• 제목/요약/키워드: 22kV Power Cable

검색결과 135건 처리시간 0.026초

22.9 kV CV 전력케이블의 14주기 고온 열화에 대한 Lightning-Impulse 특성 (Lightning Impulse Characteristics for 22.9 kV CV Power Cable Before and After Cyclic Aging for 14days)

  • 김위영;윤대혁;박태곤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 C
    • /
    • pp.1549-1551
    • /
    • 2001
  • Cyclic aging for 14 days is performed to remove a large amount of the volatiles found in freshly manufactured cable. In this paper, we examined lightning impulse characteristics of 22.9 kV CV power cable before and after cyclic aging for 14days. As the result, the breakdown voltage after aging under normal temperature was lower than that before aging, and the breakdown voltage after aging under hot temperature was lower than that before aging. We found that the dispersion of lightning impulse breakdown voltage before 14 cyclic aging test were reduced rather than those after 14 cyclic aging test.

  • PDF

Design of HTS power cable with fault current limiting function

  • Kim, Dongmin;Kim, Sungkyu;Cho, Jeonwook;Kim, Seokho
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제22권1호
    • /
    • pp.7-11
    • /
    • 2020
  • As demand for electricity in urban areas increases, it is necessary to improve electric power stability by interconnecting neighboring substations and high temperature superconductor (HTS) power cables are considered as a promising option due to its large power capacity. However, the interconnection of substations reduces grid impedance and expected fault current is over 45 kA, which exceeds the capacity of a circuit breaker in Korean grid. To reduce the fault current below 45 kA, a HTS power cable having a fault current limiting (FCL) function is considered by as a feasible solution for the interconnection of substations. In this study, a FCL HTS power cable of 600 MVA/154 kV, transmission level class, is considered to reduce the fault current from 63 kA to less than 45 kA by generating an impedance over 1 Ωwhen the fault current is induced. For the thermal design of FCL HTS power cable, a parametric study is conducted to meet a required temperature limit and impedance by modifying the cable core from usual HTS power cables which are designed to bypass the fault current through cable former. The analysis results give a minimum cable length and an area of stainless steel former to suppress the temperature of cable below a design limit.

고온초전도 전력케이블의 냉각조건 (Cooling Condition of HTS Power Cable)

  • 김동락;김승현;양형석;조승연;이제묘
    • 한국초전도저온공학회:학술대회논문집
    • /
    • 한국초전도저온공학회 2002년도 학술대회 논문집
    • /
    • pp.35-36
    • /
    • 2002
  • High temperature super conducting(HTS) cable system for power transmission are under development that will be cooled by sub-cooled liquid nitrogen to provide cooling of the cable and termination. The target of the development during the first 3-years stage is 22.9kV/50MVA class and 30m length cold dielectric type 3-phase power cable. The essential features of the HTS cable cryogenic system and performance conditions for the design of power cable will be discussed.

  • PDF

멀티케이블을 이용한 초전도 전력케이블의 구성에 관한 연구 (A Study on the Composition of Superconducting Power Cable Using the Multi-cable)

  • 최석진;이상진;심기덕;조전욱;이수길;고태국
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제12권1호
    • /
    • pp.42-46
    • /
    • 2010
  • The HTS power cable is composed of 2 layers for transmission and 1 layer for shield. The superconducting tapes of transmission layers and shield layer are wound in a cylindrical shape with a winding pitch. The radius of cylinder and the number of superconducting tapes are decided considering to the transmission current capacity and the critical current of superconducting tapes. The increasement of transmission current capacity will increase in volume of HTS cable system. In this paper, the composition method of supercondcuting power cable using the multi-cable is presented. The coated conductor tape can be wound on the smaller cylinder because it has the smaller critical bending diameter than the BSCCO tape. A small-scale cable was composed using the coated conductor tapes and a multi-cable is composed using a small-scale cable considering to transmission current capacity. Even increase of transmission current capacity, this method has advantage that the HTS superconducting power cable can be composed easily. The 22.9 kV and 154 kV superconducting power cable was composed using the presented method.

14주기 열화에 따른 22.9kV 전력케이블의 Lightning-Impulse 특성분석 (Lightning Impulse Characteristics for 22.9kV Power Cable Before and After Cyclic Aging for 14days)

  • 김위영;허종철;박태곤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2274-2276
    • /
    • 2005
  • Cyclic aging for 14days is performed to remove the large amount of the volatiles found in freshly manufactured cable. In this paper, we examined lightning impulse characteristics of power cable before and after cyclic aging for 14days. As the result, the breakdown voltage after aging was lower than that before aging, but the breakdown voltage after aging was higher than that before aging in TR CNCV-W $60mm^2$ power cable.

  • PDF

Insulation Characteristics of the Model Cable for 22.9 kV Class HTS Power Cable

  • Kim, Hae-Jong;Seong, Ki-Chul;Cho, Jeon-Wook;Kwag, Dong-Soon;Cheon, Hyeon-Gweon;Kim, Sang-Hyun
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 하계학술대회 논문집 Vol.6
    • /
    • pp.542-543
    • /
    • 2005
  • In this paper, describes the fabrication and dielectric insulation characteristics experimental results of the model cable for the 22.9kV class HTS power cable. The model cable were tested with partial discharge(PD), AC and impulse withstand voltage in liquid nitrogen($LN_2$) and liquid nitrogen pressure. In these test results, PD inception stress and AC, impulse breakdown strength increase as the pressure of the liquid nitrogen increases.

  • PDF

초전도(신)전력계통 고장전류 분석 및 병렬한류시스템 (A fault current analysis and parallel FCL scheme on superconducting new power system)

  • 윤재영;이승렬;김종율
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제8권1호
    • /
    • pp.49-53
    • /
    • 2006
  • This paper specifies the new power supply paradigm converting 154kV voltage level into 22.9kV class with equivalent capacity using superconducting rower facilities and analyze the fault current characteristics with and without HTS-FCL (High Temperature Superconducting-Fault Current Limiter). Superconducting new power system is the power system to which applies the 22.9kV HTS cable in parallel to HTS transformer and HTS-FCL with low-voltage and mass-capacity characteristics replacing 154kV conventional cable and transformer. The fault current of superconducting new power system will increase greatly because of the mass capacity and low impedance of HTS transformer and cable. This means that the HTS-FCL is necessary to reduce the fault current below the breaking current of circuit breaker. This paper analyze the fault current and suggests the parallel HTS-FCL scheme complementing the inherent problem of HTS-FCL, that is recovery after quenching is impossible within shorter than a few seconds.

고온초전도 케이블 단말용 cryostat 설계 (Design of Termination Cryostat for HTS Power Cable)

  • 양형석;김승현;김동락;조승연;김도형;류희석;성기철
    • 한국초전도저온공학회:학술대회논문집
    • /
    • 한국초전도저온공학회 2003년도 학술대회 논문집
    • /
    • pp.160-162
    • /
    • 2003
  • Termination cryostat for 22.9kV, 1.26kA-class HTS power cable has been designed. The cryostat consists of vacuum vessel, liquid nitrogen vessel, current lead and HTS power cable. The current lead and the HTS power cable are connected in liquid nitrogen vessel cooled by forced-circulation subcooled liquid nitrogen. The maximum total heat load of this cryostat is expected to be 150w. In this paper, the detailed design of the termination cryostat is mentioned.

  • PDF

22.9kV 배전선로 절연전선의 부식 검출 시스템 개발에 대한 연구 (A Study on the Development of Corrosion Detecting System for 22.9 kV Distribution Power Line Insulation Cable)

  • 김용준;오용철;이건영
    • 전기학회논문지
    • /
    • 제60권7호
    • /
    • pp.1410-1416
    • /
    • 2011
  • A corrosion detecting system for 22.9 kV distribution power line insulation cable, which can travel autonomously along the live line, is proposed. Eddy current test method is employed to detect the corrosion, and the system developed here is capable of detecting internal corrosion of a ACSR-OC. Somewhat details of the electrical and mechanical mechanism of the system and traveling algorithm are introduced. Experimental results applied to the sample cables having artificial corrosion and the operating distribution lines are provided. From the result, we confirmed that the system is useful for detecting internal corrosion of a ACSR, and is expected to be a new non-destructive testing equipment in the area of diagnosis for the distribution power line.