• Title/Summary/Keyword: 풀비등 열전달

Search Result 50, Processing Time 0.023 seconds

A Study on the Performance of Heat Transfer of Low Fin Tubes Used in Cooling of the Cutting Oil of the Machine Tool (공작기계 절삭유 냉각용 낮은 핀관의 열전달 성능에 관한 연구)

  • 조동현
    • Proceedings of the Korean Society of Machine Tool Engineers Conference
    • /
    • 1998.10a
    • /
    • pp.125-133
    • /
    • 1998
  • Nine tubes with trapezoidal integral-fins having fin densities from 748 to 1654fpm and 10,30 grooves and finned tubes with caves of 0.55 and 0.64mm height respectively are tested. A plain tube having same diameter as the finned tubes is also tested for comparison. In case of condensation CFC-11 condensates at saturation state of 32$^{\circ}C$ on the outside surface cooled by inside cooling water flows. And in case of boiling the refrigerant evaporates at a saturation state of 1bar on the outside tube surface and heat is supplied by hot water which circulates inside of the tube. The tube having fin density of 1299fpm and 30grooves has the best condensation overall heat transfer coefficient. However, as far as boiling heat transfer coefficient concerns, fin tubes with cave show higher value than low fin tube having fin density of 1299fpm and 30 grooves.

  • PDF

Development of Pool Boiling Heat Transfer Correlation for Hydrocarbon Refrigerants (탄화수소계 냉매의 풀비등 열전달 상관식 개발)

  • Park Ki-Jung;Baek In-Cheol;Jung Dong-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.3
    • /
    • pp.247-253
    • /
    • 2006
  • In this work, pool boiling heat transfer coefficients (HTCs) of hydrocarbon refrigerants are measured from a horizontal smooth tube of 19.0 mm outside diameter. Tested pure refrigerants are Propylene, Propane, Isobutane, Butane and Dimethylether (DME). The pool temperature was maintained at saturation temperature of $7^{\circ}C$ and heat flux was varied from $10kW/m^2$ to $80kW/m^2$ with an interval of $10kW/m^2$. Wall temperatures were measured directly by thermocouple hole of 0.5 mm out-diameter, 152 mm long and inserting ungrounded sheathed thermocouples from the side of the tube. Tested results show that HTCs of Propane, Propylene are 2.5%, 10.4% higher than those of R22 while those of Butane and Isobutane are 55.2%, 44.3% lower than those of R22 respectively. For pure refrigerants, new correlation can be applied to all of CFCs, HCFCS, HFCs, as well as hydrocarbons was developed. The mean deviation was 4.6%.

The characteristics of heat transfer coefficient for falling-film evaporation on a horizontal tube with aqueous LiBr solution (LiBr 수용액의 수평관 유하액막 증발에 있어서의 열전달계수 특성)

  • Ji, Yong-Hae
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.21 no.2
    • /
    • pp.294-302
    • /
    • 1997
  • Falling-film evaporation experiments for aqueous solution of lithium bromide (LiBr) were performed on a horizontal smooth 19.05-mm-dia copper tube. Average heat transfer coefficients were obtained with varied film Reynolds numbers, system pressures, LiBr concentrations and degrees of wall superheat. Heat transfer coefficients increase with increasing system pressure and decreasing concentration. For degrees of wall superheat, the heat transfer coefficient did not't show the distinct trend. For this experimental ranges, heat transfer coefficients showed maximum values at an optimal film Reynolds number. The results of this work were compared with pool boiling data reported previously, and it was shown that the heat transfer performance is superior to the pool boiling.

An Experimental Study on the Effect of Low Fin Tube Geometry on Pool Boiling of a LiBr Solution (낮은 핀관의 형상이 LiBr 수용액의 풀 비등에 미치는 영향에 대한 실험적 연구)

  • Kim, Nae-Hyun
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.39 no.7
    • /
    • pp.591-598
    • /
    • 2015
  • Pool boiling heat transfer coefficients of a LiBr solution were obtained for seven low fin tubes having different fin pitch and fin height. The test range covered saturation pressure from 7.38kPa to 101.3kPa, heat flux from $20kW/m^2$ to $40 kW/m^2$ and LiBr concentration from 0% to 50%. The optimum fin geometry for the present experimental range turned out to be 26 fpi with 0.18 mm fin height.The advantage of added heat transfer area and the disadvantage of slower bubble growth and departure appear to have yielded an optimum fin pitch. The heat transfer coefficient decreased as saturation pressure decreased and Libr concentration increased. The reason may be attributed to the low saturation pressure, which increased the bubble departure diameter and decreased the bubble departure frequency. As the LiBr concenreation increased, the saturation temperature increased and the mass diffusion rate decreased, which resulted in a reduced heat transfer coefficient. The heat transfer coefficients of the low fin tube were greater than those of the smooth tube. Correlations were developed based on the present data.

Effect of Liquid Subcooling on Pool Boiling Heat Transfer in Vertical Annuli with Closed Bottoms (액체과냉도가 하부폐쇄 수직환상공간 내부의 풀비등 열전달에 미치는 영향)

  • Kang Myeong-Gie
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.29 no.2 s.233
    • /
    • pp.239-246
    • /
    • 2005
  • Effects of subcooling on pool boiling heat transfer in vertical annuli with closed bottoms have been investigated experimentally. For the test, a tube of 19.1mm diameter and the water at atmospheric pressure have been used. Three annular gaps of 7.05, 18.15, and 28.20 have been tested in the subcooled water and results of the annuli are compared with the data of a single unrestricted tube. The increase in pool subcooling results in much change in heat transfer coefficients. At highly subcooled regions, heat transfer coefficients for the annuli are much larger than those of a single tube. As the heat flux increases and subcooling decrease, a deterioration of heat transfer coefficients is observed at the annulus of 7.05mm gap. Single-phase natural convection and liquid agitation are the governing mechanisms for the single tube while liquid agitation and bubble coalescence are the major factors at the bottom closed annuli.

Hysteresis on Boiling Heat Transfer at Low Temperature on Enhanced Tubes in a Flooded Evaporator (만액식 증발기의 열전달 촉진관에서 저온 비등열전달의 이력현상 특성)

  • 윤현필;박종익;정진희;강용태
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.4
    • /
    • pp.254-260
    • /
    • 2003
  • The boiling characteristics for R134a are studied to clarify the hysteresis at low temperature on enhanced tubes of a flooded evaporator. Initial boiling conditions, refrigerant temperature, and inlet temperature of the chilled water are considered as the key parameters of the experiments. Unlike previous studies of the boiling heat transfer with uniform heat flux and uniform wall temperature, the wall temperature was varied along the tube. In, this study, it was found that the hysteresis of the temperature overshoot (705) at the onset of nucleate boiling initially at the inlet section of the tube. It is also concluded that the abnormal operation can be avoided during the low temperature boiling if the refrigeration system is started with LMTD larger than $3.4^{\circ}C$ at initial stage and larger than $1.0^{\circ}C$ at normal stage.

Nucleate Pool Boiling Heat Transfer in Vertical Annuli (수직 환상 공간 내부의 풀핵비등 열전달)

  • Gang, Myeong-Gi
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.25 no.8
    • /
    • pp.1113-1121
    • /
    • 2001
  • Effects of gap sizes(3.9 and 15mm) of vertical annuli and the bottom blockage on the nucleate pool boiling heat transfer at atmospheric pressure condition have been examined experimentally, and the results were compared to those with a single tube without confinement. The annular geometry resulted in significant increase in heat transfer coefficient. The effect is much enhanced with the bottom blockage. The heat transfer coefficient for the closed bottom condition is three times greater than the unconfined tube at 30kW/㎡ when the gap size is 3.9mm. However, with further increase of the heat flux much more than 70kW/㎡, all these effects were diminished.

Effects of Tube Diameter on Nucleate Pool Boiling Heat Transfer (튜브 직경이 풀핵비등 열전달에 미치는 영향)

  • Kang, Myeong-Gie
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.7
    • /
    • pp.930-937
    • /
    • 2000
  • A series of data sets for the heat transfer coefficient versus wall superheat has been obtained experimentally using various combinations of tube diameters ($9.7{\sim}25.5mm$), surface roughness ($15.1{\sim}60.9nm$), and tube orientations (horizontal and vertical) to obtain effects of tube diameters on nucleate pool boiling heat transfer for the saturated water at atmospheric pressure. In addition, the results are compared with the well known Cornwell and Houston's correlation for horizontal tubes to identify the deviation of the present experimental data from the correlation and the applicability of it to vertical tubes. The experimental results show that the heat transfer coefficient decreases as the tube diameter increases for both horizontal and vertical tubes and they are in good agreement with the Cornwell and Houston's correlation within ${\pm}20%$ scatter range.

Pool Boiling Heat Transfer Coefficient of HFC32/HFC152a on a Plain Surface (평판 표면에서 HFC32/HFC152a 혼합냉매의 풀 비등 열전달계수)

  • Kang, Dong-Gyu;Lee, Yohan;Jung, Dongsoo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.9
    • /
    • pp.484-492
    • /
    • 2013
  • Nucleate pool boiling heat transfer coefficients (HTCs) are measured with HFC32/HFC152a mixture at several compositions. All data are taken at the liquid pool temperature of $7^{\circ}C$, on a horizontal plain square surface of $9.53{\times}9.53$ mm, with heat fluxes of 10 $kW/m^2$ to 100 $kW/m^2$ with an interval of 10 $kW/m^2$, in the increasing order of heat flux. Test results show that the HTCs of these mixtures are up to 45% lower than those of the ideal HTCs calculated by a linear mixing rule with pure fluids' HTCs, due to the mass transfer resistance associated with non-azeotropic refrigerant mixtures. Pool boiling data show the deduction in HTCs with an increase in GTD of the mixture. The present mixture data agree well with five well known correlations, within 20% deviation.

Pool boiling heat transfer enhancement by perforated plates (천공판의 풀비등 열전달 촉진에 대한 연구)

  • Kim, Nae-Hyeon
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.20 no.4
    • /
    • pp.1406-1415
    • /
    • 1996
  • Several recent studies have revealed that boiling heat transfer may be considerably enhanced in a narrow restricted region. In his study, the narrow restricted region was formed by attaching a perforated plate on top of a boiling surface. Through systematic experiments, effects of the hole size, hole pattern, gap width between the perforated plate and the boiling surface were investigated using water or R-113. Results show that perforated plates considerably enhance the boiling of water or R-113. For water, especially, they have outperformed commercial enhanced tubes, which confirms that boiling enhancement mechanism of the perforated plate (thin film evaporation beneath the elongated bubble) is very effective to the boiling of high surface tension liquids such as water. Optimum configuration was found - 3.0 mm hole diameter, 15 mm * 15 mm hole pattern, 0.3 ~ 0.5 mm gap width for water, and 2.0 mm hole diameter, 3.5 mm * 3.5 mm hole pattern, O.5 mm gap width for R-113. A correlation which correlates most of the data within .+-. 30% was also developed.