Heating Performance Analysis of Building Integrated Geothermal System (건물일체형 지열히트펌프시스템의 난방 성능 분석)

  • Jin, Shangzhen;Lee, Jin-Uk;Kim, Tae-Yeon;Leigh, Seung-Bok
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2012.03a
    • /
    • pp.206-210
    • /
    • 2012
  • Ground source heat pump is a central heating and cooling system that pumps heat to or from the ground. Building Integrated Geothermal system used in this experiment is one of the Ground Source Heat Pump Systems which utilize energy pile. The purpose of this study is to evaluate heating performance of the system. The building is a low-energy experiment apartment in Yonsei University Songdo Campus and the subject is one of the energy reduced houses in this apartment. In the experiment, indoor temperature, outdoor temperature and the inlet and outlet temperature of ground heat exchanger and subject model, were measured. Then the heat pump's Coefficient of performance(COP) of the heat pump was calculated. As a result, the COP of heat pump is 4-5. Although the depth of the ground heat exchanger in this experiment is shallower than usual heat exchanger, the result of heating performance of this system was good as well.

  • PDF

Measurements of In-situ Thermal Conductivity of Closed Type Ground Heat Exchanger in Korea (국내의 주요 지역에서 밀폐형 열교환기의 열전도도 측정)

  • Jung, Kye-Hoon;Lim, Hyo-Jae;Han, Ji-Won;Park, Kyung-Woo
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.3401-3406
    • /
    • 2007
  • This study was performed to acquire the reliable in-situ thermal conductivity of closed type ground heat exchanger used in ground source heat pump. We selected four sites(Cheonan, Daejeon, Daegu, Gwangju) which are central area of South Korea. Test results show that the effective thermal conductivities are 2.33 W/m$^{\circ}C$, 2.50 W/m$^{\circ}C$, 2.75 W/m$^{\circ}C$ and 2.86 W/m$^{\circ}C$. From this data, we can see that thermal conductivity varies about the range of 23% with the sites. Also, thermal conductivity increases up to 20% by changing grouting material from low salica sand to high one.

  • PDF

Heat Pipe Heat Exchanger (히트파이프 열교환기)

  • 이영수;이기우
    • Journal of the KSME
    • /
    • v.35 no.9
    • /
    • pp.805-815
    • /
    • 1995
  • 히트파이프에 관한 연구는 구미, 일본 등 선진 각국뿐만 아니라, 중국, 독립국가연합 및 동구권 에서도 다년간 활발하게 진행되어 왔다. 석유파동 이후 에너지 절약을 위한 노력의 결과로 폐 열회수 장치가 많이 개발되면서 히트파이프를 전열소자로 사용한 폐열회수 장치가 상당히 늘어나 이에 소요되는 히트파이프의 생산량도 급격한 신장세를 나타내고 있다. 이는 히트파이프 자체가 응답성이 좋고, 구조가 간단하며, 전열성이 뛰어난 장점으로 인하여 많은 연구가 이루어졌기 때 문이라 하겠다.그 응용분야는 인공위성으로부터 폐열회수용 열교환기, 전기장치 전자소자의 냉각, 음향기기의 냉각, 태양열과 지열의 유효이용, 플라스틱 금형의 냉각, 공작기계의 주축냉각, 포장 기계, 주방기기, 전력케이블의 냉각, 엔진 및 브레이크의 냉각 등 응용분야가 광범위하여 급격 하게 발전하고 있다. 그러나 국내에서는 히트파이프와 관련된 학술적인 연구결과가 발표되고 있을 뿐, 체계적이며 지속적인 연구가 수행되지 못하고 있다. 또한 산업계에서도 관련제품의 대 부분을 수입에 의존하고 있으며, 일부 제작업체에서는 제품이 나오고 있으나 축적기술결여로 그 성능면에 있어서 보증이 어려워 업계의 연구개발에 대한 노력이 절실히 요구되고 있다.

  • PDF

Effects of Soil and Air Flow Characteristics on the Soil-Air Heat Exchanger Performances (토양과 공기유동특성이 토양-공기 열교환기 성능에 미치는 영향)

  • 김영복;김기영
    • Journal of Biosystems Engineering
    • /
    • v.23 no.1
    • /
    • pp.21-30
    • /
    • 1998
  • A theoretical model was developed to evaluate the effects of soil and airflow characteristics on the soil-air heat exchanger performances. The model, which includes three-dimensional transient energy and mass equilibrium-equation, was solved by using a computer program that uses Finite Difference Methods and Gauss-Seidel iteration computation. Energy gains, heat exchange efficiencies, and outlet air temperature are presented including the effects of soil moisture content, soil conductivity, soil thermal diffusivity, and soil initial temperature. Also, data related to the effects of airflow rate and inlet air temperature on the thermal performance of the system are presented. The results indicated that energy gains depend on soil conductivity, soil thermal diffusivity, and soil initial temperature. Heat exchange efficiencies relied on air mass flow rate and soil moisture content.

  • PDF

A study on the Heat Transfer Performance according to Ground Heat Exchanger Types (지중열교환기의 종류에 따른 열전달 성능에 관한 연구)

  • Hwang, SuckHo;Song, Doosam
    • KIEAE Journal
    • /
    • v.10 no.4
    • /
    • pp.75-80
    • /
    • 2010
  • Generally, ground-source heat pump (GSHP) systems have a higher performance than conventional air-source systems. However, the major fault of GSHP systems is their expensive boring costs. Therefore, it is important issue that to reduce initial cost and ensure stability of system through accurate prediction of the heat extraction and injection rates of the ground heat exchanger. Conventional analysis methods employed by line source theory are used to predict heat transfer rate between ground heat exchanger and soil. Shape of ground heat exchanger was simplified by equivalent diameter model, but these methods do not accurately reflect the heat transfer characteristics according to the heat exchanger geometry. In this study, a numerical model that combines a user subroutine module that calculates circulation water conditions in the ground heat exchanger and FEFLOW program which can simulate heat/moisture transfer in the soil, is developed. Heat transfer performance was evaluated for 3 different types ground heat exchanger(U-tube, Double U-tube, Coaxial).

Development of low-cost, low-depth unit-type ground heat exchanger (저심도 저비용 유닛형 지중열교환기의 개발)

  • Oh, Jin-Hwan;Nam, Yujin;Chae, Ho-Byung
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2014.05a
    • /
    • pp.166-167
    • /
    • 2014
  • Recently, in according to increase cognizance of energy and resources exhaustion, renewable energy system is received attention. In particular, ground heat pump system(GSHP) utilizing annually stable ground temperature for energy saving have been attracted in many buildings. However, GSHP system have disadvantage due to increase of initial installation and boring cost. In this study, in order to reduce the initial cost and to supply ground heat pump system into small scale house, an unit-type ground heat exchanger was developed.

  • PDF

Effects of Earth-Tube Characteristics on the Soil-Air Heat Exchanger Performances (지중매설관의 특성이 토양 - 공기 열교환기 성능에 미치는 영향)

  • 김영복
    • Journal of Biosystems Engineering
    • /
    • v.22 no.4
    • /
    • pp.459-468
    • /
    • 1997
  • To optimize the design and operation of a soil- air heat exchanger system, the effects of variables characterizing system design and operation on the performance of the system were analyzed by a theoretical model which included the three-dimensional transient heat conduction equation. The solution of the theoretical model was acquired by a computer program that uses Finite Difference Methods and Gauss-Seidel iteration computation, in which the time discretization scheme was an implicit difference appoximation. The computer program was validated first by comparison of the results for different grid sizes. Air outlet temperature, energy gain, and heat exchange efficiency of the system were analyzed based upon the tube diameter, tube length, tube thickness, and tube thermal diffusivity.

  • PDF

Thermal Conductive Characteristics and Basic Properties of Bentonite Grouts for the Ground Heat Exchanger of Geo-source Heat Pump (지열히트펌프 지중열교환기용 벤토나이트계 그라우트재의 열전도특성 및 기본성능)

  • Bai, Kang
    • Journal of the Korean Solar Energy Society
    • /
    • v.33 no.1
    • /
    • pp.66-72
    • /
    • 2013
  • In this study, the thermal conductive characteristics and basic properties of the nine commercial products of bentonite grouts were studied. Six of the nine products for ground heat exchanger systems are imported and others for civil engineering are domestic. The thermal conductivities of all bentonite products are nearly similar among products. The free swell indexes, viscosities and filter losses of the ground heat exchanger grouts are lower than those of the civil engineering ones. These characteristics seem to increase of the fluidity to fill the bentonite slurry to bore-hall perfectly, rather than to prevent underground water penetration. Thus, the mixtures of bentonites and sands are recommended for high thermal conduction grouts.

Numerical analysis of the vertical tube-in-tube ground coil heat exchanger (수직으로 매설된 이중관형 지중 열교환기에 대한 해석적인 연구)

  • 유지오;금성민;신현준
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.3
    • /
    • pp.339-348
    • /
    • 1999
  • A computer model was developed in order to predict the temperature distribution and the performance of the vertical tube-in-tube ground coil heat exchanger. This model has been validated by experimental results conducted by ORNL. The heat exchanger performance with the variation of the length is calculated and compared. As results, the heat exchanger performance is proportional to the length but the performance per unit length decreases. The minimum performance of 70m - PVC heat exchanger during cyclic operation for a week is obtained 20,054kJ/h for cooling operation and 13,915kJ/h for heating operation. And minimum temperature difference is $4.64^{\circ}C$ for cooling operation and $2.64^{\circ}C$ for heating operation. In each case, it is noted that the temperature difference between the pipe and the far-field occurs within 0.8m from the heat exchanger.

  • PDF

A Study on Development Potential of Shallow Geothermal Energy as Space Heating and Cooling Sources in Mongolia (몽골의 천부 지열에너지(냉난방 에너지)개발 가능성에 관한 연구)

  • Hahn, Jeong-Sang;Yoon, Yun-Sang;Yoon, Kern-Sin;Lee, Tae-Yul;Kim, Hyong-Soo
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.8 no.2
    • /
    • pp.36-47
    • /
    • 2012
  • Time-series variation of groundwater temperature in Mongolia shows that maximum temperature is occured from end of October to the first of February(winter time) and minimum temperature is observed from end of April to the first of May(summer time). Therefore ground temperature is s a good source for space heating in winter and cooling in summer. Groundwater temperatures monitored from 3 alluvial wells in Ulaabaatar at depth between 20 and 24 m are $(4.43{\pm}0.8)^{\circ}C$ with average of $4.21^{\circ}C$ but mean annual ground temperature(MAGT) at the depth of 100 m in Ulaanbaatar was about $3.5{\sim}6.0^{\circ}C$. Bore hole length required to extract 1 RT's heat energy from ground in heating time and to reject 1 RT's heat energy to ground in summer time are estimated about 130 m and 98 m respectively. But in case that thermally enhanced backfill and U tube pipe placement along the wall are used, the length can be reduced about 25%. Due to low MAGT of Ulaabaatar such as $6^{\circ}C$, the required length of GHX in summer cooling time is less than the one of winter heating time. Mongolia has enough available property, therefore the most cost effective option for supplying a heating energy in winter will be horizontal GHX which absorbs solar energy during summer time. It can supply 1 RT's ground heat energy by 570 m long horizontally installed GHX.