• 제목/요약/키워드: Binary refrigeration

검색결과 38건 처리시간 0.02초

R22 대체냉매의 성능 평가 (Performance evaluation of R22 alternative refrigerants)

  • 송용재;박봉진;정동수;김종보
    • 설비공학논문집
    • /
    • 제10권3호
    • /
    • pp.292-302
    • /
    • 1998
  • In this study, 14 refrigerant mixtures composed of R32, R125, R134a, R143a, R152a, and R1270(Propylene) were tested in a breadboard heat pump in an attempt to replace R22 used in most of the residential air conditioners and heat pumps. The heat pump was of 1 ton capacity and water was employed as the secondary heat transfer fluids. All tests were conducted under ARI test A condition. Ternary mixtures composed of R32, R125, and R134a were shown to have 4∼5% higher COP and capacity than R22 and hence they seem to be very promising candidates to replace R22. On the other hand, ternary mixtures containing R125, R134a, and R152a have lower COP and capacity than R22. R32/R134a binary mixtures show a 7% increase in COP and have the similar capacity to that of R22 and hence they are also good candidates to replace R22. Special care must be exercised when a suction line heat exchanger is used with these mixtures in air conditioners. Finally, the compressor discharge temperatures of all mixtures tested were lower than those of R22 by 15.g∼34.7t, which indicates that these mixtures would offer better system reliability and longer life time than R22.

  • PDF

평판 표면에서 HFC32/HFC152a 혼합냉매의 풀 비등 열전달계수 (Pool Boiling Heat Transfer Coefficient of HFC32/HFC152a on a Plain Surface)

  • 강동규;이요한;정동수
    • 설비공학논문집
    • /
    • 제25권9호
    • /
    • pp.484-492
    • /
    • 2013
  • Nucleate pool boiling heat transfer coefficients (HTCs) are measured with HFC32/HFC152a mixture at several compositions. All data are taken at the liquid pool temperature of $7^{\circ}C$, on a horizontal plain square surface of $9.53{\times}9.53$ mm, with heat fluxes of 10 $kW/m^2$ to 100 $kW/m^2$ with an interval of 10 $kW/m^2$, in the increasing order of heat flux. Test results show that the HTCs of these mixtures are up to 45% lower than those of the ideal HTCs calculated by a linear mixing rule with pure fluids' HTCs, due to the mass transfer resistance associated with non-azeotropic refrigerant mixtures. Pool boiling data show the deduction in HTCs with an increase in GTD of the mixture. The present mixture data agree well with five well known correlations, within 20% deviation.

이산화탄소/프로판 혼합냉매의 냉방성능에 대한 충전량의 영향 및 순환성분비 변화 특성 (Influence of Charging Amounts on the Cooling Performance of $CO_2/Propane$ Mixtures and Concentration Shift Behavior)

  • 김주혁;황윤욱;김민수
    • 설비공학논문집
    • /
    • 제18권11호
    • /
    • pp.851-858
    • /
    • 2006
  • [ $CO_2$ ] and propane mixtures, which are environmentally benign, nontoxic, low in price, and compatible with materials and lubricants, were considered as promising alternative refrigerants. A fully instrumented air-conditioning system was developed for a precise performance evaluation of pure $CO_2$ and $CO_2/propane$ mixtures. In this paper, the effect of the charging amount and circulation concentration on the cooling performance of the system using $CO_2$ and propane mixtures was tested and discussed. Pure $CO_2$ and 85/15, 75/25 and 60/40 binary blends by the charged mass percentage of $CO_2/propane$ were selected as working fluids. An optimum charging amount was proposed as a parameter instead of the degree of subcooling, which can not be well defined in the transcritical cycle, to properly compare the performance between the transcritical and subcritical cycles.

이산화탄소와 프로판 혼합냉매의 기상-액상 평형 (Vapor-Liquid Equilibria of Carbon Dioxide and Propane Mixtures)

  • 김주혁;김민수;김만회
    • 설비공학논문집
    • /
    • 제18권11호
    • /
    • pp.859-866
    • /
    • 2006
  • This paper presents the vapor-liquid equilibrium (VLE) data measured for carbon dioxide and propane mixtures. Their mixtures were considered as promising alternative refrigerants due to good thermophysical properties and negligible environmental impact. The isothermal VLE data were measured at eight temperatures ranging from 253.15 to 323.15 K in the circulation type equipment with a view cell. The binary system was found to be a zeotropic mixture in the tested temperature range and could be correlated with sufficient accuracy by using the Peng-Robinson equation of state (PR EoS) with the van der Waals one fluid mixing rule. A comparison with published experimental VLE data has been carried out by means of the PR equation of state. In addition, the phase behaviors of carbon dioxide and propane mixtures were analyzed based on the measured VLE data.

세관내 R-22 대체냉매의 응축열전달에 관한 연구 (The Condensation Heat Transfer of Alternative Refrigerants for R-22 in Small Diameter Tubes)

  • 손창효;정진호;오종택;오후규
    • 대한기계학회논문집B
    • /
    • 제25권2호
    • /
    • pp.180-186
    • /
    • 2001
  • The condensation heat transfer coefficients of pure refrigerants R-22, R-134a, and a binary refrigerant mixture R-410A flowing in a small diameter tube were investigated. The experiment apparatus consists of a refrigerant loop and a water loop. The main components of the refrigerant loop consist of a variable-speed pump, a mass flowmeter, an evaporator, and a condenser(test section). The water loop consists of a variable-speed pump, an isothermal tank, and a flowmeter. The condenser is a counterflow heat exchanger with refrigerant flowing in the inner tube and water flowing in the annulus. The test section consists of smooth, horizontal copper tube of 3.38mm outer diameter and 1.77mm inner diameter. The length of test section is 1220mm. The refrigerant mass fluxes varied from 450 to 1050kg/(㎡$.$s) and the average inlet and outlet qualities were 0.05 and 0.95, respectively. The main results were summarized as follows ; in the case of single-phase flow, the heat transfer coefficients increase with increasing mass flux. The heat transfer coefficient of R-410A was higher than that of R-22 and R-134a, and the heat transfer for small diameter tubes were about 20% to 27% higher than those predicted by Gnielinski. In the case of two-phase flow, the heat transfer coefficients also increase with increasing mass flux and quality. The condensation heat transfer coefficient of R-410A was slightly higher than that of R-22 and R-134a. Most of correlations proposed in the large diameter tube showed significant deviations with experimental data except for the ranges of low quality and low mass flux.

수평관에서 프로판, 이소부탄, BFC134a를 포함한 혼합냉매의 풀비등 열전달계수 (Pool Boiling Heat Transfer Coefficients of Mixtures Containing Propane, Isobutane and HFC134a on a Plain Tube)

  • 박기정;백인철;정동수
    • 설비공학논문집
    • /
    • 제18권12호
    • /
    • pp.955-963
    • /
    • 2006
  • Nucleate pool boiling heat transfer coefficients (HTCs) were measured with one nonazeotropic mixture of Propane/Isobutane and two azeotropic mixtures of HFC134a/Isobutane and Propane/HFC134a. All data were taken at the liquid pool temperature of $7^{\circ}C$ on a horizontal plain tube with heat fluxes of $10kW/m^2\;to\;80kW/m^2$ with an interval of $10kW/m^2$ in the decreasing order of heat flux. The measurements were made through electrical heating by a cartridge heater. The nonazeotropic mixture of Propane/Isobutane showed a reduction of HTCs as much as 41% from the ideal values. The azeotropic mixtures of HFC134a/Isobutane and Propane/HFC134a showed a reduction of HTCs as much as 44% from the ideal values at compositions other than azeotropic compositions. At azeotropic compositions, however, the HTCs were even higher than the ideal values due to the increase in the vapor pressure. For all mixtures, the reduction in heat transfer was greater with a larger gliding temperature difference. Stephan and $K{\ddot{o}}rner's$ and Jung et al's correlations predicted the HTCs of mixtures with a mean deviation of 11%. The largest mean deviation occurred at the azeotropic compositions of HFC134a/Isobutane and Propane/HFC134a.

저온용 R502 대체냉매의 성능 평가 (Performance of R502 Alternative Refrigerants for Low Temperature Applications)

  • 하종철;황지환;백인철;정동수
    • 설비공학논문집
    • /
    • 제17권10호
    • /
    • pp.883-890
    • /
    • 2005
  • In this study, 2 pure hydrocarbon refrigerants of R1270 (Propylene) and R290 (Propane) and 3 binary mixtures composed of R1270, R29O and R152a were tested in a refrigerating bench tester with a scroll compressor in an attempt to substitute R502 used in most of the low temperature applications. The test bench provided 3\sim3.5$ kW capacity and water and water/glycol mixture were employed as the secondary heat transfer fluids. All tests were conducted under the same external conditions resulting in the average saturation temperatures of -28 and $45^{\circ}C$ in the evaporator and condenser, respectively. Test results showed that all refrigerants tested had $9.6\sim18.7\%$ higher capacity and $17.1\sim27.3\%$ higher COP than R502. The compressor discharge temperature of R1270 was similar to that of R502 while those of all other refrigerants were $23.7\sim27.9\%$ lower than that of R502. For all alternative refrigerants, the amount of charge was reduced up to $60\%$ as compared to R502. Overall, these alternative refrigerants offer better system performance and reliability than R502 and can be used as long term substitutes for R502 due to their excellent environmental properties.

가정용 냉방기의 대체 냉매 성능 분석을 위한 전산 해석 연구 (Computer Simulation Study for Analyzing Alternative Refrigerants in Residential Air-conditioners)

  • 유환규;정동수
    • 태양에너지
    • /
    • 제15권3호
    • /
    • pp.75-90
    • /
    • 1995
  • 본 논문은 가정용 냉방기에 널리 사용되고 있는 HCFC22를 대체할 수 있는 혼합냉매의 개발 및 이들의 성능 연구에 관한 것이다. 현재까지 HCFC22를 대체할 수 있는 순수냉매가 없으므로, 혼합냉매 개발에 본 연구의 초점이 맞추어졌고, 이를 위해 가정용 냉방기를 모사 하는 컴퓨터 프로그램이 개발되었다. 연구에서 개발된 혼합냉매를 구성하는 순수냉매들은 다음과 같다: R32, R124, R125, R134, R134a, R143a, R152a. 컴퓨터 모사 결과들은 다음의 혼합냉매들에 대해서 발표되었다: R32/R134a, R32/R152a, R32/R134, R32/R124, R143a/R134a, R143a/R152a, R143a/R124, R125/R134a, R125/R152a, R125/R124, R32/R152a/R134a, R32/R152a/R134, R32/R152a/R124. 가장 좋은 에너지 효율을 보인 것은 삼원 혼합냉매인 R32/R152a/R124로서, HCFC22에 비해 이것의 성적 계수는 13.7% 높고 냉동 능력은 23% 낮은 것으로 판명되었다. 한편 이원 혼합냉매 중 가장 성능이 좋은 것은 R32/R124로서 이것의 성적 계수는 HCFC22에 비해 13.4% 높고 냉동 체적 용량은 9.6% 낮은 것으로 판명되었다.

  • PDF