Plate and Shell 열교환기 내의 R-22 응축열전달 특성에 관한 실험적 연구 (Experimental Study on R-22 Condensation Heat Transfer Characteristic in Plate and Shell Heat Exchanger)

  • 서무교;박재홍;김영수
    • 대한기계학회논문집B
    • /
    • 제25권6호
    • /
    • pp.860-867
    • /
    • 2001
  • In this study, condensation heat transfer experiments were conducted with plate and shell heat exchangers(P&SHE) using R-22. An experimental refrigerant loop has been established to measure the condensation heat transfer coefficient of R-22 in a vertical P&SHE. Two vertical counter flow channels were formed in the P&SHE by three plates of geometry with a corrugated trapezoid shape of a chevron angle of 45°. Downflow of the condensing R-22 in one channel releases heat to the cold upflow of water in the other channel. The effect of the refrigerant mass flux, average heat flux, system pressure and vapor quality of R-22 on the measured data were explored in detail. The results indicate that at a higher vapor quality the condensation heat transfer coefficients are significantly higher. A rise in the refrigerant mass flux causes an increase in the h(sub)r. Also, a rise in the average heat flux causes an increase in the h(sub)r. Finally, at a higher system pressure the h(sub)r is found to be slightly lower. Correlation is also provided for the measured heat transfer coefficients in terms of the Nusselt number.

습증기를 포함한 연소가스의 폐열회수를 위한 열교환기 성능 예측 (Performance Prediction of Heat Exchanger for Waste Heat Recovery from Humid Flue Gases)

  • 정동운;이상용;이한주
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2000년도 춘계학술대회논문집B
    • /
    • pp.276-281
    • /
    • 2000
  • A simulation program using the mass transfer correlation was constructed to analyze 1-D simplified condensing flow across the tube bank. Higher efficiency was anticipated by reducing the flue gas temperature down below the dew point where the water vapor in the flue gas is condensed at the surface of the heat exchanger; that is, the heat transfer by the latent heat is added to that by the sensible heat. Thus, there can be an optimum operating condition to maximize the heat recovery from the flue gas. The temperature rises of the flue gas and the cooling water between the inlet and the outlet of the tube bank were compared with the experimental data reported previously. The predicted results agree well with the experimental data. Using this simulation program, the parametric studies have been conducted fur various operating conditions, such as the velocities and temperatures of the vapor/gas mixture and the cooling water, the number of the rows, and the conductivity of the wall material.

  • PDF

컨테이너형 ESS 화재방지를 위한 내부 응결점 개선 관한 연구 (Study on Improvement of Dew Point within ESS Container for Fire Prevention)

  • 김운학;강석원;신기석
    • 한국재난정보학회 논문집
    • /
    • 제15권2호
    • /
    • pp.165-174
    • /
    • 2019
  • 연구목적: 본 연구에서는 제안되는 ESS 컨테이너 화재사고의 원인들에 대한 상관관계를 확인하였다. 연구방법: 이들의 개선에 필요한 컨테이너 내부의 환경개선을 통하여 컨테이너 화재사고의 저감 가능성에 대한 조사를 시행하였다. 연구결과: 본 연구를 통해 내 외부 온도차에 발생되는 수분응결 조건의 개선과 이를 통한 BMS board의 절연 내력의 변화가 있음을 확인하였다. 연구결론: BMS Board 응결과 절연 내력저하와의 상관 관계를 확인하였다.

Local Heat Transfer Coefficients for Reflux Condensation Experiment in a Vertical Tube in the Presence of Noncondensible Gas

  • Moon, Young-Min;No, Hee-Cheon;Bang, Young-Seok
    • 한국원자력학회:학술대회논문집
    • /
    • 한국원자력학회 1999년도 춘계학술발표회요약집
    • /
    • pp.104-104
    • /
    • 1999
  • The local heat transfer coefficient is experimentally investigated for the reflux condensation in a countercurrent flow between the steam-air mixture and the condensate. A single vertical tube has a geometry which is a length of 2.4m, inner diameter of 16.56mm and outer diameter of 19.05mm and is made of stainless steel. Air is used as a noncondensible gas. The secondary side is installed in the form of coolant block around vertical tube and the heat by primary condensation is transferred to the coolant water. The local temperatures are measured at 15 locations in the vertical direction and each location has 3 measurement points in the radial direction, which are installed at the tube center, at the outer wall and at the coolant side. In three different pressures, the 27 sets of data are obtained in the range of inlet steam flow rate 1.348 -3.282kg/hr, of inlet air mass fraction 11.8 -55.0%. The local heat transfer coefficient increases as the increase of inlet steam flow rate and decreases as the decrease of inlet air mass fraction. As an increase of the system pressure, the active condensing region is contracted and the heat transfer capability in this region is magnified. The empirical correlation is developed represented with the 165 sets of local heat transfer data. As a result, the Jacob number and film Reynolds number are dominant parameters to govern the local heat transfer coefficient. The rms error is 17. 7% between the results by the experiment and by the correlation.

  • PDF

R744-R404A용 캐스케이드 냉동시스템 개발에 관한 연구(2) - 최대 성능계수에 관한 예측과 비교 - (Development of cascade refrigeration system using R744 and R404A - Prediction and comparison on maximum COP(Coefficient of Performance) -)

  • 오후규;손창효
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제35권2호
    • /
    • pp.189-195
    • /
    • 2011
  • 본 논문은 R744-R404A용 캐스케이드 냉동시스템의 기초 설계자료를 제공하기 위해서 COP 예측 상관식을 제안하고 그 결과를 타 상관식과 비교하였다. 작동변수로는 R404A용 고온사이클과 R744용 저온사이클의 과냉각도와 과열도, 압축기효율, 응축과 증발온도이다. 이에 대한 주요결과를 요약하면 다음과 같다. 다중회귀 분석을 통해 R744-R404A용 캐스케이드 냉동시스템의 성능 예측식을 제안하였고, 그 결과를 타 연구자들의 상관식과 비교하였다. 그 결과 본 연구에서 제안한 성능 예측식은 타 연구자들의 상관식과 일치하지 않았다. 따라서 향후 R744-R404A용 캐스케이드 냉동시스템에 대한 추가 실험 데이터와 본 연구에서 제안한 COP 예측 상관식을 비교하여 그 신뢰성을 확보할 필요가 있다.

세관내 R-22 대체냉매의 응축압력강항에 관한 연구 (The Condensation Pressure Drop of Alternative Refrigerants for R-22 in Small Diameter Tubes)

  • 오후규;손창효;최영석;김기수
    • 대한기계학회논문집B
    • /
    • 제25권9호
    • /
    • pp.1245-1252
    • /
    • 2001
  • The condensation pressure drop for pure refrigerants R-22, R-134a, and a binary refrigerant mixture R-410A flowing in a small diameter tube was investigated. The test section is a counterflow heat exchanger with refrigerant flowing in the inner tube and coolant flowing in the annulus. The test section consists of 1220 [mm] length with horizontal copper tube of 3.38 [mm] outer diameter and 1.77 [mm] inner diameter. The refrigerant mass fluxes ranged from 450 to 1050 [kg/(㎡$.$s)] and the average inlet and outlet qualities were 0.05 and 0.95, respectively. The main experimental results were summarized as follows : In the case of single-phase flow, the pressure drop of R-134a is much higher than that of R-22 and R-410A for the same Reynolds number. The friction factors for small diameter tubes are higher than those predicted by Blasius equation. In the case of two-phase flow, the pressure drop increases with increasing mass flux and decreasing quality. The pressure drop of R-134a is much higher than that of R-22 and R-410A for the same mass flux. Most of correlations proposed in the large diameter tube showed enormous deviations with experimental data. However, the correlation predicted by Honda et al showed relatively good agreement with experimental data for R-134.