• Title/Summary/Keyword: 피난설비

Search Result 151, Processing Time 0.021 seconds

Case Study of a Field Test for a Smoke Control System Using Sandwich Pressurization (샌드위치 가압을 이용하는 연기제어 시스템의 현장실험 사례 연구)

  • Kim, Jung-Yup;Ahn, Chan-Sol
    • Fire Science and Engineering
    • /
    • v.30 no.5
    • /
    • pp.87-92
    • /
    • 2016
  • Amid the growing number of high-rise complex buildings in Korea, efficient smoke prevention technology in a fire is required and as an alternative of a mechanical smoke control system in high-rise buildings, the use of a smoke control system using sandwich pressurization has been on the rise. In such a system, the appropriate pressure difference and the data for designing the air supply and exhaust flow rate are necessary to prevent the spread of smoke and offer a tenable evacuation environment. As part of such effort, this paper presents a field test process and result after testing a building where such a smoke control system using sandwich pressurization has been installed. A ventilation rate of 6 cycles per hour were applied to simulate the air exhaust flow rate on a fire floor and the air supply flow rate on the floors above and below the fire floor. As a result of the system operation, pressure difference of approximately 260 Pa between the 12th floor of a fire and the 13th floor was generated. The over pressure of the experiment has a serious effect on the evacuation or fire compartment so that it is necessary to examine the improvement.

Numerical Study on Air Egress Velocity in Vestibule Pressurization System : Characteristics of Air Flow in the Vestibule with Multiple Fire Doors in an Apartment Building (부속실 가압 시스템의 방연풍속에 관한 수치해석적 연구: 공동주택 부속실내에 다수 출입문의 존재시 기류특성)

  • Seo, Chanwon;Shin, Weon Gyu
    • Fire Science and Engineering
    • /
    • v.28 no.5
    • /
    • pp.30-36
    • /
    • 2014
  • The pressurized smoke control system in the vestibule is important for fire safety in buildings because it is concerned with egress time of people and the safety of fire fighters. The vestibule pressurization system can prevent smoke from entering the vestibule using differential pressure when fire doors are closed and using the egress velocity when fire doors are open. Air supplying units in the vestibule need to be arranged by taking account of the location of doors and the volume of the vestibule in order to assure the uniform air egress velocity through a fire door when it is open. In this study, computational fluid dynamics (CFD) simulations were conducted for the vestibule where multiple doors are installed and it was found that the reverse flow occurs when the damper position in vestibule is not appropriate.

A Study on the Ventilation Performance for Fan flow effect of Model Tunnel(II) (모형도로터널의 환기성능에 미치는 FAN유량에 관한 연구(II))

  • Kim, Se-Jong;Han, Jung-Chul;Lee, Ju-Hee;Kwon, Young-Jin
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.04a
    • /
    • pp.313-318
    • /
    • 2011
  • 도로터널은 반지하 공간으로서 환기에 많은 설비와 구조에 대한 연구가 진행되고 있으며 특히 제트팬의 경우 평상시에는 환기를 담당하고 있다. 또한 화재시에는 화재연기의 유독가스를 효과적으로 차단하는 제연역할을 함으로서 피난에 대한 중요한 역할을 담당한다. 이러한 제트팬의 특성을 정량적으로 유추하고 공학적인 QRA의 수행을 위한 기초적 연구로서 터널내부의 제트팬의 환기특성을 알아보기 위하여 모형실험체의 내부측정을 2/3까지한 전보에 이어 이번 연구에서는 터널내부전체를 측정하여 제트팬이 모형터널내에 미치는 영향을 CFD와 비교한 연구이다.

  • PDF

Reduced-Scale Tests of A Intelligent Tunnel Smoke-Control System (지능형 터널 배연시스템 축소모형 실험)

  • Son, Yun-Suk;Park, Won-Hee;Kim, Chi-Hun;Jung, Woo-Sung
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.04a
    • /
    • pp.378-383
    • /
    • 2011
  • 지능형 터널 배연시스템은 터널상부의 온도를 감지하는 온도감지부에서 들어오는 신호를 해독하여 화재위치 및 화재크기를 선정하고 제연설비의 운전방향 및 배연량을 조절함으로써 연기를 효율적으로 제어할 수 있는 시스템이다. 지능형 터널 배연시스템의 성능을 검증하기 위하여 실물터널의 크기를 1/60로 축소한 모델에서 두가지의 화원위치에 따라 실험을 수행하였다. 화재 발생 후 초기에는 온도가 상승하다가 제연팬이 작동하면 온도가 급격히 낮아진 후 일정하게 유지되면서 서서히 증가한다. 터널화재시 승객의 피난 장애를 주는 연기의 제어를 통해 터널의 안전성을 향상시킬 수 있는 것을 확인하였다.

  • PDF

A Study on Lighting Emergency Lamp using Photovoltaic Generation System (태양광발전시스템을 이용한 유도등용 헝광램프의 점등에 관한 연구)

  • 이상집;성낙규;이승환;오봉환;백동현;이훈구;한경희
    • Fire Science and Engineering
    • /
    • v.14 no.1
    • /
    • pp.22-26
    • /
    • 2000
  • Emergency lamp is installation usage on an emergency situation or firing. It's an offer at least of brightness. It's lighting to common source usually. It's transferred to reserve battery on power stoppage. This emergency lamp is lighted from solar cell system. The solar cell should be operated at the maximum power point. This paper proposes the new control method that half-bridge inverter using the solar cell can operate emergency lamp.

  • PDF

A Study on Reducing Method for Stack Effect in High-rise Building (고층 건축물 연돌효과 저감 방법에 대한 연구)

  • Kim, Jin Soo
    • 한국방재학회:학술대회논문집
    • /
    • 2011.02a
    • /
    • pp.66-66
    • /
    • 2011
  • 중위도 이북의 건물에서 고층건물의 혹한기 연돌효과는 건물의 여러 가지 기능에 큰 영향을 미치며, 승강기 승강로는 화재시 차압 때문에 연기의 주된 전파통로가 된다. 외피의 밀폐성능을 높여 건물 내부의 연도효과를 줄일 수 있으나, 외피의 밀폐기능은 비상시 피난을 위해 피난경로를 개방하는 순간 일시에 무력화된다. 또한 건물 외피의 밀폐성능이 우수할수록 연돌효과 그 자체로써 건물외피에 미치는 구조적 영향이 커진다. 고층부의 연돌효과는 외피를 밖으로 밀어내는 작용이므로 풍하측에서는 마이너스 풍압에 더하여 건물 외피에 부담을 증가시킨다. 그러므로 고층건물에 발생하는 혹한기 연돌효과의 영향을 정리하자면 다음과 같다. ${\bullet}$ 건물 외벽 및 창문에 미치는 구조적 영향 ${\bullet}$ 제연 시스템의 기능 저해 ${\bullet}$ 승강기 문 개폐 장애와 소음 등 설비 기능의 부정적 영향 ${\bullet}$ 공조기능 장애 ${\bullet}$ 화재시 승강기 승강로 등 수직 샤프트를 통한 연기 전파 혹한기 건물 안팎의 온도차가 40K일 때 높이 600m인 초고층 건물 최상층에 발생하는 연돌효과에 의한 차압은 풍속으로 환산할 때 32m/s에 달한다. 그러므로 초고층 건물 설계시에는 최상층의 풍하측에 설계상의 예상 최대풍속에다 이러한 환산풍속을 더한 고속 풍력이 창문을 밖으로 밀어내는 것으로 보아야 한다. 또한 공조 및 환기시스템에서는 이러한 차압을 고려하지 않으면 고층부에서 환기 성능이 무력화될 수 있다. 다음과 같은 방법들을 이용하여 고층건물의 연돌효과를 효과적으로 줄일 수 있다. 1) 계단실의 연돌효과 저감 방법 계단실에 발생하는 연돌효과에 의한 차압은 계단실에 상승기류를 발생시킨다. 이러한 차압과 상승기류는 계단실 상하부를 개방하면 자연적으로 평형을 이루게 되므로 별도의 제어가 필요 없게 된다. 또한 화재감지기와 연동하여 상하부 외벽의 개구부를 열어두게 되면 피난상황에 따라 문이 여닫힘으로써 발생하는 압력상태의 변화를 고려할 필요가 없게 된다. 2) 승강기 승강로의 연돌효과 승강로의 상하부에 대규모 개구를 두면 대규모의 외기가 도입되어 상승 유동 후 배출되므로 승강로 내부 온도 저하로 연돌효과가 저감되고, 승강로로 유입된 연기는 대규모의 외기에 희석되어 농도가 낮아지고 대부분 외부로 배출된다. 3) 샤프트 복합효과를 이용하는 방법 거실 평면적에 비해 승강기나 계단이 아주 많고 누설틈새 등 개구의 면적 합계가 크면 샤프트들이 서로 복합효과를 이루어 연돌효과에 의한 차압이 줄어든다. 연돌효과 제어용 샤프트를 하나 더 보조적으로 설치함으로써, 보조샤프트에 의해 발생하는 차압으로 거실을 가압 혹은 감압하여 문제가 되는 차압을 어느 정도 상쇄할 수 있다.

  • PDF

Direction of Fire Safety Development through Analysis of Previous Firefighting-Related Research (소방분야 선행연구 분석을 통한 소방안전 발전방향)

  • Jeong, Mu Heon;Lee, Sun Jai;Park, In-Seon
    • Fire Science and Engineering
    • /
    • v.33 no.5
    • /
    • pp.103-108
    • /
    • 2019
  • The purpose of this study is to suggest the development direction of fire safety through the analysis of previous researches in the field of fire fighting. To this end, 929 papers published in the Journal of Korean Institute of Fire Science and Engineering have been sorted by field of study and analyzed for frequency. Accordingly, it was confirmed that researches were conducted in the order of fire chemistry and physics, detection and extinguishing system, fire safety design and management, evacuation and human behavior. In contrast, very little research has been conducted on human behavior, fire safety education, or training. This result is discussed in the article, and suggestions for future research objectives are made.

Study on the Ship Fire Analysis According to Explosion Hazard (폭발의 위험성에 의한 선박화재의 사고사례 분석)

  • You, Jisun;Chung, Yeong-Jin
    • Fire Science and Engineering
    • /
    • v.29 no.1
    • /
    • pp.80-86
    • /
    • 2015
  • This study analyzed recent cases of ship fires explosions and investigated their problems and coping plans. Through analysis on the statistical figures, it was found that our nation's situations of maritime accidents by kind during the period of 2009~2013 showed the ratios of ship accidents caused by fires explosions was the highest in 2012 with 7.58% (55 cases) followed by year 2009 with 3.39% (34 cases), year 2010 with 3.39% (25 cases), year 2011 with 6.03% (57 cases) and year 2013 with 6.74% (43 cases), which indicates a steady increase in the number of ship accidents. Majority of reasons for ship fires explosions were lack of safety awareness. Since those accidents happen on the sea, fires, once they happen, tend to get serious due to absence of on board & nearby fire extinguishing facilities, public fire service's uneasy access to them and great influences of natural factors such as wind and etc. Ship fires explosions are special cases unlike what happens to general edifices. So, their coping plans should focus on preventive measures since the damages those cases bring about can be detrimental. For this reason, it's necessary to research precise evacuation plans, develop ship structure & materials reinforcing fire resistance to secure more time for evacuation and enhance people's safety awareness by implementing thorough safety training.

Analysis of Ambivalence Differences among Groups for Temporary Firefighting Facilities of Workers at Construction Sites (공사현장 근로자의 임시소방시설에 대한 집단 간 Ambivalence 차이분석)

  • Moon, Pil-Jae;Kong, Ha-Sung
    • The Journal of the Convergence on Culture Technology
    • /
    • v.7 no.4
    • /
    • pp.765-778
    • /
    • 2021
  • The purpose of this study is to prevent fire accidents in advance by deriving prior knowledge among groups about temporary fire-fighting facilities of workers at construction sites and devising appropriate improvement measures. The findings are as follows.First, in the case of fire extinguishers, statistical attention was paid to the contractor, supervisor, partner worker and fire extinguisher manager between designations. 87% of fire managers and 70% of facility supervisors said fire extinguisher management managers needed to be designated for each type of construction, which requires designation of fire extinguisher management managers, frequently checking and relocating. Second, in the case of simple fire extinguishing facilities, statistical attention was paid to the application of penalties for unauthorized use of fire extinguishing facilities with construction companies, supervisors, and business partners.Third, in the case of emergency alarm measures, statistical attention was paid to the application of emergency alarm sound to temporary broadcasting facilities with construction works, supervisors, and business partners.Fourth, in the case of induction, statistical attention was paid to the application of connection between construction works, supervisors, and partner workers, such as passage guidance, emergency lighting, etc.It was found that 65% of construction workers and 55% of electrical workers had different applications such as aisle guidance and emergency lighting for each type of business partner. In order to resolve blind spots such as evacuation zone guidance due to the structure of the building, it is necessary to easily distinguish the direction of the entrance door from a long distance by applying it in conjunction with passage guidance lights and emergency lighting.

A study on the optimal ventilation and smoke exhaust systems in case of fire in subway stations installed with PSD (PSD가 설치된 지하철 역사 내 화재 시 최적 배연시스템 연구)

  • Kim, Hyo-Gyu;Yoo, Ji-Oh;Kim, Doo-Young
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.20 no.2
    • /
    • pp.527-539
    • /
    • 2018
  • The subway used by many passengers is required to maintain a safe and comfortable environment and PSD (Platform Screen Door) must be installed in the platform after reinforcing the standard in 2003. In the previous research, in case of subway fire to control it, it is necessary to design the optimal ventilation and smoke exhaust system according to equipment capacity of the smoke exhaust system. Therefore, in this study, based on the results of previous research, three-dimensional numerical analysis was performed for the CO gas and smoke flow by the subway ventilation system in case of platform fire. As a result of this study, it was found that in case of emergency, if only the upper-level smoke exhaust system is activated, the risk of evacuation is high due to CO gas (653.8 ppm) and smoke concentration ($768.4mg/m^3$). And when all the smoke exhaust systems are activated and only the fire side PSD is opened, CO gas (36.0 ppm) and smoke concentration ($26.2mg/m^3$) are detected and the propagation range of smoke flow was reduced. When all the smoke exhaust systems are activated and only the fire side PSD is closed, it was analyzed as the most effective ventilation mode in the evacuation environment due to the absence of smoke-recirculation.