• Title/Summary/Keyword: Condensation Conefficient

Search Result 1, Processing Time 0.015 seconds

A Study on the Improement of Condensation and Boiling Heat Transfer on Horizontal Tube by Fin Effect(ll)-Shellside Condensation- (수평 원형전열관의 핀효과에 의한 응축 및 비등 열전달촉진에 관한 연구 (2)-튜브외부 응축-)

  • 한규일;조동현
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.18 no.5
    • /
    • pp.1275-1287
    • /
    • 1994
  • Heat transfer performance improvement by fin and grooves is studied for condensation of R-11 on integral-fin tubes. Eight tubes with trapezoidal shaped integral-fins having fin densities from 748 to 1654 fpm and 10, 30 grooves are tested. A plain tube having the same diameter as the finned tubes is also tested for comparison. R-11 condenses at saturation state of $32^{\circ}C$ on the outside tube surface cooled by inside water flow. All of test data ate taken at steady state. Beatty and Katz's, Rudy's and Webb's theoretical models are used to predict the R-11 condensation coefficient of tubes having 748, 1024 and 1299 fpm. The predicted value by Betty and Katz's model is within 10% of experimental values in this study at fpm<1024 and Rudy's model predicted the experimental data at fpm>1024 within 15%. The tube having fin density of 1299 fpm and 30 grooves has the best overall heat transfer performance. This tube shows the overall heat transfer coefficient of 11500 $W/m^{2}K$,/TEX> at coolant velocity of 3.0m/s.