• 제목/요약/키워드: 캐스케이드 히트펌프

검색결과 3건 처리시간 0.017초

2단 승온 캐스케이드 히트펌프의 성능 특성에 관한 연구 (Study on the Performance of a Cascade Heat Pump with Two-stage Water Heating Process)

  • 장한별;최종민
    • 한국지열·수열에너지학회논문집
    • /
    • 제12권4호
    • /
    • pp.27-32
    • /
    • 2016
  • It is estimated that only heating and cooling take about one third of the total energy consumption worldwide. However, the conventional heating and cooling systems have low efficiencies. Also, boilers and electric heaters that are mostly used to generate both domestic and industrial hot water are inefficient and high energy consumers. For this reason, cascade heat pumps which are known to be very energy efficient and have less environmental impact are being promoted to replace conventional heating, cooling and hot water systems. In this study, a newly designed cascade heat pump by two-stage water heating method has been experimentally investigated. By adopting the auxiliary heat exchanger, the performance of the system was increased. The performance enhancement rate of the system could be maximized by adjusting the low stage compressor speed rather than the high stage compressor speed. The performance of the system with the auxiliary heat exchanger was enhanced by 16.5%.

해수열원 캐스케이드 열펌프시스템의 운전 특성에 관한 실험적 연구 (An Experimental Study on the Performance of a Sea Water Heat Source Cascade Heat Pump)

  • 김지영;백영진;장기창;박성룡;나호상;이재훈
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2007년도 춘계학술대회B
    • /
    • pp.1969-1973
    • /
    • 2007
  • The purpose of this study is to investigate the performance of a sea water heat source cascade heat pump system. R717(Ammonia) is used for a low-stage working fluid while R134a is for a high-stage. In order to gain a high temperature supply water in winter season, the system is designed to perform a cascade cycle. In this study, two experiments were carried out. One is a system starting test from the low load temperature of $10^{\circ}C$. The other is a system performance investigation over the R717 compressor capacity changes. Experimental results show that when it starts from the low load temperature, the suction temperature of the low-stage compressor is higher than that of a high-stage. The system performance increases when a water source temperature or a low-stage compressor rotational frequency goes higher.

  • PDF

캐스케이드 열펌프시스템의 운전 특성에 관한 연구 (A Study on the Operating Performance of a Cascade Heat Pump)

  • 장기창;백영진;나호상;김지영;이재훈
    • 한국지열·수열에너지학회논문집
    • /
    • 제5권1호
    • /
    • pp.7-11
    • /
    • 2009
  • The purpose of this study is to investigate the performance of a water heat source cascade heat pump system R717(Ammonia) is used for a low-stage working fluid while R134a is for a high-stage. In order to gain a high temperature supply water in winter season, the system is designed to perform a cascade cycle. In this study, two experiments were carried out. One is a system starting test from the low load temperature of $10^{\circ}C$. The other is a system performance investigation over the R717 compressor capacity changes. Experimental results show that when it starts from the low load temperature, the suction temperature of the low-stage compressor is higher than that of a high-stage. The system performance increases when a water source temperature or a low-stage compressor rotational frequency goes higher.

  • PDF