• 제목/요약/키워드: Air-conditioning System

검색결과 3,314건 처리시간 0.029초

Fuzzy-Neuro Controller for Control of Air-Conditioning System

  • Lee, Sang-Bae
    • 한국지능시스템학회논문지
    • /
    • 제5권1호
    • /
    • pp.33-42
    • /
    • 1995
  • A practical application of a fuzzy-neuro controller is described for an air-conditioning system. Air-handing units are being widely used for improving the performance of central air-conditioning systems. The fuzzy-neuro control system has two controlled variables, temperature and humidity and three control elements, cooling, heating, and humidification. In order to achieve high efficiency and economical contorl, especially in large offices and industrial buildings, two controllable parameters, temperature and humidity, must be adequately controlled by the three final controlling elements. In this paper a fuzzy-neuro control system is described for controlling air-conditioning systems efficiently and economically. Simulation results confirmed that the fuzzy neuro control system is effective for this multivariable system.

  • PDF

R134a와 R152a 냉매를 이용한 자동차용 에어컨 시스템의 성능 비교 (Performance Comparison of Automotive Air conditioning System by using R134a and R152a)

  • 김종수;남수병;이대웅;유성연;김진혁
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.9-14
    • /
    • 2006
  • This study presented the feasibility of R152a refrigerant as an alternative of R134a which is used in the current automobile air conditioning system. The performance of air conditioning system installed in the actual vehicle was tested using the climate wind tunnel. The experiments were conducted at various refrigerant charge quantities and various driving conditions such as city traffic, highway traffic and parking. Same components and lubricant were used for both R134a and R152a system. The effects of air set values of thermal expansion valve on the performance were also investigated. In case of the R152a system, refrigerant charge quantity can be reduced about 20%, better performance and superior compressor durability is expected due to the lower discharge pressure compared to the R134a system.

  • PDF

R744를 2차 냉매로 사용하는 내부열교환기 부착 R404A 냉동시스템의 성능 분석 (Performance Analysis of R404A Refrigeration System with Internal Heat Exchanger Using R744 as a Secondary Refrigerant)

  • 오후규;손창효;이문빈;전민주
    • 설비공학논문집
    • /
    • 제25권10호
    • /
    • pp.548-554
    • /
    • 2013
  • A thermodynamic analysis of the R404A refrigeration system with an internal heat exchanger using R744 as a secondary refrigerant is presented in this paper to optimize the design for operating parameters of the system. The main results are summarized as follows: The COP increases with increasing subcooling and superheating degree of R404A, internal heat exchanger and compression efficiency of the R404A cycle and evaporating temperature of the R744 cycle and decreasing temperature difference of the cascade heat exchanger and condensing temperature of the R404A cycle. The mass flow ratio decreases with increasing evaporating temperature of the R744 cycle and internal heat exchanger efficiency of the R404A cycle and decreasing subcooling and superheating degree of the R744 cycle, temperature difference of the cascade heat exchanger and condensing temperature of the R404A cycle.

신경망무고장모델과 이중퍼지로직을 사용한 냉방기 고장진단 알고리즘 (Fault Diagnosis Algorithm of an Air-conditioning System by using a Neural No-fault Model and a Dual Fuzzy Logic)

  • 한도영;정남철
    • 설비공학논문집
    • /
    • 제18권10호
    • /
    • pp.791-799
    • /
    • 2006
  • The fault diagnosis technologies may be applied in order to decrease the energy consumption and the maintenance cost of an air-conditioning system. In this paper, a fault diagnosis algorithm was developed by using a neural no-fault model and a dual fuzzy logic. Five different faults, such as the compressor valve leakage, the liquid line blockage, the condenser fouling, the evaporator fouling, and the refrigerant leakage of an air-conditioning system, were considered. The fault diagnosis algorithm was tested by using a fault simulation facility. Test results showed that the algorithm developed for this study was effective to detect and diagnose various faults. Therefore, this algorithm may be practically used for the fault diagnosis of an air-conditioning system.

가정용 공조기의 응축기 적용 알루미늄 열교환기의 성능 평가 (Performance evaluation of brazed aluminum heat exchangers for a condenser in residential air-conditioning applications)

  • 김만회;김권진
    • 설비공학논문집
    • /
    • 제10권1호
    • /
    • pp.44-55
    • /
    • 1998
  • The evaluation of aluminum flat tube and louver fin heat exchangers for a condenser in residential air-conditioning applications has been conducted. A series of tests for two-different brazed aluminum heat exchangers was performed and the results were compared with conventional fin and tube heat exchangers for residential air-conditioning system. Refrigerant charge amount for a window-system air-conditioner with the brazed aluminum condenser is decreased by 35% and the volume and material of heat exchanger can be reduced by 50% compared to the conventional fin and tube heat exchangers.

  • PDF

PMV 지표에 의한 개별 공조시스템(PACS)의 쾌적성 평가에 관한 연구 (Evaluation of Thermal Comfort in Task Area with Personal Air-Conditioning System(PACS) b PMV Index)

  • 최익순;정광섭;박영칠;한화택;이정재
    • 설비공학논문집
    • /
    • 제13권7호
    • /
    • pp.647-652
    • /
    • 2001
  • The thermal comfort of indoor spaces is very important factor in our life. Regions, cultures, climates and individual difference for establishing thermally comfortable environments should be considered carefully because these factors have a large influence on the thermal comfort doing some complicated interactions with environmental, psychological and physical elements. Recently, predicted mean vote(PMV) based on the heat transfer theory between environmental factors and human bodies has evaluated by many researchers and widely used nowadays. The objective of this study is to evaluate the thermal comfort in workspaces with personal air conditioning system using the measurements of environmental comfort parameters and the questionnaire survey of occupant's thermal senses with response to the environment.

  • PDF

멀티형 냉방시스템의 압축기 제어 (Compressor Control of a Multi-type AIr Conditioning System)

  • 한도영;권형진
    • 설비공학논문집
    • /
    • 제13권8호
    • /
    • pp.780-786
    • /
    • 2001
  • For the compressor speed control of a multi-type air conditioning system, a fuzzy control algorithm was developed. The sum of zone temperature errors and its derivative were used as input variables, and the compressor speed was selected as the output variable. To test the effectiveness of the control algorithm, one outdoor environmental chamber and four indoor environmental chambers were used. In the chambers the zone temperature step change test and the indoor unit change over test were performed. Test results showed that, for the control of compressor speed, the fuzzy control algorithm was more effective than the conventional proportional control algorithm for the energy conservation.

  • PDF