Amid the growing number of high-rise complex buildings in Korea, efficient smoke prevention technology in a fire is required and as an alternative of a mechanical smoke control system in high-rise buildings, the use of a smoke control system using sandwich pressurization has been on the rise. In such a system, the appropriate pressure difference and the data for designing the air supply and exhaust flow rate are necessary to prevent the spread of smoke and offer a tenable evacuation environment. As part of such effort, this paper presents a field test process and result after testing a building where such a smoke control system using sandwich pressurization has been installed. A ventilation rate of 6 cycles per hour were applied to simulate the air exhaust flow rate on a fire floor and the air supply flow rate on the floors above and below the fire floor. As a result of the system operation, pressure difference of approximately 260 Pa between the 12th floor of a fire and the 13th floor was generated. The over pressure of the experiment has a serious effect on the evacuation or fire compartment so that it is necessary to examine the improvement.
The pressurized smoke control system in the vestibule is important for fire safety in buildings because it is concerned with egress time of people and the safety of fire fighters. The vestibule pressurization system can prevent smoke from entering the vestibule using differential pressure when fire doors are closed and using the egress velocity when fire doors are open. Air supplying units in the vestibule need to be arranged by taking account of the location of doors and the volume of the vestibule in order to assure the uniform air egress velocity through a fire door when it is open. In this study, computational fluid dynamics (CFD) simulations were conducted for the vestibule where multiple doors are installed and it was found that the reverse flow occurs when the damper position in vestibule is not appropriate.
Kim, Se-Jong;Han, Jung-Chul;Lee, Ju-Hee;Kwon, Young-Jin
Proceedings of the Korea Institute of Fire Science and Engineering Conference
/
2011.04a
/
pp.313-318
/
2011
도로터널은 반지하 공간으로서 환기에 많은 설비와 구조에 대한 연구가 진행되고 있으며 특히 제트팬의 경우 평상시에는 환기를 담당하고 있다. 또한 화재시에는 화재연기의 유독가스를 효과적으로 차단하는 제연역할을 함으로서 피난에 대한 중요한 역할을 담당한다. 이러한 제트팬의 특성을 정량적으로 유추하고 공학적인 QRA의 수행을 위한 기초적 연구로서 터널내부의 제트팬의 환기특성을 알아보기 위하여 모형실험체의 내부측정을 2/3까지한 전보에 이어 이번 연구에서는 터널내부전체를 측정하여 제트팬이 모형터널내에 미치는 영향을 CFD와 비교한 연구이다.
Proceedings of the Korea Institute of Fire Science and Engineering Conference
/
2011.04a
/
pp.378-383
/
2011
지능형 터널 배연시스템은 터널상부의 온도를 감지하는 온도감지부에서 들어오는 신호를 해독하여 화재위치 및 화재크기를 선정하고 제연설비의 운전방향 및 배연량을 조절함으로써 연기를 효율적으로 제어할 수 있는 시스템이다. 지능형 터널 배연시스템의 성능을 검증하기 위하여 실물터널의 크기를 1/60로 축소한 모델에서 두가지의 화원위치에 따라 실험을 수행하였다. 화재 발생 후 초기에는 온도가 상승하다가 제연팬이 작동하면 온도가 급격히 낮아진 후 일정하게 유지되면서 서서히 증가한다. 터널화재시 승객의 피난 장애를 주는 연기의 제어를 통해 터널의 안전성을 향상시킬 수 있는 것을 확인하였다.
Emergency lamp is installation usage on an emergency situation or firing. It's an offer at least of brightness. It's lighting to common source usually. It's transferred to reserve battery on power stoppage. This emergency lamp is lighted from solar cell system. The solar cell should be operated at the maximum power point. This paper proposes the new control method that half-bridge inverter using the solar cell can operate emergency lamp.
중위도 이북의 건물에서 고층건물의 혹한기 연돌효과는 건물의 여러 가지 기능에 큰 영향을 미치며, 승강기 승강로는 화재시 차압 때문에 연기의 주된 전파통로가 된다. 외피의 밀폐성능을 높여 건물 내부의 연도효과를 줄일 수 있으나, 외피의 밀폐기능은 비상시 피난을 위해 피난경로를 개방하는 순간 일시에 무력화된다. 또한 건물 외피의 밀폐성능이 우수할수록 연돌효과 그 자체로써 건물외피에 미치는 구조적 영향이 커진다. 고층부의 연돌효과는 외피를 밖으로 밀어내는 작용이므로 풍하측에서는 마이너스 풍압에 더하여 건물 외피에 부담을 증가시킨다. 그러므로 고층건물에 발생하는 혹한기 연돌효과의 영향을 정리하자면 다음과 같다. ${\bullet}$ 건물 외벽 및 창문에 미치는 구조적 영향 ${\bullet}$ 제연 시스템의 기능 저해 ${\bullet}$ 승강기 문 개폐 장애와 소음 등 설비 기능의 부정적 영향 ${\bullet}$ 공조기능 장애 ${\bullet}$ 화재시 승강기 승강로 등 수직 샤프트를 통한 연기 전파 혹한기 건물 안팎의 온도차가 40K일 때 높이 600m인 초고층 건물 최상층에 발생하는 연돌효과에 의한 차압은 풍속으로 환산할 때 32m/s에 달한다. 그러므로 초고층 건물 설계시에는 최상층의 풍하측에 설계상의 예상 최대풍속에다 이러한 환산풍속을 더한 고속 풍력이 창문을 밖으로 밀어내는 것으로 보아야 한다. 또한 공조 및 환기시스템에서는 이러한 차압을 고려하지 않으면 고층부에서 환기 성능이 무력화될 수 있다. 다음과 같은 방법들을 이용하여 고층건물의 연돌효과를 효과적으로 줄일 수 있다. 1) 계단실의 연돌효과 저감 방법 계단실에 발생하는 연돌효과에 의한 차압은 계단실에 상승기류를 발생시킨다. 이러한 차압과 상승기류는 계단실 상하부를 개방하면 자연적으로 평형을 이루게 되므로 별도의 제어가 필요 없게 된다. 또한 화재감지기와 연동하여 상하부 외벽의 개구부를 열어두게 되면 피난상황에 따라 문이 여닫힘으로써 발생하는 압력상태의 변화를 고려할 필요가 없게 된다. 2) 승강기 승강로의 연돌효과 승강로의 상하부에 대규모 개구를 두면 대규모의 외기가 도입되어 상승 유동 후 배출되므로 승강로 내부 온도 저하로 연돌효과가 저감되고, 승강로로 유입된 연기는 대규모의 외기에 희석되어 농도가 낮아지고 대부분 외부로 배출된다. 3) 샤프트 복합효과를 이용하는 방법 거실 평면적에 비해 승강기나 계단이 아주 많고 누설틈새 등 개구의 면적 합계가 크면 샤프트들이 서로 복합효과를 이루어 연돌효과에 의한 차압이 줄어든다. 연돌효과 제어용 샤프트를 하나 더 보조적으로 설치함으로써, 보조샤프트에 의해 발생하는 차압으로 거실을 가압 혹은 감압하여 문제가 되는 차압을 어느 정도 상쇄할 수 있다.
The purpose of this study is to suggest the development direction of fire safety through the analysis of previous researches in the field of fire fighting. To this end, 929 papers published in the Journal of Korean Institute of Fire Science and Engineering have been sorted by field of study and analyzed for frequency. Accordingly, it was confirmed that researches were conducted in the order of fire chemistry and physics, detection and extinguishing system, fire safety design and management, evacuation and human behavior. In contrast, very little research has been conducted on human behavior, fire safety education, or training. This result is discussed in the article, and suggestions for future research objectives are made.
This study analyzed recent cases of ship fires explosions and investigated their problems and coping plans. Through analysis on the statistical figures, it was found that our nation's situations of maritime accidents by kind during the period of 2009~2013 showed the ratios of ship accidents caused by fires explosions was the highest in 2012 with 7.58% (55 cases) followed by year 2009 with 3.39% (34 cases), year 2010 with 3.39% (25 cases), year 2011 with 6.03% (57 cases) and year 2013 with 6.74% (43 cases), which indicates a steady increase in the number of ship accidents. Majority of reasons for ship fires explosions were lack of safety awareness. Since those accidents happen on the sea, fires, once they happen, tend to get serious due to absence of on board & nearby fire extinguishing facilities, public fire service's uneasy access to them and great influences of natural factors such as wind and etc. Ship fires explosions are special cases unlike what happens to general edifices. So, their coping plans should focus on preventive measures since the damages those cases bring about can be detrimental. For this reason, it's necessary to research precise evacuation plans, develop ship structure & materials reinforcing fire resistance to secure more time for evacuation and enhance people's safety awareness by implementing thorough safety training.
The Journal of the Convergence on Culture Technology
/
v.7
no.4
/
pp.765-778
/
2021
The purpose of this study is to prevent fire accidents in advance by deriving prior knowledge among groups about temporary fire-fighting facilities of workers at construction sites and devising appropriate improvement measures. The findings are as follows.First, in the case of fire extinguishers, statistical attention was paid to the contractor, supervisor, partner worker and fire extinguisher manager between designations. 87% of fire managers and 70% of facility supervisors said fire extinguisher management managers needed to be designated for each type of construction, which requires designation of fire extinguisher management managers, frequently checking and relocating. Second, in the case of simple fire extinguishing facilities, statistical attention was paid to the application of penalties for unauthorized use of fire extinguishing facilities with construction companies, supervisors, and business partners.Third, in the case of emergency alarm measures, statistical attention was paid to the application of emergency alarm sound to temporary broadcasting facilities with construction works, supervisors, and business partners.Fourth, in the case of induction, statistical attention was paid to the application of connection between construction works, supervisors, and partner workers, such as passage guidance, emergency lighting, etc.It was found that 65% of construction workers and 55% of electrical workers had different applications such as aisle guidance and emergency lighting for each type of business partner. In order to resolve blind spots such as evacuation zone guidance due to the structure of the building, it is necessary to easily distinguish the direction of the entrance door from a long distance by applying it in conjunction with passage guidance lights and emergency lighting.
Journal of Korean Tunnelling and Underground Space Association
/
v.20
no.2
/
pp.527-539
/
2018
The subway used by many passengers is required to maintain a safe and comfortable environment and PSD (Platform Screen Door) must be installed in the platform after reinforcing the standard in 2003. In the previous research, in case of subway fire to control it, it is necessary to design the optimal ventilation and smoke exhaust system according to equipment capacity of the smoke exhaust system. Therefore, in this study, based on the results of previous research, three-dimensional numerical analysis was performed for the CO gas and smoke flow by the subway ventilation system in case of platform fire. As a result of this study, it was found that in case of emergency, if only the upper-level smoke exhaust system is activated, the risk of evacuation is high due to CO gas (653.8 ppm) and smoke concentration ($768.4mg/m^3$). And when all the smoke exhaust systems are activated and only the fire side PSD is opened, CO gas (36.0 ppm) and smoke concentration ($26.2mg/m^3$) are detected and the propagation range of smoke flow was reduced. When all the smoke exhaust systems are activated and only the fire side PSD is closed, it was analyzed as the most effective ventilation mode in the evacuation environment due to the absence of smoke-recirculation.
본 웹사이트에 게시된 이메일 주소가 전자우편 수집 프로그램이나
그 밖의 기술적 장치를 이용하여 무단으로 수집되는 것을 거부하며,
이를 위반시 정보통신망법에 의해 형사 처벌됨을 유념하시기 바랍니다.
[게시일 2004년 10월 1일]
이용약관
제 1 장 총칙
제 1 조 (목적)
이 이용약관은 KoreaScience 홈페이지(이하 “당 사이트”)에서 제공하는 인터넷 서비스(이하 '서비스')의 가입조건 및 이용에 관한 제반 사항과 기타 필요한 사항을 구체적으로 규정함을 목적으로 합니다.
제 2 조 (용어의 정의)
① "이용자"라 함은 당 사이트에 접속하여 이 약관에 따라 당 사이트가 제공하는 서비스를 받는 회원 및 비회원을
말합니다.
② "회원"이라 함은 서비스를 이용하기 위하여 당 사이트에 개인정보를 제공하여 아이디(ID)와 비밀번호를 부여
받은 자를 말합니다.
③ "회원 아이디(ID)"라 함은 회원의 식별 및 서비스 이용을 위하여 자신이 선정한 문자 및 숫자의 조합을
말합니다.
④ "비밀번호(패스워드)"라 함은 회원이 자신의 비밀보호를 위하여 선정한 문자 및 숫자의 조합을 말합니다.
제 3 조 (이용약관의 효력 및 변경)
① 이 약관은 당 사이트에 게시하거나 기타의 방법으로 회원에게 공지함으로써 효력이 발생합니다.
② 당 사이트는 이 약관을 개정할 경우에 적용일자 및 개정사유를 명시하여 현행 약관과 함께 당 사이트의
초기화면에 그 적용일자 7일 이전부터 적용일자 전일까지 공지합니다. 다만, 회원에게 불리하게 약관내용을
변경하는 경우에는 최소한 30일 이상의 사전 유예기간을 두고 공지합니다. 이 경우 당 사이트는 개정 전
내용과 개정 후 내용을 명확하게 비교하여 이용자가 알기 쉽도록 표시합니다.
제 4 조(약관 외 준칙)
① 이 약관은 당 사이트가 제공하는 서비스에 관한 이용안내와 함께 적용됩니다.
② 이 약관에 명시되지 아니한 사항은 관계법령의 규정이 적용됩니다.
제 2 장 이용계약의 체결
제 5 조 (이용계약의 성립 등)
① 이용계약은 이용고객이 당 사이트가 정한 약관에 「동의합니다」를 선택하고, 당 사이트가 정한
온라인신청양식을 작성하여 서비스 이용을 신청한 후, 당 사이트가 이를 승낙함으로써 성립합니다.
② 제1항의 승낙은 당 사이트가 제공하는 과학기술정보검색, 맞춤정보, 서지정보 등 다른 서비스의 이용승낙을
포함합니다.
제 6 조 (회원가입)
서비스를 이용하고자 하는 고객은 당 사이트에서 정한 회원가입양식에 개인정보를 기재하여 가입을 하여야 합니다.
제 7 조 (개인정보의 보호 및 사용)
당 사이트는 관계법령이 정하는 바에 따라 회원 등록정보를 포함한 회원의 개인정보를 보호하기 위해 노력합니다. 회원 개인정보의 보호 및 사용에 대해서는 관련법령 및 당 사이트의 개인정보 보호정책이 적용됩니다.
제 8 조 (이용 신청의 승낙과 제한)
① 당 사이트는 제6조의 규정에 의한 이용신청고객에 대하여 서비스 이용을 승낙합니다.
② 당 사이트는 아래사항에 해당하는 경우에 대해서 승낙하지 아니 합니다.
- 이용계약 신청서의 내용을 허위로 기재한 경우
- 기타 규정한 제반사항을 위반하며 신청하는 경우
제 9 조 (회원 ID 부여 및 변경 등)
① 당 사이트는 이용고객에 대하여 약관에 정하는 바에 따라 자신이 선정한 회원 ID를 부여합니다.
② 회원 ID는 원칙적으로 변경이 불가하며 부득이한 사유로 인하여 변경 하고자 하는 경우에는 해당 ID를
해지하고 재가입해야 합니다.
③ 기타 회원 개인정보 관리 및 변경 등에 관한 사항은 서비스별 안내에 정하는 바에 의합니다.
제 3 장 계약 당사자의 의무
제 10 조 (KISTI의 의무)
① 당 사이트는 이용고객이 희망한 서비스 제공 개시일에 특별한 사정이 없는 한 서비스를 이용할 수 있도록
하여야 합니다.
② 당 사이트는 개인정보 보호를 위해 보안시스템을 구축하며 개인정보 보호정책을 공시하고 준수합니다.
③ 당 사이트는 회원으로부터 제기되는 의견이나 불만이 정당하다고 객관적으로 인정될 경우에는 적절한 절차를
거쳐 즉시 처리하여야 합니다. 다만, 즉시 처리가 곤란한 경우는 회원에게 그 사유와 처리일정을 통보하여야
합니다.
제 11 조 (회원의 의무)
① 이용자는 회원가입 신청 또는 회원정보 변경 시 실명으로 모든 사항을 사실에 근거하여 작성하여야 하며,
허위 또는 타인의 정보를 등록할 경우 일체의 권리를 주장할 수 없습니다.
② 당 사이트가 관계법령 및 개인정보 보호정책에 의거하여 그 책임을 지는 경우를 제외하고 회원에게 부여된
ID의 비밀번호 관리소홀, 부정사용에 의하여 발생하는 모든 결과에 대한 책임은 회원에게 있습니다.
③ 회원은 당 사이트 및 제 3자의 지적 재산권을 침해해서는 안 됩니다.
제 4 장 서비스의 이용
제 12 조 (서비스 이용 시간)
① 서비스 이용은 당 사이트의 업무상 또는 기술상 특별한 지장이 없는 한 연중무휴, 1일 24시간 운영을
원칙으로 합니다. 단, 당 사이트는 시스템 정기점검, 증설 및 교체를 위해 당 사이트가 정한 날이나 시간에
서비스를 일시 중단할 수 있으며, 예정되어 있는 작업으로 인한 서비스 일시중단은 당 사이트 홈페이지를
통해 사전에 공지합니다.
② 당 사이트는 서비스를 특정범위로 분할하여 각 범위별로 이용가능시간을 별도로 지정할 수 있습니다. 다만
이 경우 그 내용을 공지합니다.
제 13 조 (홈페이지 저작권)
① NDSL에서 제공하는 모든 저작물의 저작권은 원저작자에게 있으며, KISTI는 복제/배포/전송권을 확보하고
있습니다.
② NDSL에서 제공하는 콘텐츠를 상업적 및 기타 영리목적으로 복제/배포/전송할 경우 사전에 KISTI의 허락을
받아야 합니다.
③ NDSL에서 제공하는 콘텐츠를 보도, 비평, 교육, 연구 등을 위하여 정당한 범위 안에서 공정한 관행에
합치되게 인용할 수 있습니다.
④ NDSL에서 제공하는 콘텐츠를 무단 복제, 전송, 배포 기타 저작권법에 위반되는 방법으로 이용할 경우
저작권법 제136조에 따라 5년 이하의 징역 또는 5천만 원 이하의 벌금에 처해질 수 있습니다.
제 14 조 (유료서비스)
① 당 사이트 및 협력기관이 정한 유료서비스(원문복사 등)는 별도로 정해진 바에 따르며, 변경사항은 시행 전에
당 사이트 홈페이지를 통하여 회원에게 공지합니다.
② 유료서비스를 이용하려는 회원은 정해진 요금체계에 따라 요금을 납부해야 합니다.
제 5 장 계약 해지 및 이용 제한
제 15 조 (계약 해지)
회원이 이용계약을 해지하고자 하는 때에는 [가입해지] 메뉴를 이용해 직접 해지해야 합니다.
제 16 조 (서비스 이용제한)
① 당 사이트는 회원이 서비스 이용내용에 있어서 본 약관 제 11조 내용을 위반하거나, 다음 각 호에 해당하는
경우 서비스 이용을 제한할 수 있습니다.
- 2년 이상 서비스를 이용한 적이 없는 경우
- 기타 정상적인 서비스 운영에 방해가 될 경우
② 상기 이용제한 규정에 따라 서비스를 이용하는 회원에게 서비스 이용에 대하여 별도 공지 없이 서비스 이용의
일시정지, 이용계약 해지 할 수 있습니다.
제 17 조 (전자우편주소 수집 금지)
회원은 전자우편주소 추출기 등을 이용하여 전자우편주소를 수집 또는 제3자에게 제공할 수 없습니다.
제 6 장 손해배상 및 기타사항
제 18 조 (손해배상)
당 사이트는 무료로 제공되는 서비스와 관련하여 회원에게 어떠한 손해가 발생하더라도 당 사이트가 고의 또는 과실로 인한 손해발생을 제외하고는 이에 대하여 책임을 부담하지 아니합니다.
제 19 조 (관할 법원)
서비스 이용으로 발생한 분쟁에 대해 소송이 제기되는 경우 민사 소송법상의 관할 법원에 제기합니다.
[부 칙]
1. (시행일) 이 약관은 2016년 9월 5일부터 적용되며, 종전 약관은 본 약관으로 대체되며, 개정된 약관의 적용일 이전 가입자도 개정된 약관의 적용을 받습니다.