Experimental Investigation of Variations in Inclination Angle of Natural Convective Heat Sink with Plate Fins (플레이트-휜을 가지는 자연대류 히트싱트의 경사각 변화에 대한 실험적 연구)

  • Do, Kyu-Hyung;Kim, Tae-Hoon;Han, Yong-Shik;Choi, Byung-Il;Kim, Myung-Bae
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.36 no.6
    • /
    • pp.571-578
    • /
    • 2012
  • In this paper, an experimental investigation is performed to estimate the thermal performance of a natural convective heat sink with plate fins subject to the uniform wall temperature condition. Extensive experiments are performed with various input powers, fin spacings, and heights of the natural convective heat sinks with plate fins. In particular, the effect of the inclination angle on the thermal performance of the heat sink is studied. In order to validate the experimental data, the experimental results are compared with results from previous studies. Based on the experimental results, the appropriate ranges of the previous correlations between the input power, the fin spacing, the fin height, and the inclination angle for the natural convective heat sink with plate fins are evaluated.

The Study on Absorption Performance of a Plate-Fin Type Absorber (플레이트-휜형 흡수기의 흡수성능에 대한 연구)

  • 강인석;김남진;김종보
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.7
    • /
    • pp.557-563
    • /
    • 2001
  • Small capacity gas absorption systems for cooling and heating have been favorably considered to reduce the seasonal imbalance of electrical loads and LNG consumption recently. A multifunctional plate-fin heat exchanger was adopted as an absorber and the performance was tested and analyzed to reduce the size and weight of the absorption heat pump. The test was performed using breadboard type ammonia absorption machine. The performance was compared with the plate type absorber and there was little difference in heat and mass transfer characteristics. The heat and mass transfer performance was a function of poor solution and vapor flow rates and the mass transfer was dependent on vapor flow rate more than heat transfer.

  • PDF

A Study of Performance of Roll-plate type fin-tube Heat Exchanger for the Refrigerator (냉장고용 롤-플레이트형 휜-관 열교환기의 성능에 관한 연구)

  • Ahn, Sung-Jun;Kim, Jong-Su;Kwon, Oh-Boong;Park, Yong-Jong;Ha, Young-Ju;Choi, Sang-Jo
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.2292-2297
    • /
    • 2008
  • Recently, a study on condensers for refrigerators has focused on new model which will cost less and will be more efficient. Some widely used condensers for domestic refrigerators are wire-and-tube type condenser, hot-wall type condenser, and spiral type condenser. Some companies which use the spiral type condenser at the moment try to develop a new type condenser which will cost less and will be as efficient as the spiral type. The new type condenser consists of a steel tube, steel plates and louver fins attached to the tube. The tube and the plate are bent into a single-passage serpentine shape.

  • PDF

Basic Experiment on Frost of Plate Fin Coil Evaporator (플레이트 휜 코일형 증발기의 착상에 관한 기초 실험)

  • 백승문;김창영;한인근;김재돌;윤정인
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 1999.11a
    • /
    • pp.211-216
    • /
    • 1999
  • One of the problems in a refrigerator operation is the frost formation on a cold surface of the evaporator. The frost layer is formed by the sublimation of water vapor when the surface temperature is below the freezing point. This frost layer is usually porous and formed on the cold surface of the evaporator. The frost layer on the surface of a evaporator will make side effect such as thermal resistance. However, these important factors have not been used in determining the defrosting period. In this report, a prediction taking into account the change of the fin efficiency due to the growth of the frost layer.

  • PDF

Development of a Cooling System for a Concentrating Photovoltaic Module (고집광 태양전지 모듈의 냉각시스템 개발)

  • Kim, Tae-Hoon;Do, Kyu-Hyung;Choi, Byung-Il;Han, Yong-Shik;Kim, Myung-Bae
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.35 no.6
    • /
    • pp.551-560
    • /
    • 2011
  • In this paper, a cooling system that includes a heat spreader and a natural convective heat sink is proposed for the cooling of a concentrating photovoltaic (CPV) module. The heat spreader and the natural convective heat sink are designed on the basis of previous analytical investigations. In order to evaluate the proposed cooling system, we conducted experimental investigations varying the heat rate and the inclined angle of the cooling system. From the experimental results, it is found that the proposed cooling system satisfies the design constraints for good operation of the CPV module. Finally, a correlation is suggested for estimating the effects of the heat rate and the inclined angle on the thermal performance of the natural convective heat sink is suggested.