• 제목/요약/키워드: 휜-관열교환기

검색결과 2건 처리시간 0.018초

냉매유로를 1차원 배열화한 휜-관 열교환기 성능해석 (Performance Evaluation of a Fin-Tube Heat Exchanger Using One-Dimensionalized Refrigerant Circuit)

  • 김두환;예휘열;이관수;차우호
    • 설비공학논문집
    • /
    • 제20권12호
    • /
    • pp.833-843
    • /
    • 2008
  • A new method is presented for developing a simulation program which can analyze the heat transfer characteristics of fin-tube heat exchanger. This method is able to describe several types of refrigerant circuit arrangement. The delivery path of air and refrigerant properties is simplified by transforming three-dimensional array into one-dimensional array. By comparing simulated results with experiment results, the deviation was 8.2%. Several fin-tube heat exchangers of different design factors and operating conditions were simulated using this program. It was shown that this program could be used for designing practical fin-tube heat exchangers.

응축기의 설계조건에서 R22와 R134a의 압력강하 예측 및 실험 (Prediction and Experiment of Pressure Drop of R22 and R134a on Design Conditions of Condenser)

  • 강신형;변주석;김창덕
    • 에너지공학
    • /
    • 제15권4호
    • /
    • pp.243-249
    • /
    • 2006
  • 본 실험적 연구는 슬릿휜-관열교환기의 냉매측 압력강하에 대하여 수행하였다. 응축기의 설계조건에서 미세휜관내 냉매 R22와 R134a의 압력강하에 대한 실험데이터와 앞서 제안한 상관관계식과 상호 비교하였다. 실험은 냉매 R22와 Rl34a의 응축기 입구온도 $60^{\circ}C$, 질량유속 $150{\sim}250\;kg/m^{2}s$ 범위에서 수행하였다. 공기의 유입조건은 건구온도 $35^{\circ}C$, 상대습도 40%이며, 공기유속의 범위는 $0.68{\sim}1.43\;m/s$이다. 실험결과 응축기의 과냉도 $5^{\circ}C$ 조건에서 R134a의 압력강하는 R22보다 $22{\sim}22.6%$ 높게 나타났으며, 냉매의 질량유속 $200{\sim}250\;kg/m^{2}s$의 범위에서 실험으로부터 측정한 R22와 Rl34a의 압력강하는 예측결과와 ${\pm}20%$내에 일치하였다.