thermal properties and tension for ACSR conductor in case of fractured steel sleeve model by corrosion. The temperature distribution within overhead conductor has a specific gradient. Thermal properties of splice connectors(sleeve and clamp) showed normal behavior. However, mechanical properties were worse than normal sleeves. The detailed results were presented in the text.

슬리브 시공유형별 기계적 및 열적 가속열화특성 분석 연구

  • 안상현;김병걸;김상수;손홍관;박인표
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 추계학술대회 논문집
    • /
    • pp.286-286
    • /
    • 2009
  • According to previous report, aged sleeves for old transmission lines have various defect such as biased installation or corrosion of steel sleeve. These defects can cause serious accidents such as rapid increasing of sag or falling out of overhead conductor from sleeves. Moreover, the defects have been limited power capacity of transmission line. This paper study on mechanical and thermal behavior of ACSR $410mm^2$ conductor and sleeve with various defect model. The conductor has been aged artificially for 50 years. The detailed results were presented in the text.

  • PDF

편중 시공된 직선 슬리브의 장력 및 열적 특성 분석 연구 (The Study on Tension and Thermal Properties of Baised Installed Sleeve)

  • 안상현;김병걸;김상수;손홍관;박인표;김성규
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.1209-1210
    • /
    • 2008
  • According to previous report, aged sleeves for old transmission lines have variable defects such as biased installed case or corrosion of steel sleeve. Biased installed sleeve occupied 20 percent among the investigated aged sleeves. This defect must cause local heating of splice connector and limit power transmission capacity. It even inspire falling out of overhead conductor from sleeves. This paper studies thermal properties and tension for ACSR conductor in case of biased installed sleeve model. The detailed results were presented in the text.

  • PDF

강 슬리브 파단 직선 슬리브의 장력 및 열적 특성 분석 연구 (The Study on Tension and thermal properties of Corrosive-fractured Steel Sleeve)

  • 안상현;김병걸;김상수;손홍관;박인표;김성규
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 하계학술대회 논문집 Vol.9
    • /
    • pp.104-105
    • /
    • 2008
  • According to previous report, aged sleeves of old transmission line showed several defaulted installation patterns, which is biased or corrosive-fractured of steel sleeve installed cases. The latter case occupied almost 25 percent of investigated aged sleeves. These defects can cause serious accidents such as rapid increasing of sag or falling out of overhead conductor from sleeves. This paper studies thermal properties and tension for ACSR conductor in case of fractured steel sleeve model. The detailed results were presented in the text.

  • PDF

로딩 코일을 이용한 광대역 슬리브 모노폴 안테나의 설계 (The Design of the Broadband Sleeve Monopole Antenna using loading Coil)

  • 강상원;최광제
    • 한국전자파학회:학술대회논문집
    • /
    • 한국전자파학회 2001년도 종합학술발표회 논문집 Vol.11 No.1
    • /
    • pp.106-110
    • /
    • 2001
  • In this paper, a broadband sleeve monopole antenna using a loading coil in sleeve is proposed. The antenna of the proposed structure has the same of the single sleeve monopole antenna, except for using the coil instead of the inner conductor in sleeve. As a result, it is found that the bandwidth is 1.239~2.154 GHz(above 53.9%) for S$\sub$11/=-10dB(VSWR<2), and the antenna impedance is good for a communication system and feeder which the impedance has 50$\Omega$.

  • PDF

시공유형에 따른 ACSR 480Rail 가공송전선 접속개소의 기계적 및 열적 특성 연구 (The Study on Mechanical and Thermal Properties of ACSR 480Rail Conductor with Various Defects)

  • 안상현;김병걸;김상수;손홍관;박인표
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.1297_1298
    • /
    • 2009
  • According to previous report, aged sleeves for old transmission lines have various defect such as biased installation or corrosion of steel sleeve. These defects occupied almost 50 percent of investigated aged sleeves. These defects can cause serious accidents such as rapid increasing of sag or falling out of overhead conductor from sleeves. Moreover, the defects have been limited power capacity of transmission line. This paper study on thermal behavior of ACSR 480Rail conductor and sleeve with various defect model. The detailed results were presented in the text.

  • PDF

정상시공된 가공송전선 접속개소에서의 전류에 따른 온도변화 거동 (The Study on Aged Sleeves for Old Transmission Lines)

  • 김병걸;김상수;안상현;손홍관;박인표;이동일;장태인
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 추계학술대회 논문집
    • /
    • pp.518-519
    • /
    • 2007
  • In this paper, the temperature distribution within ACSR conductor was precisely measured and examined, conducted as part of a serious of studies on large currents in transmission lines. According to measurements of the conductor temperature near a joint(sleeve and clamp), the electrical resistance of joint is lower than that of the same length conductor. The detailed results were presented in the text.

  • PDF