Characteristic of air-side sensible heat transfer and pressure drop on the corrugate fin tube heat exchangers (Corrugate 휜-관 현열 열교환기의 구조에 따른 공기측 열전달 및 압력손실 특성)

  • Ryu, Joon-Il;Jeon, Chang-Duk;Lee, Jin-Ho;Nam, Leem-Woo
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.216-221
    • /
    • 2007
  • An experiment was carried out to investigate the effect of a coolant circuit arrangement on the heat transfer and air pressure drop of a fin-tube sensible heat exchanger with the corrugated fin surface. The air inlet temperature was set to $23^{\circ}C$,the relative humidity to 50% and the air inlet flow rate to 20, 22, $25m^3/min$, respectively. while the coolant temperature was set to $7^{\circ}C$, and the coolant mass flow rate to 10, 16, 22kg/min, respectively. Experiment showed that the exchanger having a diameter of 12.7mm with parallel circuit does better performance in sensible heat transfer and air pressure drop than those three of diameter of 12.7mm with a series circuit and that with diameter of 15.88mm with a parallel circuit.