• Title/Summary/Keyword: Cable fault location

Search Result 67, Processing Time 0.033 seconds

Design of Fault Location System for High Voltage Underground Power Cable (지중송전선 고장점 탐색 장치 설계)

  • Lee, Jae-Duck;Ryoo, Hee-Suk;Choi, Sang-Bong;Nam, Kee-Young;Jeong, Seong-Hwan;Kim, Dae-Kyeong
    • Proceedings of the KIEE Conference
    • /
    • 2006.10c
    • /
    • pp.603-605
    • /
    • 2006
  • To reduce inference of any power delivery failures in underground power cable, power system operators are trying to find effective way of finding fault location as soon as possible. But it is very difficult to find fault location exactly for underground power cable. We are developing fault location system for underground power cable which can detect its fault location exactly. This new system monitors current and voltage of underground power cable by using low voltage and current sensors and if there are any accidents, it records its transient signal. Fault location is calculated by analyzing recorded signal. To develop fault location system for power cable, we needed fault simulation system and we installed it physically and tested. In this rapers, we describe on describe of fault location system for underground power cable.

  • PDF

H/W Design for Fault Location System on Underground Power Cable System (고장점 탐색 장치를 위한 H/W 설계)

  • Lee, Jae-Duck;Ryoo, Hee-Suk;Jung, Dong-Hak;Choi, Sang-Bong;Nam, Kee-Young;Jeong, Seong-Hwan;Kim, Dae-Kyeong
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.709-711
    • /
    • 2005
  • Developing fault location system for underground power cable which can detect its fault location exactly require very high speed data acquisition and signal processing capability. We are developing fault location system which is different from conventional fault locator. This fault location system monitor underground power cable by using on-line speed current sensor and if there are an accident, it record its transient signal and calculate fault location by analyzing it. Signals which acquired when power cable fault arise, showed transient characteristics and its frequency band is very hish. So, to develop fault location system, we designed special high speed data acquisition and signal processing board. In this thesis, we describe on data acquisition and signal processing H/W design for fault location system on underground power cable.

  • PDF

Signal Processing Technology for Fault location System in Underground Power Cable (고장점 탐색 장치를 위한 신호처리 연구)

  • Lee, Jae-Duck;Ryoo, Hee-Suk;Jung, Dong-Hak;Choi, Sang-Bong;Nam, Kee-Young;Jeong, Seong-Hwan;Kim, Dae-Kyeong
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.712-714
    • /
    • 2005
  • With rapid growth of industry, underground power delivery systems are growing so rapidly and its capacity also growing. So if there are any accident in underground power cable, its inference is too great to count. So power system operators should find Its fault location as soon as possible and replace it But it is difficult to find its fault location for underground power cable. We are developing fault location system for underground power cable which can detect its fault location exactly. This system usually monitor underground power cable on-line But if there are an accident, it record Its transient signal and we can calculate fault location by analyzing it. To develop fault location system for power cable, we needed fault simulation system and we installed it physically and tested at various point. in this thesis, we describe on signal processing technology to detect fault location on power cable and on the result of tested fault location performance.

  • PDF

Development of Portable Cable Fault Detection System with Automatic Fault Distinction and Distance Measurement (자동 고장 판별 및 거리 측정 기능을 갖는 휴대용 케이블 고장 검출 장치 개발)

  • Kim, Jae-Jin;Jeon, Jeong-Chay
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.10
    • /
    • pp.1774-1779
    • /
    • 2016
  • This paper proposes a portable cable fault detection system with automatic fault distinction and distance measurement using time-frequency correlation and reference signal elimination method and automatic fault classification algorithm in order to have more accurate fault determination and location detection than conventional time domain refelectometry (TDR) system despite increased signal attenuation due to the long distance to cable fault location. The performance of the developed system method was validated via an experiment in the test field constructed for the standardized performance test of power cable fault location equipments. The performance evaluation showed that accuracy of the developed system is less than 1.34%. Also, an error of automatic fault type and location by detection of phase and peak value through elimination of the reference signal and normalization of correlation coefficient and automatic fault classification algorithm not occurred.

Design and Construction of Test Field for Low Voltage Under Cable Fault Location Detection (저압 지중케이블 고장 위치 검출 실증 시험장 설계 및 구축)

  • Oh, Hun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.10
    • /
    • pp.6666-6672
    • /
    • 2015
  • Various reflectometry methods to locate power cable fault have been studied. But, most related studies has been verifying by simulation and laboratory test and study in conditions similar with real cable fault filed was not performed due to the absence of cable fault test field. Therefore, this paper design and construct test field for the standardized performance test and the operating education of cable fault location equipments. In the constructed test, open, short, half open and poor contact fault at 100m, 200m location of cable was produced and 1km cable role was installed for maximum distance measurement test. The test field will be used in the development and standardization of cable fault location technology, and te performance evaluation and certificate test of the related equipments.

Diagnosis of Poor Contact Fault in the Power Cable Using SSTDR (SSTDR을 이용한 케이블의 접촉 불량 고장 진단)

  • Kim, Taek-Hee;Jeon, Jeong-Chay
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.8
    • /
    • pp.1442-1449
    • /
    • 2016
  • This paper proposes a diagnosis to detecting poor contact fault and fault location. Electrical fire by poor contact fault of power cable occupied a large proportion in the total electrical installations. The proposed method has an object to prevent electrical fault in advance. But detecting poor contact fault is difficult to detect fault type and fault location by using conventional reflectometry due to faults generated intermittently and repeatedly on the time change. Therefore, in this paper poor contact fault and fault conditions were defined. System generating poor contact fault produced for the experimental setup. SSTDR and algorithm of reference signal elimination heighten performance detecting poor contact fault on live power cable. The diagnosis methods of signal process and analysis of reflected signal was proposed for detecting poor contact fault and fault location. The poor contact fault and location had been detected through proposed diagnosis methods. The fault location and error rate of detection were verified detecting accuracy by experiment results.

A Fault Location Algorithm Using Wavelet Transformation for HVDC Cables (웨이블렛 변환을 이용한 HVDC 케이블 고장점 표정 알고리즘)

  • Kwon, Young-Jin;Kang, Sang-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.8
    • /
    • pp.1311-1317
    • /
    • 2008
  • In this paper, a fault location algorithm using wavelet transform is proposed for HVDC cable lines. The arriving instants of the first and second fault-induced backward travelling waves can be detected by using wavelet transform. The fault distance is estimated by using the time difference between the two instants of backward travelling waves and the velocity of the travelling wave. To distinguish between the backward wave from fault point and the backward wave from the remote end, polarities of backward waves are used. The proposed algorithm is verified varying with fault distances and fault resistances in underground cables of VSC(voltage source converter) HVDC system and CSC(Current Source Converter) HVDC respectively. Performance evaluations of the proposed algorithm shows that it has good ability for a fault location of HVDC cable faults.

A Study on Fault Location Using Wavelet in 154kV Transmission Power Cable (154kV 지중송전케이블에서 Wavelet을 이용한 Fault Location에 관한 연구)

  • Lee, Jun-Seong;Mun, Seong-Cheol;Lee, Jong-Beom
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.12
    • /
    • pp.608-613
    • /
    • 2000
  • This paper describes a fault location technique using wavelets in underground transmission power cable system. Estimation of fault location is performed using data smapled at two ends underground system. In the case of 50% fault of total underground transmission line, fault location is calculated using sampled single-end data in underground transmission line. Traveling wave is utilized in capturing the travel time of the transients along the monitored lines between the relay and the fault point. This traveling time information is provided by the wavelet. Simulation was performed using EMTP, ATP Draw and MATLAB. The results of fault location shown in this paper will be evaluated as an effective suggestion for fault location in real underground transmission line.

  • PDF

Development of Fault Location Method Using SWT and Travelling Wave on Underground Power Cable Systems (SWT와 진행파를 이용한 지중송전계통 고장점 추정 기법 개발)

  • Jung, Chae-Kyun;Lee, Jong-Beom
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.2
    • /
    • pp.184-190
    • /
    • 2008
  • The fault location algorithm based on stationary wavelet transform was developed to locate the fault point more accurately. The stationary wavelet transform(SWT) was introduced instead of conventional discrete wavelet transform(DWT) because SWT has redundancy properties which is more useful in noise signal processing. In previous paper, noise cancellation technique based on the correlation of wavelet coefficients at multi-scales was introduced, and the efficiency was also proved in full. In this paper, fault section discrimination and fault location algorithm using noise cancellation technique were tested by ATP simulation on real power cable systems. From these results, the fault can be located even in very difficult and complicated situations such as different inception angle and fault resistance.

Detection and Location of Cable Fault Using Improved SSTDR (개선된 SSTDR을 이용한 케이블 고장 검출과 위치 계산)

  • Jeon, Jeong-Chay;Kim, Jae-Jin;Choi, Myeong-Il
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.9
    • /
    • pp.1583-1589
    • /
    • 2016
  • This paper proposes an improved spread spectrum time domain reflectometry (ISSTDR) using time-frequency correlation and reference signal elimination method in order to have more accurate fault determination and location detection than conventional (SSTDR) despite increased signal attenuation due to the long distance to cable fault location. The proposed method has a two-step process: the first step is to detect a peak location of the reference signal using time-frequency correlation analysis, and the second step is to detect a peak location of the correlation coefficient of the reflected signal by removing the reference signal. The proposed method was validated through comparison with existing SSTDR methods in open-and short-circuit fault detection experiments of low voltage power cables. The experimental results showed that the proposed method can detect correlation coefficients at fault locations accurately despite reflected signal attenuation so that cable faults can be detected more accurately and clearly in comparison to existing methods.