• Title/Summary/Keyword: Cast Resin Transformer

Search Result 43, Processing Time 0.019 seconds

Analysis of Temperature Characteristic According to Variation of Air Duct of the Cast Resin Transformer (몰드변압기의 공기덕트의 구조 변화에 따른 온도특성 해석)

  • Kim, Ji-Ho;Lee, Hyang-Beom;Shon, Jin-Geun
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.64 no.4
    • /
    • pp.256-260
    • /
    • 2015
  • In this paper, achieved rise temperature distribution about degradation phenomenon of 24 MVA distribution cast resin transformer using CFD(Computational Fluid Dynamics). Usually, life of transformer is depended on temperature distribution of specification region than thermal special quality of transformer interior. Specially, life of transformer by decline of dielectric strength decreases rapidly in case rise by strangeness transformer interior hot spot temperature value permits. Because calculating high-voltage(HV) winding and low-voltage(LV) winding of cast resin transformer and Joule's loss of core for improvement these life, forecasted heat source, and HV winding and LV winding of cast transformer rise temperature distribution of core for supply of electric power and temperature distribution of highest point on the basis of the results. Also, calculated temperature rise limit of cast resin transformer and permission maximum temperature using analysis by electromagnetic heat source. Calculated and forecasted rise temperature distribution by heat source of thermal analysis with calculated result.

Study on the Thermal Degradation Properties of Epoxy Resin for the Cast Resin Transformer (몰드변압기용 에폭시 수지의 열 열화 특성에 관한 연구)

  • Nam, K.D.;Jung, J.I.;Huh, C.S.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1572-1574
    • /
    • 2000
  • In this paper, study on the properties of the thermal degradated epoxy resin which is used in cast resin transformer is performed to investigate the problems of the decreasing insulation characteristics and crack in the cast resin transformer. In the test, contact angle, weight loss, surface resistivity and relative dielectric constant are measured. As the results of the above measurements, the epoxy resin has increased to 150$^{\circ}C$ in the contact angle and surface resistivity but at the above 150$^{\circ}C$ the values have decreased. The relative dielectric constants have increased in the thermal treated samples with the degradation temperature. Consequently, the insulation properties of the epoxy resin which is used in cast resin transformer have increased by the 150$^{\circ}C$ but decreased in the above 150$^{\circ}C$.

  • PDF

A Study on the Comparison of the Vibration Data in Cast Resin Transformer According to the Load Type (부하 형태에 따른 몰드변압기에서의 진동데이터 비교에 관한 연구)

  • Shong, Kil-Mok;Choi, Myung-Il;Kim, Young-Seog;Bang, Sun-Bae;Kim, Chong-Min
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.4
    • /
    • pp.75-81
    • /
    • 2012
  • In this study, vibration characteristics in according to the load type of cast resin transformer using vibration measurement device were compared. Measurement conditions are the same installation and operation of the three-phase cast resin transformer. If the load increases in transformer using the rotating machinery, the frequency is growing. In the transformer using the lighting and heating loads, it's detected the 55 [${\mu}m/s$] in or outside and 120 [${\mu}m/s$] or more at 60[Hz], the 30 [${\mu}m/s$] in or outside at 120[Hz], and the 70 [${\mu}m/s$] in or outside at 420[Hz]. When increases the loads, it's appeared the 60 [${\mu}m/s$] or less at 450[Hz] or more in rotating machinery, but the velocity of lighting and lighting loads are appeared from 5[${\mu}m/s$] to 115[${\mu}m/s$] inside the 420[Hz] in the same load condition of 20[%]. Through this study, it's verified that there are differences the internal vibration in according to the type of load in cast resin transformer.

Analysis on Characteristics of Core and Winding Vibration in Cast Resin Transformer (몰드변압기 철심과 권선 진동 특성분석)

  • Kim, Chong-Min;Choi, Myung-Il;Kim, Young-Seog;Bang, Sun-Bae;Shong, Kil-Mok
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.10
    • /
    • pp.52-59
    • /
    • 2012
  • In this paper, The cast resin transformer's vibration is measured using noncontact raser vibrometer(LV110D). The vibration characteristics of transformer windings and core are analyzed for relation between vibration magnitude and cause. Using the analysis results, the technique is presented to diagnose cast resin transformer. which is able to diagnose transformer' deformation in winding and core geometry. The magnetostriction and electromagnetic force act on the core and windings, causing them to vibrate. The vibration from windings and core penetrates into transformer cast resin and reaches the outside walls. The fundamental frequency of the core and windings vibration signal is twice that of the power frequency(120Hz). The results show that the magnitude of core vibration is linear to driving voltage amplitude and magnitude of windings vibration is increased to loading current under the some level and then stabilized.

The vibration detection and analysis of 3-phase cast resin transformer in less than 50% load conditions (50% 미만 부하조건에서의 3상 몰드변압기 진동 측정과 분석)

  • Shong, Kil-Mok;Bang, Sun-Bae;Kim, Chong-Min;Kim, Young-Seok;Choi, Myung-Il
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.61 no.7
    • /
    • pp.992-997
    • /
    • 2012
  • In this paper, we were analyzed the vibration characteristics of the three-phase cast resin transformer using less than 50% of load in the field. Most of the cast resin transformer is less than 50% in the domestic field is used for load conditions. Consisting of a solid insulator cast resin transformer is generating lots of noise and vibration. In addition, because it is affected by Joule 's heat is used in light load conditions. As a results, the transformer vibrations at frequencies below about from 200Hz to 500Hz were detected. Vibration velocity depends on the load variations were found. Load up to approximately 20-30% in most cases the vibration velocity was found at 4,000 ${\mu}m/s$ or less, 8,000 ${\mu}m/s$ or more. Vibration frequency at light load conditions were generated at the 120Hz, 240Hz, 360Hz and 480Hz. At the load condition of from 10% to 20%, vibration velocity is higher than another. Most of the vibration velocity were identified at the 1,000 ${\mu}m/s$ or less. Using the vibration frequency and velocity measurements data, the load on the cast resin transformer analyzed the correlation of the burden. Therefore, this data could be found in the vibration characteristics of the light-load conditions. If the field measurements using the data perform diagnostics on the transformer, it's expected to be very effective.

A study on the live line diagnostic technique of cast resin transformer by the partial discharge detection (부분방전검출에 의한 몰드변압기 무정전진단기법 연구)

  • Lee, Jun;Choi, Gil-Soo;Lee, Eun-Suk
    • Proceedings of the KIEE Conference
    • /
    • 1999.11d
    • /
    • pp.1048-1050
    • /
    • 1999
  • It is difficult to maintain cast resin transformer in the field. In this paper, we developed the diagnosis techniques to detect degrade of cast resin transformer using partial discharge, EMI and material analysis.

  • PDF

Frequency Spectra of AC Signal Generated from the Operation of Cast-Resin Power Transformer (운전중인 몰드형 전력변압기의 음향방출신호에 대한 주파수 스펙트럼 특성)

  • 구경철;이상우;이동인;이광식;김인식;김이국;신용철
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.246-250
    • /
    • 2000
  • In this paper, Frequency spectra of AE(acoustic emission) signals generated from the magnetizing and the load currents in the actual operating cast-resin power transformer of 500[kVA] under distribution system of22.9[kV] were also analysed to distinguish the AE signals due to void discharges from the magnetic circuit noises in the core of cast-resin power transformer. As the experimental results, we could distinguish the AE signals whether those signals were caused due to the void discharges or due to the magnetic circuit noises by analyzing the frequency spectrum of AE signals. Frequency spectra of AE signals generated from the cast-resin power transformer in operation due to both the magnetizing and the load currents appeared in the range of 40-120[khz].

  • PDF

Diagnosis of Insulation Deterioration in Cast-Resin Power Transformer using Acoustic Emission Techniques (음향방출법에 의한 몰드형 전력변압기의 절연열화 진단)

  • 이상우;김인식;이동인;이광식
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.14 no.6
    • /
    • pp.35-42
    • /
    • 2000
  • In this paper, AE(Acoustic Emission) signals detected from the growth of the electrical tree in an epoxy resin under ac high-voltage application were analysed to diagnose the insulation deterioration of cast-resin power transformer. Frequency spectra of AE signals generated from the magnetizing and the load currents in the actual operating cast-resin power transformer of 500[kVA] under distribution system of 22.9[kV] were also analysed to distinguish the AE signals due to void discharges from the magnetic circuit noises in the core of the transformer. As the experimental results, we could distinguish the AE signals whether those signals were caused due to the void discharges or due to the magnetic circuit noises by analyzing the frequency spectrum of AE signals. The frequency spectra of AE signals generated from the cast-resin power transformer in operation due to both the magnetizing and the load currents appeared in the range of 40-120[kHz], but the frequency band of AE signals emitted from the void discharges in an epoxy resin sample was about 50[kHz] to 230[kHz].

  • PDF

The Diagnosis cast-resin Transformer using Infrared Thermography system (열화상을 이용한 몰드변압기의 진단)

  • Jeong, Sung-Cheon;Chun, Jong-Chul;Lim, Yong-Bae
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.216-219
    • /
    • 2003
  • This paper presents the analyzing method for surface temperature distribution of a cast-resin transformer. For the study, the surface temperature of the transformer winding was measured and analyzed by a infrared thermography system. Alternating voltages were applied to simulate deterioration of the specimen transformer, and the hot-spot on the transformer surface was measured to analyze the condition for the winding. The hot line condition measured to the changes in surface temperature using infrared thermography camera and was set up the based of diagnostic method of the electric power apparatus. The results ould show the possibility of remote diagnosis using internet.

  • PDF

A Study on the Comparison of Denoising Performance of Stationary Wavelet Transform for Discharge Signal Data in Cast-resin Transformer (SWT(Stationary Wavelet Transform)를 이용한 몰드변압기 방전 측정신호의 디노이징 특성 연구)

  • Choi, Myeong-Il;Kim, Jae-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.3
    • /
    • pp.84-90
    • /
    • 2014
  • The partial discharge of Cast-resin Transformer has a difficulty to be analyzed, because it is an abnormal condition signal of which stochastic characteristics varies with time variance. In this study, background noise coming from the outside of the cast-resin transformers through ground wire can be removed and only a discharge signal of which defects are simulated can be obtained, using the wavelet transform method, which is a time-frequency domain analysis technique. As a result, it was confirmed that de-noising using the SWT technique is the best efficient among three methods of the wavelet transform techniques.