• Title/Summary/Keyword: 직교류 열교환기

Search Result 20, Processing Time 0.024 seconds

Experimental Investigation of an Cross-Flow Air-Cooled Plate Heat Exchanger with Single-Wave and Double-Wave Plates (단일굴곡 및 이중굴곡 판 형상을 갖는 직교류 공랭식 판형열교환기의 전열특성에 대한 실험적 연구)

  • Kim, Min-Sung;Paik, Young-Jin;Lee, Jae-Hoon;Park, Seong-Ryong;Ra, Ho-Sang;Jeong, Jae-Hoon;Lim, Hyug
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.6
    • /
    • pp.347-354
    • /
    • 2009
  • Experimental study on a cross-flow air-cooled plate heat exchanger (PHE) was performed. Two types of PHEs were manufactured either with single-wave plates or with double-wave plates in parallel. Cooling air flows through the PHEs in a crosswise direction against internal hot water. The heat exchanger aims to substitute open-loop cooling towers with closed-loop water circulation, which guarantees cleanliness and compactness. In this study, prototype single-wave and double-wave PHEs were designed and tested in a laboratory scale experiments. From the tests, the double-wave PHE shows approximately 50% enhanced heat transfer performance compared to the single-wave PHE. However, the double-wave PHE costs 30% additional pressure drop. For the commercialization, a wide channel design for air flow would be essential for performance and reliability.

Experimental Study of Air Side Pressure Drop and Heat Transfer Characteristics of Enhanced Fin-Tube Heat Exchangers (열전달 촉진 핀-관 열교환기의 공기측 압력강화 및 열전달 특성에 관한 실험)

  • Youn, Baek;Kil, Yong Hyun;Park, Hyun Yeon;Kim, Young Saeng
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.22 no.11
    • /
    • pp.1555-1563
    • /
    • 1998
  • Heat transfer and pressure drop for ${\phi}10.07$ dry surface fin-tube heat exchanger with wave and wave-slit fins were measured for different fin spacings and number of tube rows. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively, and wave depth of wave fin is 1.5mm. The experiments were performed for 4 different fin spacings, 1.3, 1.5, 1.7 and 2.0mm, and the number of tube rows were 1,2 and 3 rows. The present results were compared with the previous results for the wave depth of 2mm. Also hydrophilic coated and bare fins were tested. Correlations for Colburn j-factor and friction factor were developed.

Experimental study of air side pressure drop and heat transfer characteristics of wave and wave-slit fin-tube heat exchangers (웨이브 및 웨이브-슬릿 열전달촉진 휜-관 열교환기의 공기측 압력강하 및 열전달 특성에 관한 실험)

  • Yoon, Baek;Gil, Yong-Hyun;Park, Hyun-Yeon;Yoo, Guk-Chul;Kim, Young-Saeng
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.10 no.5
    • /
    • pp.589-599
    • /
    • 1998
  • Air side heat transfer and pressure drop for fin-tube heat exchanger with wave and wave-slit fins were measured for various fin spacings and number of tube rows. Outer diameter of the tube including fin collar is 10.07mm, and experiments were done with dry surface condition. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively, and wave depth of the wave fin is 2mm. Experiments were conducted for 1, 2 and 3 rows and 3 different fin spacings, 1.3, 1.5 and 1.7mm. An attempt was made to demonstrate advantage of the enhanced fins over the plane fin by introducing the concept of fan power, Effect of the number of tube rows on heat transfer was discussed in connection with general mechanisms of heat transfer enhancement for fin-tube heat exchanger. Also the effect of hydrophilic coating was investigated. Lastly, correlations for Colburn j-factor and friction factor were developed.

  • PDF

Performance Analysis and Testing of a Cross-Flow Aluminum Heat Exchanger for Kitchen Ventilation (주방환기용 직교류 알루미늄 열교환기의 성능해석 및 시험)

  • Kim N.H.;Cho J.P.;Han S.P.;Choi J.Y.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.3
    • /
    • pp.193-201
    • /
    • 2006
  • Thermal performance model was developed for a cross-flow aluminum heat exchanger with relatively short passage. Appropriate heat transfer coefficient and friction factor equations for laminar channel flow were obtained considering developing regions. The heat exchanger was analyzed using the unmixed cross-flow ${\epsilon}$-NTU relationship considering leak-age between streams. Thermal contact between corrugations and plates was also considered. Tests were separately conducted for two samples - one made of non-treated aluminum sheets, and the other made of varnish-treated ones. The samples were made by stacking corrugations and plates one after another. The model adequately predicted the thermal performance and pressure drop of the non-treated heat exchanger. The thermal performance of the varnish-treated one was $7{\sim}12%$ overpredicted, and the pressure drop of the varnished-treated heat exchanger was $5{\sim}15%$ underpredicted. The air leakage ratio of the non-treated heat exchanger was $23{\sim}26%$. The ratio decreased to less than $10%$ with the varnish treatment.

Heat Transfer Enhancement in Cross-flow Heat Exchanger Using Vortex Generator (와류발생기를 사용한 직교류 열교환기의 열전달 촉진)

  • Yoo, Seong-Yeon;Kwon, Hwa-Kil;Lee, Sang-Sub;Kim, Byeong-Chae;Park, Dong-Seong
    • Proceedings of the KSME Conference
    • /
    • 2003.11a
    • /
    • pp.61-66
    • /
    • 2003
  • Fouling is very serious problem in heat exchanger because it rapidly deteriorates the performance of heat exchanger. Cross-flow heat exchanger with vortex generators is developed, which enhance heat transfer and reduce fouling. In the present heat exchanger, shell and baffle are removed from the conventional shell-and-tube heat exchanger. The naphthalene sublimation technique is employed to measure the local heat transfer coefficients. The experiments are performed for single circular tube, staggered array tube bank and in-line array tube bank with and without vortex generators. Local and average Nusselt numbers of single tube and tube bank with vortex generator are investigated and compared to those of without vortex generator.

  • PDF

Analysis of Heat Transfer Performance for Mini-Channel Tube Bundles in Cross flow using CFD (전산유체역학을 이용한 직교류 미세관 관군의 전열 성능 해석)

  • Nam, Ki-Won;Min, Jun-Kee;Jeong, Ji-Hwan
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.34 no.4
    • /
    • pp.491-499
    • /
    • 2010
  • Heat transfer performance of tube bundles have long been investigated since they were widely used. Most of previous experimental and numerical works for tube bundles were performed with tube diameter in the range of 25~51mm and Reynolds number of $8.000{\leq}Re{\leq}30.000$. Recently, tube bundles with small diameter tube collects interests since the mini-channel tube provides higher compactness. The present work aims to investigate the applicability of previous correlations available in the open literature to the tube bundles with small diameter of 1.5mm and $3.000{\leq}Re{\leq}7.000$. A commercial CFD package was used to analyze the thermal-hydraulic performance of them. The results show that the Zukauskas correlation developed for larger diameter tube and higher Reynolds number are still in good agreement with them within the discrepancy of 4.7%. The analyses also show that the Nuselt number increases with a decrease in the longitudinal pitch.

A theoretical Analysis and CFD Simulation on the Ceramic Heat Exchanger (세라믹 열교환기의 이론해석 및 CFD 시뮬레이션)

  • Paeng, Jin-Gi;Yoon, Young-Hwan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.5
    • /
    • pp.282-290
    • /
    • 2009
  • A ceramic monolith heat exchanger is studied to find the performance of heat transfer and pressure drop by numerical computation and $\xi$-NTU method. The numerical computation was performed throughout the domain including fluid region in exhaust gas-side rectangular ducts, ceramic core and fluid region in air-side rectangular duct with the air and exhaust in cross flow direction. In addition, the heat exchanger was also analyzed to estimate the performance by conventional $\xi$-NTU method with several Nusselt number correlations for flow in rectangular duct from literature. By comparisons of both performances by the numerical computation and the $\xi$-NTU method, the effectiveness by $\xi$-NTU method was closest to the result by numerical computation within a relative error of 2.14% when Stephan's Nusselt number correlation was adopted to the $\xi$-NTU method among the several correlations.

Aluminum and Plastic Heat Exchange Element : A Performance Comparison for Cooling of Telecommunication Cabinet (통신 함체 냉각용 알루미늄과 플라스틱 열교환 소자의 성능 비교)

  • Kim, Nae-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.6
    • /
    • pp.279-288
    • /
    • 2017
  • Heat generation rate in a telecommunication cabinet increases due to the continued usage of mobile devices. Insufficient removal of heat intensifies the cabinet temperature, resulting in the malfunction of electronic devices. In this study, we assessed both aluminum and plastic heat exchangers used for cooling of the telecommunication cabinet, and compared the results against theoretical predictions. The aluminum heat exchanger was composed of counter flow parallel channels of 4.5 mm pitch, and the plastic heat exchangers were composed of cross flow triangular channels of 2.0 mm pitch. Samples were made by installing two plastic heat exchangers in both series and parallel. Results showed that the heat transfer rate was highest for the series cross flow heat exchanger, and was least for the aluminum heat exchanger. The temperature efficiency of the series cross flow heat exchanger was 59% greater than that of the aluminum heat exchanger, and was 4.3% greater than that of the parallel cross flow heat exchanger. In contrast, the pressure drop of the parallel cross flow heat exchanger was significantly lower than other samples. The heat exchange efficiency was also the largest for the parallel cross flow heat exchanger. The theoretical analysis predicted the temperature efficiency to be within 3.3%, and the pressure drop within 6.1%.

An experimental study on the performance of a window system air-conditioner using R407C and R410B (R407C 및 R410B 적용 창문형 에어컨의 성능에 관한 실험적 연구)

  • Kim, M.H.;Shin, J.S.;Kim, K.J.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.9 no.4
    • /
    • pp.536-544
    • /
    • 1997
  • This study presents test results of a residential window system air-conditioner using R22 and two potential alternative refrigerants, R407C and R410B. A series of performance tests was performed for the basic and liquid-suction heat exchange cycle in a psychrometric calorimeter test facility. For R407C, the same rotary compressor was used as in the R22 system. However, compressor for the R410B system was modified to provide the similar cooling capacity. The evaporator circuit was changed to get a counter-cross flow heat exchanger to take advantage of zeotropic mixture's temperature glide, and liquid-line suction-line heat exchange cycle was also considered to improve the performance of the system. Test results were compared to those for the basic R22 system.

  • PDF

A Study on Numerical Analysis of Thermal Stress for an Monolith Ceramic Heat Exchanger (일체형 세라믹 열교환기의 전산 열응력 해석에 관한 연구)

  • Paeng, Jin-Gi;Kim, Ki-Chul;Yoon, Young-Hwan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.11
    • /
    • pp.613-620
    • /
    • 2009
  • The thermal stresses of a ceramic heat exchanger were analyzed numerically since the ceramic material is good in heat resistance but weak in the thermal stress. The analysis of thermal stress was conducted in the ceramic core with two boundary conditions depending on bolt jointing. The thermal stresses were computed by applying temperature and pressure distributions obtained from the numerical results of conjugate heat transfer to ANSYS WORKRBENCH. When number of bolt joining halls was reduced from $8\times2$ to $4\times2$, the maximum principal stresses decrease by 47.6~50.5% and increase in safety factors by 2.18~2.5 for ultimate tensile strength. Thus, it can be said that bolt joining halls should be minimized in ceramic heat exchanger to be efficient in reducing thermal stress. In addition, the width of particular gas flow passages were revised from 52 mm to 42 mm to reduce maximum thermal stresses since certain passages experienced high thermal stresses. From the revision, safety factors were increased by 13.8~14.1% for the boundary condition of $4\times2$ bolt joining halls. Therefore, it is suggested that thermal stress can be reduced by changing local geometry of a ceramic heat exchanger.