• 제목/요약/키워드: Boiler Module

검색결과 23건 처리시간 0.023초

멀티버너 보일러용 열교환기 모듈 특성 시험 - 모듈 순서에 따른 특성결과 - (Experimental Study on Thermal Characteristics of Heat Exchanger Modules for Multi Burner Boiler)

  • 강새별;김종진;안준
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2008년도 추계학술대회B
    • /
    • pp.3053-3058
    • /
    • 2008
  • We develop a heat exchanger modules for a multi-burner boiler. The heat exchanger module is kind of a heat recovery steam generator (HRSG). This heat recovery system has 4 heat exchanger modules. The 1st module consists of 27 bare tubes due to high temperature exhaust gas and the others consist of 27 finned tubes. The maximum steam pressure of each module is 1 MPa and tested steam pressure is 0.7 MPa. In order to test these heat exchanger modules, we make a 0.5t/h flue tube boiler (LNG, $40\;Nm^3/h$). We tested the heat exchanger module with changing the position of each heat exchanger module. We measured the inlet and outlet temperature of each heat exchanger module and calculated the heat exchange rate. The results show that if module C is placed at second stage (the 1st stage is always module O, bare tube module), there is no need to attach an additional heat exchanger module. In this case the exit temperature of module C is low enough to enter an economizer which is more effective in heat recovery than a heat exchanger module.

  • PDF

멀티버너 보일러용 열교환기 모듈 특성 시험 - 부하별 특성 결과 - (Experimental Study on Thermal Characteristics of Heat Exchanger Modules for Multi Burner Boiler - Part Load Test Results -)

  • 김종진;최규성;기호충;강새별
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1025-1030
    • /
    • 2008
  • We develop heat exchanger modules for a multi-burner boiler. The heat exchanger module is kind of a heat recovery steam generator (HRSG). This heat recovery system has 4 heat exchanger modules. The 1st module consists of 27 bare tubes due to high temperature exhaust gas and the others consist of 27 finned tubes. The maximum steam pressure of each module is 10 bar and tested steam pressure is 4 bar. In order to test these heat exchanger modules, we make a 0.5t/h flue tube boiler (LNG, $40\;Nm^3/h$). The test results of 100% boiler load show that heat transfer rate of 1st module is 49.7 Mcal/h which is 34% of total heat transfer rate and that of 2nd module is 82.6 Mcal/h which is 57% of total heat transfer rate. The reason of higher the heat transfer rate of 2nd module than that of 1st module is that the 2nd heat exchanger module has finned tubes instead of bare tube. The boiler load 50% results show that only 2 heat exchanger modules are needed to extract the heat from the flue gas to water. From this result, it is very important of optimum design of the first finned tube among all water tubes.

  • PDF

해상 운송을 위한 보일러 모듈의 구조 해석 (Structural Analysis of Boiler Module for Sea-Transportation)

  • 전윤철;김태완;정동관
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집A
    • /
    • pp.788-793
    • /
    • 2001
  • Finite element analysis was carried out to investigate the integrity and reliability of boiler module during sea transportation. The boiler module was supported by steel structure to relieve the instantaneous shock from oceanic wave and its primary parts were strengthened with several reinforcements. Finned tube walls which were used in the furnace wall were assumed as orthotropic plates having equivalent material properties. The bank tubes were also equivalently modeled in accordance with ASME B31.1 for the convenience of finite element modeling. The calculation results were compared with the yield stress of the material. In particular, the bank tube stress, which was evaluated by converting the calculated stresses in equivalent tubes into those in original tubes by using the ratio of diameter, was also examined with yield stress.

  • PDF

드럼형 보일러의 동특성 해석을 위한 모듈 개념의 가상 플랜트 구현 (Implementation of virtual plant using module concept for the dynamic simulation of drum type boiler)

  • 남채호;권상혁;노태정;이광식
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 1997년도 한국자동제어학술회의논문집; 한국전력공사 서울연수원; 17-18 Oct. 1997
    • /
    • pp.476-479
    • /
    • 1997
  • The focus of this paper is to implement of virtual plant using module concept for the dynamic simulation of drum type boiler and to simulate the control trends of dynamic characteristics. MAtlab & Simulink is used for implement virtual plant & analyzation the dynamics & control trends. They are available for analyzing the dynamic characteristics of drum type Boiler by means of applying well measured data to virtual plant.

  • PDF

화력 발전소 드럼형 보일러 시스템의 고장 진단을 위한 퍼지 전문가 시스템의 개발 (Development of Fuzzy Expert System for Fault Diagnosis in a Drum-type Boiler System of Fossil Power Plant)

  • 변승현;박세화
    • 전자공학회논문지B
    • /
    • 제31B권10호
    • /
    • pp.53-66
    • /
    • 1994
  • In this paper, a fuzzy expert system is developed for fault diagnoisis of a drum-type boiler system in fossil power plants. The develped fuzzy espert system is composed of knowledge base, fuzzification module, knowledge base process module, knowledge base management module, inference module, and linguistic approximation module. The main objective of the fuzzy expert system is to check the states of the system including the drum level and detect faults such as the feedwater flow sensor fault, feedwater flow control valve fault, and water wall bube rupture. The fuzzy expert system diagnoses faults using process values, manipulated values, and knowledge base which is built via interviews and questionaries with the experts on the plant operations. Finally, the validity of the developed fuzzy expert system is shown via experiments using the digital simulator for boiler system is Seoul Power Plant Unit 4.

  • PDF

모듈형 수관식 보일러를 위한 열교환 모듈의 열전달 특성 (Heat Transfer Characteristics of Heat Exchange Module for a Water Tube Type Modular Boiler)

  • 안준;김종진;강새별
    • 설비공학논문집
    • /
    • 제24권3호
    • /
    • pp.265-270
    • /
    • 2012
  • A finned tube type heat exchange module has been proposed for a multi-burner water tube boiler. Fin density and length increase in streamwise direction to equalize the evaporation for each module, which makes it difficult to apply conventional bulk design procedure. The design program has been improved by updating data for every row of tubes along the flow. A numerical simulation has been also conducted to evaluate the effect of inlet conditions and validated with experiment. The heat transfer of the first row has been underpredicted by the conventional Zhukauskas correlation, since the acceleration of the flow due to the blockage is not fully inflected. The fin tip temperature is also underpredicted by Bessel solution, because of the interaction with neighboring fins.

다중버너 수관식 보일러를 위한 전열모듈의 열전달 특성: 0.5 t/h급 모형 수치해석 (Heat Transfer Module for Multi-Burner Water Tube Boiler: 0.5 t/h Class Model Simulation)

  • 안준;김종진;강새별
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.528-533
    • /
    • 2007
  • A finned tube type heat transfer module has been proposed for a multi-burner water tube boiler. Fins change their geometry along the streamwise direction to maximize the performance, which makes it difficult to apply conventional bulk analysis. The design program has been improved by updating data for every row of tubes along the flow. A numerical simulation has been also performed to evaluate the effect of inlet conditions and validated with experiment. The heat transfer of the first row has been underpredicted by the conventional Zhukauskas correlation, where the acceleration of the flow due to the blockage is not fully inflected. The fin tip temperature is also underpredicted by Bessel solution, because of the interaction with neighboring fins.

  • PDF

화학플랜트 고온고압부 설계 효율화를 위한 일관시스템 구축 (Development of Integrated Design System for High Temperature, High Pressure Parts for Chemical Plants)

  • 정동관
    • 한국가스학회지
    • /
    • 제2권4호
    • /
    • pp.1-6
    • /
    • 1998
  • 중화학 플랜트의 고온고압 요소인 증기 발생기(steam generator)의 드럼, 헤더 및 헤더 스터브 설계에 응력해석에서 부터 도면자동작도, 제작용 서류 자동생성에 이르기까지의 제반설계과정을 체계적으로 연결시킨 설계정보 통합 관리로 단순 설계오류를 줄이고, 또한 설계변경에 대해 신속한 재설계가 가능한 효율적인 설계를 도모하기 위하여 "피로수명을 고려한 헤더스터브 형상설계 모듈", "TRD301을 기초로한 후육내압부 운전조건(기동/정지 조건) 및 수명평가 모듈", "헤더 및 드럼부 자동작도 모듈"을 개발하였다. 이에 따라 형상설계 모듈을 이용하여 설계된 스터브 형상을 토대로 수명평가 모듈로 수명을 평가한 후 상세설계 도면 및 관련 서류의 자동작도로 이어지는 일관된 종합설계 시스템을 구축하였다.

  • PDF

모듈형 2 t/h급 수관식 보일러의 열전달 특성 (Heat Transfer Characteristics of 2 t/h-Class Modular Water-Tube-Type Boiler)

  • 안준;황상순;김종진;강새별
    • 대한기계학회논문집B
    • /
    • 제36권11호
    • /
    • pp.1127-1133
    • /
    • 2012
  • 본 논문에서는 다중 버너를 채택한 2 t/h 급 수관식 보일러 휜(fin)이 설치된 증발관 모듈이 제안하였다. 휜의 형상은 보일러를 구성하는 각각의 모듈에서 고르게 증발이 이루어질 수 있도록 설계하였다. 이를 위해서 기존의 벌크 설계 과정이 아닌 각각의 열에 대해 에너지 보존을 고려하는 방식으로 설계를 수행하였다. 설계한 증발관 모듈로 2 t/h 급 수관식 보일러를 제작하여 성능을 실험하여 설계를 검증하였다. 설계 과정에서 고려되지 않은 입구 조건 등의 2, 3차원 효과를 파악하기 위하여 수치해석을 병행하였다. 수치해석은 휜 팁의 온도도 예측하기 위하여 증발관의 전도를 포함한 복합열전달해석을 하였다. 휜이 설치될 경우 휜의 크기와 밀도가 증가할수록 열전달 계수가 상관식보다 낮아졌고 수치해석으로 구한 휜 팁의 온도는 해석해로 예측한 값보다 높게 나타났다.

스플리트빔 형태의 고정도 단위 실리카 측정기술 개발에 관한 연구 (A Study on the Development of a pub level Silica Measuring Technology by the Split-beam Type System)

  • 정경열;류길수
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제26권3호
    • /
    • pp.382-388
    • /
    • 2002
  • Dissolved silica is one of fatal components at a boiler facility Therefore, a dissolved silica measurement system should be equipped for managing efficiently the boiler facility. Most of silica measurement systems are composed of a sensor module of single-beam type structure, and silica density is measured with a infrared spectrometry using the Lambert-beer method. However, such a system occurs measuring error of large range and inconsistency of a light source, because of measuring a standard sample and a measuring sample alternatively. This paper introduces a method that the sensor module has a split-beam type structure and a tungsten lamp. The proposed system can measure silica density quickly and precisely more than those composing of a single-beam type structure, because of measuring and comparing with two samples at a same time. And examination results are shown to compare efficiencies of the system and existing commercial products, and for an ammonia influence.