• Title/Summary/Keyword: 증발식 열교환기

Search Result 28, Processing Time 0.024 seconds

An Experimental Study on the Evaporative Heat Transfer Characteristics of R-134a in a Micro-Channel Heat Exchanger (마이크로채널 열교환기에서 R-134a의 증발열전달 특성에 관한 실험적 연구)

  • Lee, Hae-Seung;Jeon, Dong-Soon;Kim, Young-Lyoul;Kim, Yong-Chan;Kim, Seon-Chang
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.34 no.2
    • /
    • pp.113-120
    • /
    • 2010
  • An experimental investigation was carried out to examine the evaporative heat transfer characteristics of R-134a in a micro-channel heat exchanger. The micro-channel heat exchanger used in this study was a sort of plate heat exchanger. Micro-channels were fabricated on the SUS304 plate by the photo-etching process: 13 sheets of plates were stacked and bonded by the diffusion bonding process. The effects of the evaporating temperature, mass flux of R-134a, and inlet temperature of water were examined. As the difference between the inlet temperatures of R-134a and water increased, the heat transfer rate increased. The evaporative heat transfer coefficients obtained in this study range from 0.67 to 6.23 kW/$m^2{\cdot}^{\circ}C$. The experimental correlation for the Nusselt number as a function of the Reynold number and $\Theta$ was suggested for the micro-channel heat exchanger.

Evaluation of Air-side Friction Characteristics on Design Conditions of Slit Fin and Tube Heat Exchanger (슬릿휜-관 열교환기의 설계조건에서 공기측 압력강하 산출)

  • Cho, Sung-Chul;Kim, Chang-Duk;Kim, Chang-Eob;Kwon, Jeong-Tae;Lim, Hyo-Jae
    • Journal of Energy Engineering
    • /
    • v.16 no.3
    • /
    • pp.149-154
    • /
    • 2007
  • An experimental study on the air-side pressure drop of slit fin-tube heat exchanger has been carried out. The data reduction methodology for air-side pressure drop in the literature is not based on a consistent approach. This paper focuses on method of data reduction to obtain the air-side performance of fin-tube heat exchanger using R22 and recommends standard procedures for dry and wet surface pressure drop estimation in fin-tube heat exchanger. A comparison was made between the predictions of previously proposed empirical correlations and experimental data for the air-side pressure drop on design conditions of condenser and evaporator. Results are pre-sented as plots of friction f-factor against Reynolds number based on the fin collar outside diameter and compared with previous studies. The data covers a range of refrigerant mass fluxes of $150{\sim}250\;kg/m^2s$ with air flows at velocity ranges from 0.38 m/s to 1.6 m/s.

Fault Detection and Diagnosis (FDD) Using Nonlinear Regression Models for Heat Exchanger Faults in Heat Pump System (비선형회귀모델을 이용한 히트펌프시스템의 열교환기 고장에 대한 고장감지 및 진단에 대한 연구)

  • Kim, Hak-Soo;Kim, Min-Soo
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.35 no.11
    • /
    • pp.1111-1117
    • /
    • 2011
  • This paper proposed a fault detection and diagnosis (FDD) algorithm using nonlinear regression models, focusing especially on heat exchanger faults. This research concerned four working modes: those with no fault, evaporator fault, condenser fault, and evaporator and condenser faults. This research used no fault mode data to create an FDD algorithm. Using the no fault mode data, correlation functions for predicting the degree of superheat or subcool of heat exchangers (an evaporator and a condenser) were derived. Each correlation function has five inputs and one output. Based on these correlation functions, it is possible to predict the degree of superheat or subcool of each heat exchanger under various working conditions. The FDD algorithm was developed by comparing the predicted value and the simulation value. The FDD algorithm works well in all four working modes.

Analysis of a Continuous and Instantaneous Vacuum Drying System for Drying and Separation of Suspended Paricles in Waste Solvent (폐용제에 함유된 입자의 건조 및 분리용 연속식 순간 진공건조시스템 해석)

  • 구재현;이재근
    • Resources Recycling
    • /
    • v.9 no.4
    • /
    • pp.28-36
    • /
    • 2000
  • This study describes to analyze the characteristics for separation and recovery of both the dried particles and the purified solvent from the waste solvent through the vaporization process by the continuous and instantaneous vacuum drying system. The vacuum drying system for the waste solvents recovery consists of a feeding pump, a double pipe heat exchanger, a vacuum spray chamber, and a condenser. The vacuum drying system heats the waste solvent to the vapor in the double pipe heat exchanger and the expanded vapor is sprayed at the end of the tube. The vaporized solvent in the condenser are recovered. The particles in the waste solvent are separated and dried from the vapor in the vacuum spray chamber. Performance evaluation of the vacuum drying system was conducted using the mixture of the dried pigment particles and benzene or alkylbenzene as test samples. For the mixture of 10 wt% pigment particles an 90% benzene, the recovery efficiency of benzene was 88% with the purity of 99% and the recovery efficiency of dried particles was 94% with the moisture of 1.1 wt%. The size of pigment particles was decreased from $6.5\mu\textrm{m}$ to $5.6\mu\textrm{m}$ in diameter due to high speed spraying and dispersion in the vacuum drying system during drying process. Therefore, the vacuum drying system showed to be an effective method for separating particles and solvent in the waste solvent.

  • PDF

직접 접촉방식 열 및 물질교환장치의 전달현상(III)

  • 김석현
    • Journal of the KSME
    • /
    • v.26 no.1
    • /
    • pp.31-35
    • /
    • 1986
  • 물질전달이 포함되는 교환기의 설계목표도 단순열교환기의 경우와 마찬가지로 여러 가지 주어진 제약조건(constraints; 예를들면 교환기의 제원이나 유체유동에 필요한 압력부하등)을 만족시키 면서 전달능력의 단위(number of transfer units, 이하 $N_{tu}$ 로 약함)를 최대로 해 주는데 있다. 그러나 교환장치들의 유형이나 형상에 따라 이같은 동일 목적을 위한 과정은 각양각색 이다. 본장에서는 직접 접촉식 교환기의 많은 종류중 물의 직접증발을 이용한 단열가습장치와 고체건조제 단열제습장치등 두가지의 해석과정을 예시하려고 한다.

  • PDF

Simulation of a Double Effect Double Stage Absorption Heat Pump for Usage of a Low Temperature Waste Heat (저온 폐열 활용을 위한 2중 효용 2단 흡수식 히트펌프 시뮬레이션)

  • Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.11
    • /
    • pp.7736-7744
    • /
    • 2015
  • Considering the significant waste of industrial energy, effective use of low temperature waste heat is extremely important. In this study, a heat pump cycle with double effect and double stage was realized, which escalates the hot water temperature from $50^{\circ}C$ to $70^{\circ}C$ using $160^{\circ}C$ high temperature heat source and $17^{\circ}C$ low temperature heat source. The steam generated in the first generator condenses in the first condenser generating steam in the second generator. The steam condenses in the second condenser and is provided to the second evaporator. Part of the water out of the second evaporator is supplied to the first evaporator, which evaporates using low temperature waste heat. The evaporated steam enters the first absorber and the second evaporator. The steam out of the second evaporator is absorbed into the solution at the second absorber. The hot water temperature is raised in the second condenser and in the second absorber. Proper flow rates and UA values, which satisfied temperature lift $20^{\circ}C$ and COP 1.6, were deduced through trior and error. The COP increases as the temperature of the high temperature water increases, hot water temperature decreases and flow rate increases, waste water temperature and flow rate increases, solution circulation rate decreases. On the other hand, the temperature rise of the hot water increases as the temperature of the high temperature water increases, hot water temperature increases and flow rate decreases, waste water temperature and flow rate increases, solution circulation rate increases. In addition, the COP and hot water temperature rise increase as UAs of the heat exchangers increase.

Evaporation kent transfer characteristics of R-290 and R-600a in the horizontal tubes (수평관내 R-290과 R-600a의 증발 열전달 특성)

  • Son, Chang-Hyo
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.9 no.2
    • /
    • pp.264-269
    • /
    • 2008
  • This paper presents the experimental results of evaporation heat transfer coefficients of HC(e.g. R290 and R600a), R-22 as a HCFCs refrigerant in horizontal double pipe heat exchangers, having four different inner diameters of 10.07 mm and 6.54 mm respectively. The experiments of the evaporation process were conducted at mass flux of $35.5{\sim}210.4\;kg/m^2s$ and cooling capacity of $0.95{\sim}10.1\;kW$. The main results were summarized as follows : The average evaporation heat transfer coefficient of R-290 and R-600a was higher value than that of R-22. In comparison with R-22, the evaporation heat transfer coefficient of R-290 and 600a is approximately $56.7{\sim}70.1$ and $46.6{\sim}59.7%$ higher, respectively. In comparison with experimental data and some correlations, the evaporation heat transfer coefficients are well matched with the Kandlikar's correlation regardless of a type of refrigerants and tube diameters.

Performance Characteristics of Water-Chilling Heat Pump Using CO2 on Control of Inverter Frequency (인버터 주파수 제어에 따른 CO2용 수냉식 열펌프의 성능 특성)

  • Son, Chang-Hyo
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.11 no.12
    • /
    • pp.4721-4726
    • /
    • 2010
  • The performance characteristics of water-chilling heat pump using CO2 for the control of inverter frequency was investigated experimentally. An experimental apparatus is consisted of a compressor, a gas cooler, an expansion valve, an evaporator and a liquid receiver. All heat exchangers used in the test rig are counter flow type heat exchangers with concentric dual tubes, which are made of copper. The gas cooler and the evaporator consist of 6 and 4 straight sections respectively arranged in parallel, each has 2.4m length. The experimental results summarize as the following: for constant inlet temperature of evaporator and gas cooler, as mass flow rate, compression ratio and discharge pressure increases with the inverter frequency. And heating capacity and compressor work increases, but coefficient of performance(COP) decreases with the inverter frequency of compressor. As inlet temperature of secondary fluid in the evaporator increases from $15^{\circ}C$ to $25^{\circ}C$, compression ratio and compressor work decreases, but mass flow rate, heating capacity and COP increases with the inverter frequency of compressor. The above tendency is similar with performance variation with respect to the variation of inverter frequency in the conventional vapor compression refrigeration cycle.

Performance analysis of a cold-air forced circulation type showcase (냉기 강제순환형 공랭식 쇼케이스 성능 해석)

  • Kim, Jeong-Sik;Kim, Nae-Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.14 no.3
    • /
    • pp.1003-1010
    • /
    • 2013
  • In this study, a simulation program was developed, which predicts the performance of cold-air forced circulation type air cooled showcase. The showcase has an excellent display effect in addition to preserving the grocery. In the program, the compressor was analyzed using performance data supplied by the manufacturer and the capillary tube pressure drop was analyzed using a homogeneous model. The evaporator and condenser were analyzed by dividing the heat exchangers into small elements, where energy balance and appropriate heat transfer correlations were used. A showcase model with two 3/4 HP compressors, capillary tubes of 1.6 mm inner diameter, a fin-and-tube evaporator and condenser was tested, and the results are compared with the predicted values. It is shown that both evaporation and condensation temperatures are adequately predicted by the program.

Simulation on the performance of an automobile climate control system with Internal heat exchanger and TXV (내부열교환기와 TXV를 적용한 자동차용 공조시스템의 성능에 관한 수치적 연구)

  • Park, Cha-Sik
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.22 no.1
    • /
    • pp.31-36
    • /
    • 2021
  • Recently, automobile air conditioning systems have applied an alternative refrigerant that can replace the high GWP refrigerant R134a due to the global warming problem. This study simulated the performance of an automobile climate control system with an internal heat exchanger and TXV. Refrigerant R1234yf was applied as the working fluid. Amesim, a commercial software program, was used to model the main components of the compressor, condenser, TXV, evaporator, and internal heat exchanger. As the outside temperature increased from 30℃ to 40℃, the cooling capacity of the system decreased by 3.1%, and the power consumption of the compressor increased by 17.1%. In addition, The performance characteristics of the refrigeration cycle were simulated by increasing the fin pitch of the condenser from 0.8 mm to 1.4 mm. When the fin pitch was larger than 1.0 mm, the condenser capacity decreased, and the system COP was lowered by 5.9%. When the fin pitch of the condenser was 0.8 mm, which was smaller than 1.0 mm, there was no significant change in the system performance. Hence, the optimal performance was observed at a fin pitch of 1.0 mm.