• 제목/요약/키워드: Clearances around the bedside of ICU

검색결과 1건 처리시간 0.018초

중환자실 병상주변공간의 면적과 간격에 관한 연구 (A Study on the Area and Clearances around Patient Bed Space in Intensive Care Unit)

  • 이현진;권순정
    • 의료ㆍ복지 건축 : 한국의료복지건축학회 논문집
    • /
    • 제25권3호
    • /
    • pp.47-55
    • /
    • 2019
  • Purpose: This study tries to propose the dimensions and area related to patient bed and surroundings in ICU considering nurses' observation and medical care. Methods: Literature survey, 11 Case studies, some Interviews with nurses and measuring of medical equipments' dimension in ICU have been mobilized in order to deepen the ICU bed area standards. Results: 0.3m clearance between head wall and patient bed is necessary for emergency cases. The minimum distance at the foot of the bed should not be less than 0.9m for EMR cart and medical tray. The clear floor area of one bed and surroundings in open ward is $10.2m^2(3m{\times}3.4m)$. In a single-bed patient room, the minimum clear floor area is $16.0m^2(4m{\times}4m)$. Considering the control of cross infection in ICU, Single bed patient room is recommended. Implications: The result of this study can be applied to the design of ICU and legislation of ICU standard.