• 제목/요약/키워드: 2상유동 마찰배수

검색결과 5건 처리시간 0.02초

사다리꼴 미세유로의 대류비등 2상유동 : 1부-압력강하 특성 (Convective Boiling Two-phase Flow in Trapezoidal Microchannels : Part 1-Pressure Drop Characteristics)

  • 김병주;김건일
    • 설비공학논문집
    • /
    • 제23권1호
    • /
    • pp.87-94
    • /
    • 2011
  • Characteristics of two-phase pressure drop in microchannels were investigated experimentally. The microchannels consisted of 9 parallel trapezoidal channels with each channel having $205\;{\mu}m$ of bottom width, $800\;{\mu}m$ of depth, $3.6^{\circ}$ of sidewall angle, and 7 cm of length. Pressure drops in convective boiling of Refrigerant 113 were measured in the range of inlet pressure 105~195 kPa, mass velocity $150{\sim}920\;kg/m^2s$, and heat flux $10{\sim}100\;kW/m^2$. The total pressure drop generally increased with increasing mass velocity and/or heat flux. Two-phase frictional pressure drop across the microchannels increased rapidly with exit quality and showed bigger gradient at higher mass velocity. A critical review of correlations in the literature suggested that existing correlations were not able to match the experimental results obtained for two-phase pressure drop associated with convective boiling in microchannels. A new correlation suitable for predicting two-phase friction multiplier was developed based on the separated flow model and showed good agreement with the experimental data.

미세 수평 사각 유로 내에서의 비등 유동 압력강하에 관한 실험적 연구 (An Experimental Study on Pressure Drop of Boiling Flow within Horizontal Rectangular Channels with Small Heights)

  • 이상용;이한주
    • 대한기계학회논문집B
    • /
    • 제25권9호
    • /
    • pp.1219-1226
    • /
    • 2001
  • Pressure drops were measured for the flow boiling process within horizontal rectangular channels. The gap between the upper and the lower plates of each channel ranges from 0.4 to 2mm while the channel width being fixed to 20mm. Refrigerant 113 was used as the test fluid. The mass flux ranges from 50 to 200kg/㎡s and the channel walls were uniformly heated up to 15kW/㎡. The quality range covers from 0.15 to 0.75. The present experimental conditions coincide with the operating conditions of compact heat exchangers in which the liquid and gas flows are laminar and turbulent. The measured results were well represented by the two-phase frictional multiplier of Lee (2001) which has been developed for air-water two-phase flows within the deviation of $\pm$20%.

미세 수평 사각유로에서의 2상 유동 압력강하에 관한 실험적 연구 (An Experimental Study on the Two-Phase Flow Pressure Drop Within Horizontal Rectangular Channels with Small Gap Heights)

  • 이한주;이상용
    • 대한기계학회논문집B
    • /
    • 제23권5호
    • /
    • pp.637-645
    • /
    • 1999
  • Horizontal two-phase flow pressure drop within rectangular channels with small gap heights have been examined experimentally. The gap heights range from 0.4mm to 4mm corresponding to aspect ratios(the channel height divided by the width) from 0.02 to 0.2. Water and air were used as the test fluids with the superficial velocity ranges being 0.03-2.39m/s and 0.05-18.7m/s, respectively. The experimental results In rectangular channels were compared with the Lockhart-Martinelli correlation, which are widely used for conventional round tube. The Lockhart-Martinelli correlation turned out to be Inappropriate to represent the present experimental data. In this respect, considering the aspect ratio and gap-height effects, an empirical correlation on two-phase flow pressure drop was proposed. The proposed correlation successfully covers the bubbly, plug, slug and annular flow regimes.

오프셋 스트립 휜이 있는 협소 사각유로의 비등열전달 (Boiling Heat Transfer in a Narrow Rectangular Channel with Offset Strip Fins)

  • 김병주;정은수;손병후
    • 설비공학논문집
    • /
    • 제16권10호
    • /
    • pp.977-983
    • /
    • 2004
  • An experimental study on saturated flow boiling heat transfer of R113 was peformed in a vertical narrow rectangular channel with offset strip fins. Two-phase pressure gradients and boiling heat transfer coefficients in an electrically heated test section were measured in the range of quality $0{\sim}0.6$, mass flux $17{\sim}43kg/m^{2}s$, and heat flux of $500{\sim}3,000W/m^2$ Two-phase friction multipliers were determined as a function of Lockhart-Martinelli parameter. Local boiling heat transfer coefficients were analysed in terms of mass flux, heat flux and local vapor quality. Correlation for boiling heat transfer coefficients was proposed, which was in good agreement with experimental data.

마이크로관 내 압력강하 특성 및 상관식에 관한 연구 (Pressure Drop in Microtubes and Correlation Development)

  • 황윤욱;김주혁;김민수
    • 설비공학논문집
    • /
    • 제18권1호
    • /
    • pp.38-46
    • /
    • 2006
  • The characteristics about the pressure drop in microtubes have been investigated. The test tubes are the circular, seamless, stainless steel tubes with an inner diameter of 0.244, 0.430, and 0.792 mm, respectively. R-l34a was used as a test fluid. Early flow transition which has been reported in some previous studies is not found in single-phase flow pressure drop tests. The conventional theory between friction factor and Reynolds number predicted the experimental friction factors within an absolute average deviation of $8.9\%$. The two-phase flow pressure drop increases for higher quality and mass flux, and for reduced inner diameter. The existing correlations fail to predict the experimental data. A new correlation to predict the two-phase flow pressure drop is developed in the form of the Lockhart-Martinelli correlation. The effects of the tube diameter and the surface tension were considered, and the correlation predicted the experimental data within an average absolute deviation of $8.1\%$.