Characteristics of Water Quality Change of Urban River according to Installation of Interceptors and Wastewater Treatment Plant (차집관로와 하수처리시설의 설치에 따른 도시하천의 수질변화 특성)

  • Zhou, Juan Juan;Lim, Bong Su
    • Journal of Korean Society of Environmental Engineers
    • /
    • v.36 no.12
    • /
    • pp.813-820
    • /
    • 2014
  • In this study, the characteristics of water quality change of the three streams in Daejeon were analyzed according to the expanded installation of interceptors and wastewater treatment plant (WTP). Gabcheon 5 (Singu Bridge) location showed the maximum difference of the highest and lowest concentrations in the last decade. However, the recent water quality of this location was worse than other locations, because of the impact of the effluent from the WTP. In the upstream of the WTP, the Daejeon stream was relatively better than the other locations in organic pollution reduction, and this was caused by the investment for the management of the interceptors in three streams of Daejeon. According to the water quality standard of the stream water quality, the recent water quality of the three streams in Daejeon was acceptable within them in the most of the water quality items, but because the total phosphorus concentration of the upstream such as Daejeon stream, Yudeng stream, Gabchen 3 location did not reach the standard values, a better management of the interceptor was required in the upstream of WTP than its downstream. The upstream of WTP also required a better management of the interceptor than the downstream. The operation and management of WTP was required a high efficiency because the water quality of the effluent from the WTP incurred an adverse effect to the target water quality in the location of the total water pollution load management system.

The Study on the Estimation of Emission from Sewage Treatment Plant and Manure Treatment Plant (하수 및 분뇨처리시설에서 악취물질 배출량 산정에 관한 연구)

  • 전의찬;사재환;김기현;이성호
    • Proceedings of the Korea Air Pollution Research Association Conference
    • /
    • 2003.11a
    • /
    • pp.87-88
    • /
    • 2003
  • 최근 민원의 약 20%를 차지하며, 대기질 관리 대상 중의 하나인 악취는 호흡기장애, 순환기장애, 소화기능장애, 수면장애 둥을 유발시켜는 등 인체에 다양한 악영향을 미치고 있으며, 다양한 성분이 극히 낮은 농도로 존재할 경우에도 인간의 감각기관을 가즉하게 된다. 또한, 쓰레기매립시설, 소각시설, 하수처리시설, 분뇨처리시설, 음식물쓰레기처리시설 등의 환경기초시설과 기타 생활악취 배출원들은 주로 주민의 생활주변에 밀접하게 연관되어 있는 시설이다. (중략)

  • PDF

A Study on Pre-treatment Facility for Foodwaste and Sewage Sludge Mixture (음식폐기물과 하수슬러지 병합처리를 위한 전처리시설에 관한 연구)

  • Kim, Jong-Oh;Lee, Chang-Ho;Kim, Ji-Young
    • Journal of the Korea Organic Resources Recycling Association
    • /
    • v.11 no.1
    • /
    • pp.84-89
    • /
    • 2003
  • The purpose of this study was to evaluate and improve the pre-treatment facility for foodwaste and sewage sludge mixture treatment. The process of foodwaste pre-treatment consists of storage, classification with crushing, and thickening. The effluent of sewage treatment facility was used as the diluting and washing water. The panicle size of foodwaste after pre-treatment was almost under 2mm, the mixture of foodwastes and sewage sludge showed an advantage to the anaerobic digestion. The amount of gas production increased from 0.8ton/day ($CH_4$ : 0.5ton/day) to 3.5ton/day ($CH_4$ : 2.3ton/day) after the anaerobic digestion of the foodwastes and sewage sludge mixture. The amount of sludge cake increased from 11.2ton/day to 21.2ton/day. Therefore, the proper operation of the foodwaste pre-treatment facility was contributed to the efficient anaerobic digestion of foodwaste and sewage sludge mixture treatment.

  • PDF

A study on the improvement for advanced wastewater treatment of rural community sewage treatment plant using GPS-X (PS-X을 이용한 소규모 마을하수도처리시설의 고도처리개선 연구)

  • Gu, Bon-Woo;Oh, Dea-Min;Lee, Young-Shin;Choi, Gun-Youl;Yang, Jong-Woon;Lee, Jung-Chul
    • Proceedings of the KAIS Fall Conference
    • /
    • 2009.05a
    • /
    • pp.855-858
    • /
    • 2009
  • 우리나라 농어촌 지역은 경제 발전과 함께 식생활의 개선 및 주택 개량, 수세식 화장실 보급 확대등으로 생활 오수 발생량이 크게 늘고 있는 실정이다. 이에 1994년부터 정부는 하수도법에 의한 수질개선 대책 사업등으로 마을 하수도 사업이 진행되어 왔으나, 현재 몇몇 농어촌 지역의 마을하수도 시설의 노후화 및 처리용량 부적합 등으로 현재 질소, 인의 처리효율이 방류수 수질기준에 적합하지 못하여 주변 수역의 수질개선을 위한 고도처리개선이 필요한 실정이다. 따라서, 본 연구는 소규모 마을하수도처리시설에 적용하고자 하는 고도처리개선공정을 GPS-X(General Purpose Simulator) 시뮬레이션으로 계획수질을 추정하여 대상시설에 적합한 고도처리개선공정을 설계하였다. 측정결과, 각 반응조별 시뮬레이션에서 혐기조, 무산소조, SBR1, SBR2 모두 일정한 처리형태를 보였으며, 시뮬레이션을 통한 유출수 예측결과, SS의 경우 97.3%, BOD 97.5%, TCOD 87.3%, TP 81.1%, TN 74.5%의 제거효율을 보여, 안정적인 고도처리효과를 나타내는 것으로 판단된다.

  • PDF

Development of Gutter Storage System for Urban Inundation Reduction (도시침수 저감을 위한 측구 저류시스템의 개발)

  • Lee, Sung Ho;Kim, Jung Soo;Lee, Jae Joon
    • Proceedings of the Korea Water Resources Association Conference
    • /
    • 2020.06a
    • /
    • pp.330-330
    • /
    • 2020
  • 국지성 호우의 증가로 인해 설계빈도 이상의 강우가 빈번하게 발생함에 따라 도시 지역의 내수침수피해가 빈번하게 발생하고 있다. 국지성 호우의 영향으로 특히 하천변 및 저지대의 유출량이 증가함에 따라 기존 하수관거의 통수능 부족으로 침수피해가 증가하고 있는 실정이다. 따라서 내수침수피해 저감을 위한 다양한 노력들이 이루어지고 있으나 도시지역의 경우 노후화 된 하수관거 교체를 위한 예산이 부족하며 도시개발이 완료됨에 따라 지하저류조 등의 저류지설을 설치하기 위한 부지 확보가 어려운 실정이다. 도시 지역에서 강우의 유출은 대부분 하수관거 시설에 의해 처리되므로 하수관거 통수능 부족 시 침수피해가 발생하게 된다. 따라서 기존 하수관거와 연계할 수 있으며 설치 부지와 큰 예산이 소요되지 않는 새로운 유형의 유출저감시설을 적용할 필요가 있다. 따라서 본 연구에서는 기존의 도로 배수시설에서 도로 표면 유출수의 수로역할을 하던 측구부를 도시지역의 상습침수 지역 및 개발지역 등 국지성 호우로 인한 내수침수 저감이 가능하며 기존 홍수방어시설에 비해 대규모의 부지와 예산이 소요되지 않는 새로운 우수저류시설을 개발하여 상습침수 지역에 개발된 저류시스템을 적용하여 측구 저류시스템의 용량에 따른 저류능력 및 내수침수 저감효과를 검토하고자 한다.

  • PDF

A Study on the Management System Improvement of Effluent Water Qualities for Public Sewage Treatment Facilities in Korea (우리나라 공공하수처리시설의 방류수 수질 관리체계 개선방안 고찰 - 미국, 일본, 유럽의 공공하수처리시설 방류수 수질 관리제도를 중심으로 -)

  • Jeong, Donghwan;Choi, Incheol;Cho, Yangseok;Chung, Hyenmi;Kwon, Ohsang;Yu, Soonju;Yeom, Icktae;Son, Daehee
    • Journal of Environmental Impact Assessment
    • /
    • v.23 no.4
    • /
    • pp.296-314
    • /
    • 2014
  • In recent years, Ministry of Environment (MOE) has been implementing a phased strengthening of the effluent standards for sewage treatment plants. In this regard, a comprehensive system should be developed to help check the appropriateness of such standards by specifying the grounds for standard-setting and investigating the current operation of sewage treatment plants clearly. It is necessary to establish a new standard-setting system for the effluent that is in a closer connection with the environmental criteria and rating systems. In the United States, the federal government provides guidelines on the least provisions and requirements for the Publicly Owned Treatment Works (POTWs). Local governments set the same or stricter guidelines that reflect the characteristics of each state. In Japan, the sewage treatment plants are subject to both the effluent standards and the discharge acceptable limits to pubic waters under the sewerage law. Specific requirements and limits are set in accordance with local government regulations. The European Union imposes sewage treatment plants with different provisions for effluent standards, depending on the sensitivity of public waters to eutrophication. The effluent standards for sewage treatment plants are classified by pollutant loads discharged to receiving waters. MOE also needs to introduce systems for setting new parameter standards on a POTW effluent by applying statistical means and treatment efficiencies or optimal treatment techniques, as seen in the cases of the US National Pollutant Discharge Elimination System (NPDES) or the EU Integrated Pollution Prevention and Control (IPPC).

The Impact of a Basic Environmental Facility Siting on Land Prices : A Case of Sewage Disposal Plant (환경기초시설의 입지가 지가에 미치는 영향 : 하수처리장을 사례로)

  • JUN, Byong-Woon
    • Journal of the Korean Association of Geographic Information Studies
    • /
    • v.20 no.3
    • /
    • pp.170-180
    • /
    • 2017
  • This research analyzed the effect of a basic environmental facility siting on the difference in land prices using a case study of Jisan sewage disposal plant in Daegu metropolitan city. To do so, two buffer zones were generated around Jisan sewage disposal plant to 400m at an interval of 200m as a setback distance and 822 officially announced individual land prices were acquired from Korea Ministry of Land, Infrastructure and Transport(MOLIT). Paired samples t-test was performed to compare the mean difference in land prices before and after Jisan sewage disposal plant siting. Results show that the mean land price from each buffer zone was slightly increased after the siting and the difference was statistically significant. Also, the results indicate that the mean land price within 200m was lower than that between 200m and 400m before the siting while there was not different in the mean land price for both buffer zones after the siting. Because Jisan sewage disposal plant did not have a stench and a larger capacity and its surrounding areas were blended by commercial and residential uses, a sewage disposal plant siting had little effect on the fall in land prices unlike previous studies. The findings from this research will provide new reference data for local government and local people with conflicting views on the siting of a basic environmental facility.

A study on Assessment Methodology for Best Treatment Technologies at Public Sewage Treatment Works in Korea (하수처리시설에서 최적처리기술 평가 방법론 고찰 - 미국과 유럽의 사례를 중심으로 -)

  • Jeong, Dong-Hwan;Cho, Yangseok;Choi, In-Cheol;Ahn, Kyunghee;Chung, Hyen-Mi;Kwon, Ohsang
    • Journal of Environmental Impact Assessment
    • /
    • v.24 no.4
    • /
    • pp.386-395
    • /
    • 2015
  • In order to assess sewage treatment technology necessary to achieve water quality criteria in the watershed and to ensure best treatment technology is applied in building and expanding PSTWs when establishing the Watershed Sewer System Maintenance Plan, it is necessary to develop assessment guidelines to determinate the best treatment technologies applicable to the public sewage treatment works(PSTWs). Sewage treatment technologies such as anaerobic-anoxic-aerobic treatment process are employed at PSTWs, and treatment efficiency varies due to many factors such as how the PSTWs are operated. Therefore, analyzing assessment guideline of best available technology(BAT) using currently in USA and EU, this study presents assessment parameters for the assessment guidelines to be used in determining the best treatment technologies applicable to PSTWs. We have a plan to implement pilot assessment in preparation for the final assessment guidelines based on the results of professionals survey and to determine weighted factors and assessment parameters using analytic hierarchy process (AHP).

The System Improvement of the Individual Sewage Treatment System (개인하수처리시설의 제도개선에 관한 연구)

  • Jang, Hyo-Ju;Lee, Jang-Hown;Kang, Seon-Hong
    • Journal of Korean Society of Water and Wastewater
    • /
    • v.24 no.1
    • /
    • pp.33-40
    • /
    • 2010
  • Individual sewage treatment system is classified into a sewage treatment system which treats all the domestic sewage and a water-purifier tank which treats only effluent flushing from the toilet. The number of registered manufacturers has increased rapidly since 2001. As a result, price competition has increased among the manufacturers and has caused the problems such as the inappropriate production of individual sewage treatment system, the unreasonable permit for building completion and the shortage of the professional technology of the community's public officials in charge. This study collected the problem cases that are related with existing individual sewage treatment system and operation. Efficient improvement plan for the stable supply, installation, maintenance of individual sewage treatment system were suggested.

A Study on the Feasibility of COBie to the Wastewater Treatment Plant (COBie 기반 하수처리시설 유지관리시스템 구축)

  • Choi, Jae-Ho;Um, Dong-Yong
    • KSCE Journal of Civil and Environmental Engineering Research
    • /
    • v.34 no.1
    • /
    • pp.273-283
    • /
    • 2014
  • With the introduction of COBie (Construction Operation Building Exchange) in BIM technology enabling an automatic transfer of design and construction information to operation and management (O&M) phase, the BIM centric O&M management system development process has been tested on the subject of architectural types of building. However, for now, there is a need to investigate the technical feasibility of COBie application to civil structures including industrial facilities. This study takes both "O&M Guideline for Public Wastewater Treatment Plant" and a real wastewater treatment plant into account for the purpose, in which the latter is intended to supplement the result of the first. The findings are three-folds: (1) COBie, as an asset modeling, is not sufficient enough to encompass commissioning data, (2) more relevant IFC development and family library build-up useful to modeling wastewater treatment plant is imperative, and (3) well-planned coordination and organization of COBie data-set in line with O&M practice will enhance the feasibility of the COBie in industrial facilities. The result could be used for a basis study for COBie application, particularly in industrial facilities.