• Title/Summary/Keyword: 축열효율

Search Result 113, Processing Time 0.023 seconds

Experiment on the Charging and Discharging Processes of a Closed Ice-Thermal-Energy-Storage System (밀폐식 빙축열시스템의 축열 및 방열과정에 관한 실험)

  • Kim, Kyung-Hwan;Yoon, Young-Hwan;Kim, Yeon-Kyu
    • Journal of Energy Engineering
    • /
    • v.16 no.4
    • /
    • pp.164-169
    • /
    • 2007
  • The decrease in the summer peak electric load in our country is very important. The government has arranged and implemented a lot of support policies and statutes to decrease the peak electric load. And the ice-thermal-energy-storage system is known as one of the alternatives. The purpose of this paper is to evaluate the performance and the total efficiency of its storage tank, conducting the charging operation, the parallel operation and the single operation of a storage tank. The thermal energy density stored and discharging efficiency of a storage tank and the efficiency of total energy utilization of system are $18.4\;USRT-h/m^3$, 96.2% and 2028.7 kcal/kWh under the operation of design condition. When the storage tank is supplied more ice thermal energy than design condition, it is estimated that the efficiency of system are lower than the design condition by the supercooled effect.

A Study on Transient Thermal Behavior During the Charging Process in a Stratified Water Storage Tank and Its Storage Efficiency (성층 온수 저장 중 과도 열거동과 축열효율에 관한 연구)

  • Pak, E.T.;Chu, Y.J.;Kim, Y.H.
    • Solar Energy
    • /
    • v.17 no.3
    • /
    • pp.13-21
    • /
    • 1997
  • In this study, the theoretical equation of thermal storage efficiency was established to applied long term hot water storage system. The, effective thermal diffusivity and storage efficiency were, measured through the experiment to predict the degree of mixture in thermal storage tank. The effective thermal diffusivity was inversely preportional to the storage efficiency. The most effective storage efficiency was obtained under condition of low flow rate and using the perforated distributor.

  • PDF

The Study on Cooling Load Forecast of Ice-Storage System using Neural Network (신경망을 이용한 빙축열 시스템의 냉방부하예측에 관한 연구)

  • Koh Taek-Beom
    • Proceedings of the Korea Society for Industrial Systems Conference
    • /
    • 2006.05a
    • /
    • pp.115-118
    • /
    • 2006
  • 빙축열 시스템과 같은 열교환 시스템을 이용하여 심야의 전력 경부하 시 주간에 이용할 냉방부하를 축열하였다가 주간에 공급함으로써 전력의 평준화와 전력 설비의 효율적 운용을 기할 수 있어 전력의 안정적인 수급과 에너지의 효율을 극대화할 수 있다. 하지만 빙축열 시스템의 제어 운전을 전적으로 운전자의 경험에 의존하는 경우에 충분한 냉방 부하를 공급하기 위한 잉여축열에너지가 비경제적으로 많아져서 빙축열 시스템의 경제성이 저하되고 사용 효과가 낮아지는 문제점이 많이 발생되고 있다. 경제적인 활용 효과를 고려하여 빙축열 시스템을 효율적으로 운용하기 위해서는 냉방부하량이 기후 특성에 의해 결정되므로 기후를 정확하게 예측하고 이를 토대로 다음날의 시간별 냉방부하를 예측하여 적정한 축열량을 결정하여야 하는 어려움이 따른다. 이러한 문제를 해결하기 위해 본 연구에서는 신경망을 이용하여 기상 데이터를 토대로 다음날의 온도와 습도를 예측하고 예측된 온도와 습도 및 냉방부하 실적 자료를 기반으로 신경망을 이용하여 시간별 냉방부하를 예측하는 알고리즘을 제시하였다. 제안된 냉방 부하예측 알고리즘에 의해 구축된 한국전력공사 속초생활연수원의 부하예측모델을 이용하여 온도, 습도, 냉방부하를 예측한 결과 기존 방법에 의한 것보다 우수한 예측 성능을 보였다.

  • PDF

Thermal Energy Storage System for Air Conditioning (공조용 축열 시스템)

  • 임종성
    • Journal of the KSME
    • /
    • v.33 no.2
    • /
    • pp.183-190
    • /
    • 1993
  • 에너지 문제에 현명하게 대처하기 위해선 폐열과 심야전력을 활용한 축열시스템의 저변확대가 시급하다. 특히 우리나라와 같이 냉난방으로 인한 계절별 전력 수요폭이 심한 나라에서는 공조용 축열 시스템 개발이 필요하다. 현재 우리나라에 보급되고 있는 것은 빙축열 시스템이 대부분인데 지역과 조건 그리고 용량에따라 좀더 다양한 시스템 선택이 필요하다. 그리고 에너지의 축출 방법에 있어서도 전체 공조 시스템의 특성과 효율을 특히 고려해야 할 것이다. 축열 시스템의 핵심은 무엇보다도 축열조의 소형화(compact)와 축열 효율이다. 즉 되도록 작은 크기의 축열조 로써 최대한 많은 에너지를 저장하며 또한 최대한 많은 에너지를 회수하는 것이다. 일반적으로 축열조에 열을 저장 그리고 축출하는 과정에는 에너지(useful energy)의 손실이 생기게 된다. 이는 열전달 과정 중에 시스템 내의 엔트로피의 증가로 생기는 필연적인 손실로 이것을 최소로 하는 설계 기술이 필요하다.

  • PDF

A study on the Thermal Characteristics of a Thermal Storage Tank for using Gravels (자갈식 축열조의 축열특성에 관한 연구)

  • Park, Jung-Won;Park, Bong-Kyu;Ahn, Sang-Kyu
    • Solar Energy
    • /
    • v.12 no.1
    • /
    • pp.81-87
    • /
    • 1992
  • The purpose of this study was to investigate the fluid flow characteristics of heat storage in sensible heat storage system for use In cooling and heating of buildings. Heat storage material was gravels and experiments were performed in the condition of constant temperature. The experimental parameters were fluid velocity and size of gravels. The experimental results of the heat storage quantity and the heat storage efficiency by the variation of packing size and fluid velocity were as the follows : The maximum value of the heat storage capacity and heat storage efficiency and the minimum arriving time for maximum heat storage were observed when the packing ratio was 72.5% and the fluid velocity was 0.14m/s.

  • PDF

Design and Performance Estimation of Heat Regenerator for Small-scale Regenerative Radiant Tube Burner (열처리로용 소형 축열식 복사관 버너의 축열기 설계 기술평가)

  • Cho H. C.;Cho K. W.;Lee Y. K.
    • Journal of Energy Engineering
    • /
    • v.13 no.4
    • /
    • pp.291-295
    • /
    • 2004
  • Heat regenerator attached in small-scale regenerative radiant tube burner was designed using the theoretical computation code and was confirmed the performance of waste heat recovery ratio. From the computation, when ceramic ball of 4-5kg was used, temperature efficiency and available waste heat recovery ratio were predicted 80% and 70%, respectively. Similar efficiencies were obtained from the experiments using LPG. However, since exhaust gas temperature entered into regenerator was below 850$^{\circ}C$ which was moth lower than that we expected. air preheating temperature was lowered below 800$^{\circ}C$.

Design and Estimation of Performance of Heat Regenerator for Small-scale Regenerative Radiant Tube Burner (소형 축열식 복사관 버너시스템용 축열기 설계 및 성능평가)

  • 조한창;조길원;이용국
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 2004.05a
    • /
    • pp.171-176
    • /
    • 2004
  • Heat regenerator attached in small-scale regenerative radiant tube burner was designed using the theoretical computation code and was confirmed the performance of waste heat recovery ratio. From the computation, when ceramic ball of 4-5kg was used, temperature efficiency and available waste heat recovery ratio were predicted 80% and 70%, respectively. Similar efficiencies were obtained from the experiments using LPG. However, since exhaust gas temperature entered into regenerator was below 85$0^{\circ}C$ which was much lower than that we expected, preheat air temperature was lowered below 80$0^{\circ}C$.

  • PDF

실시간 부하예측 기술을 이용한 빙축열 냉방시스템의 최적제어

  • 한도영
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.29 no.2
    • /
    • pp.25-31
    • /
    • 2000
  • 최근 경제성장과 생활수준의 향상으로 냉방기기의 설치가 보편화되면서 하절기 냉방부하 증가에 따른 전력 에너지 공급상의 위기를 맞고 있다. 이와 같은 문제점을 해결하기 위하여 한국전력공사에서는 심야 전력 공급 시간에 냉동기를 가동하여, 얼음의 형태로 냉열을 저장하였다가 주간 냉방에 활용하는 빙축열 냉방 시스템을 보급 하여 주간전력 사용을 우회시키는 방법으로 전력수급의 안정화에 기여하고 예비율을 높이려는 노력을 하고 있다. 이러한 빙축열 냉방 시스템을 좀더 효율적으로 사용하기 위해서는 빙축열 냉방 시스템에 대한 연구가 필요하며 특히 빙축열 부하예측 기술과 시스템 최적제어 기술의 개발은 최대순간 요구부하의 개선은 물론 시스템의 성능향상과 에너지 소비감소에도 효과적으로 쓰일 수 있다. 따라서 본고에서는 야간에 빙축조에 저장시킨 축열만으로 주간의 냉방부하를 감당하게 하는 전부하 축열 방식을 선택하여 시스템 각 구성요소의 동적현상을 고려한 효과적인 수학적 모텔을 제시하고 이를 사용하여 빙축열 냉방시스탱의 최적제어 알고리즘을 개발하고 시뮬레이션을 통해 그 효율성을 확인하는 것을 목적으로 한다.

  • PDF

Performance Analysis of a Vertical Double Pipe Heat Exchanger for Latent Heat Storage (수직이중관형 잠열축열장치의 성능분석)

  • Kim, Young-Bok;Song, Hyun-Kap
    • Solar Energy
    • /
    • v.10 no.1
    • /
    • pp.38-46
    • /
    • 1990
  • For the optimal design and the efficient operation of the double pipe type latent heat storage equipment, the effect of the parameters of the system were analysed. The statistical analysis showed that the theoretical and the experimental results of the volume change rate and the temperature variations were well agreed. Therefore, this theoretical model is reasonable to analyze two dimensional moving boundary problems. In the analysis of the effects of the parameters, the heat extraction fraction and the water outlet temperature of the system as function of the time were analysed depending on the initial temperature of PCM, water inlet temperature, water mass flow rate and the dimension of the inner tube.

  • PDF

Preliminary Feasibility Study of Separated Aquifer Thermal Energy Storage System using Numerical Method (수치 모델링 기법을 이용한 개별 대수층 축열 시스템 활용성 예비 평가)

  • Kim, Jong-Chan;Kim, Hyoung-Soo;Lee, Young-Min
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 2009.11a
    • /
    • pp.556-560
    • /
    • 2009
  • 개별 대수층에 냉수와 온수를 저장하여 수자원과 냉난방 열원으로 활용하는 방안에 대한 평가를 지열-지하수 부정류 모델링을 통해 수행하였다. 저장 및 회수 가동 시간이 증가함에 따라서 각각의 대수층 내에 온열과 냉열이 축열되는 현상이 확인되었으며, 지하수 유동에 의해 축열된 수체가 지하수 흐름방향으로 이동하는 현상을 확인 하여 지하수 유동이 축열 정도를 결정하는 요인이 될 수 있음을 확인하였다. 설정된 모델에 대하여, 두 개의 개별 대수층 사이의 열 간섭은 거의 없는 것으로 나타났다. 주입과 양수의 가동 횟수가 증가되면, 대수층 축열 효과는 증대되는 것으로 나타났다. 열-지하수 모델링을 통한 온도 예측은 실제 냉난방의 효율성을 결정짓는 수온을 정량적으로 계산할 수 있는 유용한 기술로 평가됨과 더불어, 수자원의 지하 저장을 통해 효율적으로 물을 확보하고 관리할 수 있는 방안이 될 수 있을 것으로 기대된다.

  • PDF