• Title/Summary/Keyword: Air side heat transfer coefficient

Search Result 69, Processing Time 0.024 seconds

Air-Side Performance of Fin-and-Tube Heat Exchangers Having Sine Wave Fins and Oval Tubes (사인 웨이브 핀과 타원관으로 구성된 핀-관 열교환기의 공기측 성능)

  • Choi, Byung-Nam;Yi, Fung;Sim, Hyun-Min;Kim, Nae-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.5
    • /
    • pp.279-288
    • /
    • 2013
  • Heat transfer and pressure drop characteristics of fin-and-tube heat exchangers having sine wave fins and oval tubes were investigated. Oval tubes having an aspect ratio of 0.6 were made, by deforming 12.7 mm round tubes. Twelve samples, having different fin pitch and tube row, were tested. The effect of fin pitch on the j and f factors was negligible. The effect of the tube row on the j factor, however, was different from that of common fin-and-tube heat exchangers having plain fins and round tubes. The highest j factor was obtained for a two-row configuration, while the lowest one was obtained for a one-row configuration. A possible reason was attributed to the flow mixing characteristics of the sine wave channel of the present geometry. Comparison with a plain fin-and-tube heat exchanger having 15.88 mm O. D. round tube reveals that the present oval fin-and-tube heat exchanger shows generally superior thermal performance, except for the one-row configuration.

Effects of Fin Configuration on the Evaporator Performance (휜 형상에 따른 증발기의 전열 성능)

  • Lee, Jin Ho;Kwon, O Kap
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.2 no.1
    • /
    • pp.27-36
    • /
    • 1990
  • An experimental investigation was made to study the performance characteristics of evaporator having different fin configurations and tube inner grooves. Three different types of fin such as super slitted fin, slitted fin, plain fin, and two types of tube such as inner grooved tube, and bare tube, are tested varying the air velocity, evaporation temperature and superheat of refrigerant. Results show that in the range of air side Reynolds number $3{\times}10^3\;-\;1.5{\times}10^4$ evaporator with super slitted fin and inner grooved tube shows best performance. It is 80% higher in overall heat transfer coefficient and 2.6 times higher in pressure loss compared to that with plain fin inner grooved tube. Friction factor is found to be almost independent of evaporating temperature and degree of superheat, while Colburn j factor varies with evaporating temperature.

  • PDF

An Experiment of Natural Circulated Air Flow and Heat Transfer in the Passive Containment Cooling System (격납용기 피동냉각계통내 자연순환 공기유량 및 열전달 실험연구)

  • Ryu, S.H.;Oh, S.M.;Park, G.C.
    • Nuclear Engineering and Technology
    • /
    • v.26 no.4
    • /
    • pp.516-525
    • /
    • 1994
  • Since the TMI and Chernobyl accidents, many passive safety features are suggested in advanced reactors in order to enhance the safety in future nuclear power plants. In order to verify the effectiveness and provide the data for detailed design of passive cooling system, in the present work, the effects of air inlet position and external condition on the natural circulated air flow rate and the natural and forced convective heat transfer coefficient have been investigated for the one-side heated closed path such as the passive containment cooling system of the Westinghouse's AP-600. A series of experiments have been peformed with the 1/26th scaled segment type test facility of the AP-600 passive containment. Under natural and forced convection, the air velocities and temperatures are measured at several points of the air flow path. The experimental result are compared with a simple one-dimensional model and it shows a good agreement.

  • PDF

An Experimental Study on Air-Side Performance of Fin-and-Tube Heat Exchangers Having Compound Enhanced Fins (복합 전열 촉진 핀이 적용된 핀-관 열교환기의 성능에 대한 실험적 연구)

  • Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.7
    • /
    • pp.4364-4374
    • /
    • 2015
  • In this study, heat transfer and friction characteristics of compound enhanced fin-and-tube heat exchangers were experimentally investigated. Louver-finned heat exchangers were also tested for comparison purpose. The effect of fin pitch on j and f factor was negligible. The j factor decreased as number of tube row increased. However, f factor was independent of number of tube row. Louver fin samples yielded higher j and f factors than compound enhanced fin samples. For one row, j and f factors of louver fin were 23% and 27% higher than those of compound enhanced fin. For two row, those were 11% and 8%, and for three row, those were 10% and 9%. However, heat transfer capacities at the same pressure drop of the compound enhanced fins were 6.4% for one row, 11.1% for two row and 13.6% for three row larger than those of louver fins, Existing louver fin correlation overpredicted the present j factors and underpredicted the present f factors.

An Experimental Study on Air-Side Performance of Fin-and-Tube Heat Exchangers Having Compound Enhanced Fins Under Wet Condition (복합 전열 촉진 핀이 적용된 핀-관 열교환기의 습표면 성능에 대한 실험적 연구)

  • Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.9
    • /
    • pp.5778-5788
    • /
    • 2015
  • In this study, wet surface heat transfer and friction characteristics of compound enhanced fin-and-tube heat exchangers were experimentally investigated. Louver-finned heat exchangers were also tested for comparison purpose. The effect of fin pitch on j and f factor was negligible. Both j and f factor decreased as number of tube row increased. Compound enhanced fin samples yielded higher j and f factors than louver fin samples. For one row, j and f factors of compound enhanced fin samples were 11% and 43% higher than those of louver fin samples. For two row, those were 8% and 50%, and for three row, those were 17% and 53%. Heat transfer capacities at the same pressure drop of the compound enhanced fin samples were 2.0% for one row, 3.1% for two row and 8.4% for three row larger than those of louver fin samples, Data were compared with predictions of existing louver fin correlations.

Analysis on Heat Loss of Single-span Greenhouse Using Small-scaled Wind Tunnel (소형풍동을 이용한 단동 비닐온실의 열손실 분석)

  • Kim, Young Hwa;Kim, Hyung kow;Lee, Tae suk;Oh, Sung sik;Ryou, Young sun
    • Journal of Bio-Environment Control
    • /
    • v.29 no.1
    • /
    • pp.73-79
    • /
    • 2020
  • The objective of this study is to analyze the heat transfer loss of covering materials in a single-span plastic greenhouse under the steady-state wind environment. To achieve this objective, the following were conducted: (1) design of a small-scaled wind tunnel (SCWT) to analyze heat losses of the greenhouse and its performance; (2) determination of the overall heat transfer coefficient (OHTC) for the covering materials using a small-scaled greenhouse model. The SCWT consists of the blowing, dispersion, steady flow, reduction and testing areas. Each part of the SCWT was customized and designed to maintain air flow at steady state and to minimize the variances in the SCWT test. In this study, the OHTCs of the covering materials were calculated by separating each with the roof, side wall, front and back of the small-scaled greenhouse model. The results of this study show that the OHTC of the roof increases as wind speed increases but the zones in which the increase rate of the OHTC decreased, were distinguished by wind tunnel wing speed of 2 ms-1. For the side wall, the increase rate of the OHTC was particularly higher in the 0-1 ms-1 zone.

Air-Side Performance of Fin-and-Tube Heat Exchangers Having Non-Symmetric Slit Fins Under Wet Condition (비대칭형 슬릿 핀이 적용된 핀-관 열교환기의 습표면 성능)

  • Kim, Nea-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.6
    • /
    • pp.3698-3707
    • /
    • 2015
  • In this study, wet surface heat transfer and friction characteristics of non-symmetric slit-finned heat exchangers are experimentally investigated. Louver-finned heat exchangers are also tested for comparison purpose. The effect of fin pitch on j and f factor is negligible. Louver fin samples yield higher j and f factors than slit fin samples. For one row, j and f factors of louver fin are 27% and 31% higher than those of slit fin. For two row, j and f factors of louver fin are 15% and 30% higher. Both j and f factor decrease as the number of tube row increases. For one row, average j/f ratios of slit fin samples are 3.4% larger than those of louver fin samples. For two row, average j/f ratios of slit fin samples are 11.5% larger. A new correlation was developed using the present data.

Wet Surface Air-Side Performance of Fin-and-Tube Heat Exchangers Having Sine Wave Fins and Oval Tubes (사인 웨이브 핀과 타원관으로 구성된 핀-관 열교환기의 공기측 습표면 성능)

  • Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.4
    • /
    • pp.2415-2423
    • /
    • 2015
  • Experiments were conducted on sine wave fin-and-tube heat exchangers having oval tubes under wet condition. Oval tubes having an aspect ratio of 0.6 were made, by deforming 12.7mm round tubes. Twelve samples, having different fin pitch and tube row, were tested. Results showed that, for oval tube samples, the effect of fin pitch on j and f factor was not significant. As for the effect of tube row, the lowest j factor was obtained for one row configuration(81% of two row configuration), which is clear contrast to round tube samples, where the highest j factor was obtained for one row configuration. Possible reasoning is provided considering the flow and heat transfer characteristics of sine wave channel combined with connecting oval tubes. Comparison of $j/f^{1/3}$ with plain fin-and-tube heat exchanger having 15.9mm O.D. round tube reveals that present oval fin-and-tube heat exchanger shows superior thermal performance except for one row configuration. In other words, $j/f^{1/3}$ of the two row oval tube heat exchanger was 1.6~2.5 times larger than those of round tube heat exchanger, 1.4~2.4 times larger for three row configuration and 1.2~2.8 times for four row configuration.

Numerical Study on the Cooling Characteristics of a Passive-Type PEMFC Stack (수동공기공급형 고분자 전해질 연료전지 스택에서의 냉각특성에 대한 전산해석 연구)

  • Lee, Jae-Hyuk;Kim, Bo-Sung;Lee, Yong-Taek;Kim, Yong-Chan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.34 no.8
    • /
    • pp.767-774
    • /
    • 2010
  • In a passive-type PEMFC stack, axial fans operate to supply both oxidant and coolant to cathode side of the stack. It is possible to make a simple system because the passive-type PEMFC stack does not require additional cooling equipment. However, the performance of a cooling system in which water is used as a coolant is better than that of the air-cooling system. To ensure system reliability, it is essential to make cooling system effective by adopting an optimal stack design. In this study, a numerical investigation has been carried out to identify an optimum cooling strategy. Various channel configurations were applied to the test section. The passive-type PEMFC was tested by varying airflow rate distribution at the cathode side and external heat transfer coefficient of the stack. The best cooling performance was achieved when a channel with thick ribs was used, and the overheating at the center of the stack was reduced when a case in which airflow was concentrated at the middle of the stack was used.