• 제목/요약/키워드: Cascading Outage

검색결과 5건 처리시간 0.023초

확률론적 연쇄사고 분석을 위한 시각화 모형 개발 (Development of Visualization Model for Probabilistic Analysis of Cascading Failure Risks)

  • 최영도;백자현;김태균;전동훈;윤기갑;박상호;구보경;허진
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제4권1호
    • /
    • pp.13-17
    • /
    • 2018
  • According to the recent blackouts, large blackouts can be described by cascading outages. Cascading outage is defined by sequential outages from an initial disturbance. Sequential and probabilistic approach are necessary to minimize the blackout damage caused by cascading outages. In addition, conventional cascading outage analysis models are computationally complex and have time constraints, it is necessary to develop the new analytical techniques. In this paper, we propose the advance visualization model for probabilistic analysis of cascading failure risks. We introduce the visualization model for identifying size of cascading and potential outages and estimate the propagation rate of sequential outage simulation. The proposed model is applied to Korean power systems.

Sequential Outage Checkers for Analyzing Cascading Outages and Preventing Large Blackouts

  • Hur, Jin;Joung, Man-Ho;Baldick, Ross
    • Journal of Electrical Engineering and Technology
    • /
    • 제6권5호
    • /
    • pp.585-594
    • /
    • 2011
  • This paper presents the use of sequential outage checkers to identify the potential cascading processes that might lead to large blackouts. In order to analyze cascading outages caused by a combination of thermal overloads, low voltages, and under-frequencies following an initial disturbance, sequential outage checkers are proposed. The proposed sequential outage checkers are verified using the AEP 9-bus system, New England 39-bus system, and IEEE 118-bus system.

전력계통설비의 정지관리 체계화 방안에 대한 연구 (A Study on the Outage Management Standards for Power System)

  • 허정용;김철환;김재철;이건웅;이성진;이창규;조범섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 A
    • /
    • pp.107-109
    • /
    • 2004
  • It is very important to operate a power system safely. An fault may causes the cascading outages in power system. Use of systematic, precise definitions related to the outages is essential for meaningful exchange of data. Moreover, it is necessary that specific instructions for reporting outages is developed. This paper presents the outage management for a power system. The outage managements of the many utilities are researched, which include the definition, classification, index and report of outage. Finally, the outage management standard is proposed, and the necessity and structure of KERC(Korean Electric Reliability Council) are presented

  • PDF

송전 계통 감시 시스템을 위한 취약도 평가 방법 개발 (Vulnerability Evaluation for Monitoring Wide Area Outage in Transmission Systems)

  • 김진환;임일형;이승재;최면송;임성일;김상태;진보건
    • 전기학회논문지
    • /
    • 제59권3호
    • /
    • pp.506-514
    • /
    • 2010
  • Defense systems are needed to prevent catastrophic failures of a power grid due to cascaded events. Cascaded events can be occurred by power flow overload. Especially, it is the most dangerous problem that overload line is outage, because it can make the power system face danger of cascaded. In this paper, vulnerability evaluation for monitoring wide are outage is proposed using by configuration information of transmission systems. This method of vulnerability evaluation is considered direct effect and indirect effect of power flow, especially overload. What is more, it can be used when the configuration of power system changes, as simple fault occurs or maintenance of facility. In the case studies, the estimation and simulation network have been testified and analysed in PSSE and C programming.

송전 계통의 광역정전 징후 시 PMU 취득 데이터를 이용한 거리계전기 Zone3 동작시간 예측 알고리증 (An Algorithm of Predicting the Zone 3 Trip Time of Distance Relay by using PMU Data when Power Systems Face Cascaded Event on Transmission System)

  • 김진환;임일형;이승재;최면송;김태완;임성일;김상태
    • 전기학회논문지
    • /
    • 제58권12호
    • /
    • pp.2303-2310
    • /
    • 2009
  • Defense systems are needed to prevent catastrophic failures of a power grid due to cascaded events. Cascaded events can be attributed to improper operations of protective relays. Especially, it is the most dangerous problem that trips of backup relays by overload. In this paper, a new algorithm of predicting Zone 3 acting time of distance relay is proposed using the real time synchronized data from PMUs on the transmission system when the power system is danger. In the proposed, some part of the power system are outage when some unexpected fault in the power system, the algorithm will monitor the impedance locus of distance relay. At this time, if there is a big change of Impedance locus, the algorithm will calculate the Zone 3 acting time of the distance relay by the over load. In the case studies, the estimation and simulation network have been testified and analysed in Matlab Simulink.