An Elimination Method Of the Circulating Current Flowing into Coaxial-Neutral Lines in 22.9[kV] CNCV Underground Cable Systems (22.9[kV] 지중배전계통케이블의 동심중성선에 흐르는 순환전류의 제거방안 및 효과)

  • Jeon, Myung-Su;Song, Joong-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.2
    • /
    • pp.107-113
    • /
    • 2008
  • In 22.9[kV]-y distribution systems, underground cables are provided with multiple-point ground in which each coaxial-neutral line of the distribution cable lines(A, B, C phases) is 3-wire common grounded. In the underground cable distribution systems, circulating current flows in the coaxial-neutral lines and its magnitude amounts to about $40{\sim}50[%]$ load currents, even though loads are balanced. Power loss due to the circulating current consequently reaches to about 76[%] total losses occurred in all conductor lines. This power loss provokes additional temperature rise of the underground cable lines and finally results in 20[%] reduction of the current capacity of the cables. This paper presents a new ground method to overcome such a problem. The proposed method eliminates the circulating current flowing in the coaxial-neutral line effectively. Measurement results confirmed from the practical site-test show validity and effectiveness of this research.

A Study on the Effective Surge Protection Method from Induced Lightning Surgeto Improve Isolate Grounding to Common Grounding (낙뢰 Surge 방호를 위한, 독립접지를 공통접지로 개선하는 효율적인 방법에 대한 연구)

  • Jeon, Hyung-Gu;Woo, Jea-Wook;Suh, Yong-Joon
    • Proceedings of the KSR Conference
    • /
    • 2011.10a
    • /
    • pp.1459-1467
    • /
    • 2011
  • This paper proposes the effective method to improve the protection from induced lightning Surge by making common grounding from individual grounding. Common grounding under equipotential principle is more effective than individual grounding for lightning Surge protection, and so common grounding is indicated as international technical standard under the AC power supply system with neutral line. So, this paper is to propose the effective way of induced lightning Surge protection method for currently installed power supply system which has no neutral grounded line and individual grounding which are weak for lightning Surge protection. This proposal can improve the power supply system as has neutral line, and improve the grounding system to common grounding system. And also this paper proposes to make effective equipotential system with voltage variable shunting devices for lightning Surge protection.

  • PDF

A Study on the Equivalent Circuit Modeling for Harmonics Analysis by Field Tests (현장시험에 의한 고조파 해석용 등가회로 모델링에 관한 연구)

  • 김경철;최종기;백승현;김종욱
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.4
    • /
    • pp.60-67
    • /
    • 2004
  • With the proliferation of nonlinear loads, high neutral harmonic currents in three-phase four-wire distribution system have been observed It has been also known that the ground impedance has an effect on the neutral currents of a system which operates with harmonics present. On-site measurements of harmonic currents and voltages, and the soil resistivity and ground resistance under case study system were made and the corresponding equivalent circuit for the harmonics analysis was developed This equivalent circuit model was simulated numerically and graphically through the use of MATLAB and CDEGS software packages, and adequate results were obtained.

electrical shock accident prevention method and risk assesment as grounding type on the low-voltage handhole using PSCAD/EMTDC (PSCAD/EMTDC를 이용한 지중함 접지방법에 따른 전격위험성 평가와 감전사고 예방대책)

  • Han, Woon-Ki;Kim, Jong-Min;Bang, Sun-Bae;Jung, Jin-Soo;Jung, Jong-Woo;Lee, Jun
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.2204-2205
    • /
    • 2008
  • 2005년도에 저압 지중함에서 감전사고가 발생한 후 감전예방을 위한 다양한 개선대책이 현장에 적용되었다. 사고발생 직후에는 지중전선의 접속부에 테이핑처리에 의한 보완조치가 적용되었으며, 그 이후 전선 접속 부를 방수형접속재로 교체하는 작업이 시행되었으며 전선 접속부 위를 감전방지용 절연고무판으로 덮거나 차량의 통행이 없는 일부 지중함의 뚜껑을 절연재질인 고강도플라스틱(FRP)으로 교체하거나 그 이외에 다중접지된 중성선과 지중함의 틀을 본딩하는 개선대책 등이 현장에 적용되었다. 이러한 다양한 개선대책은 지중함에서의 감전사고를 예방하기 위한 것으로 그중 틀접지는 이미 적용된 지중함 내의 접지설비와 중성선이 공통접속된 상태에서 지중함과 맞닿는 틀에 접지도체를 연결하는 것이다. 계통의 중성선을 이용한(TN-C)방식의 틀접지는 효과가 있으나 뚜껑부분의 진동방지를 위하여 삽입한 고무패킹은 성능저하를 일으키므로 그에 대한 대책이 필요하였다.

  • PDF

Substation Grounding Performance Evaluation by Ground Current Measurement (지락전류 분류계수 측정에 의한 변전소 접지성능 진단)

  • Choi Jong kee;Ahn Yong Ho;Ryu Hee Young;Jung Gil Jo;Lee Bong Hee;Han Byung Sung;Kim Kyung Cheol
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.594-596
    • /
    • 2004
  • 부식이나 경년열화 등으로 인한 변전소 접지성능 저하에 대한 대책마련을 위하여 정기적인 변전소 접지저항의 측정은 필수적이라고 한 수 있다 그러나 단지 접지저항의 측정을 위하여 변전소 접지망과 연결되어 있는 외부접지계통, 즉 배전 중성선이나 송전선로 가공지선의 다중접지계통을 분리한다는 것은 현실적으로 불가능한 작업이다. 본 논문에서는 접지시험을 위한 시험전류를 주입하고 가공지선 및 중성선으로의 분류계수를 측정함으로써 운전 중인 상태에서 변전소 접지망 단독의 접지저항을 측정하는 시스템, 측정기법 및 사례연구를 제 시 하였다.

  • PDF

배전산업의 현대화 22.9kV-y 다중접지 배전방식의 도입

  • 황원서
    • 전기의세계
    • /
    • v.46 no.7
    • /
    • pp.25-27
    • /
    • 1997
  • 우리나라 배전전압은 1917년 경성전기주식회사가 표준 배전전압으로 3.3kV를 채택한 이래 1960년대 중반까지는 3.3kV, 5.7kV-y, 6.6kV이었다. 1965년 10월, 경북 칠곡군 약목변전소 관내의 당시 박정희 대통령 생가 인근을 통과하는 22kV 비접지 송전선로 9km에 다중접지된 중성선을 추가시설, 3상 4선식 배전선로화하여 4개부락 40kV의 부하를 공급함으로써 우리나라에 22.9kV-y 중성선 다중접지 배전방식 도입의 효시가 된 이래, '22.9kV-y승압'사업은 1970년부터 1986년까지 한전의 배전분야 최우선사업으로 전국 방방곡곡에 걸쳐 시행되었다. 이제는 서울 일부와 제주도에서만 시행중으로 종료단계인 오늘에 이르기까지, '22.9kV-y승압'은 한전의 본사와 전국의 사업장에서 수많은 배전분야 종사자들이 총력을 기울여 이룩한 세계 전력 산업사에 그 유례가 드문 격상에 의한 배전전압 단일화 사업으로써, 배전사업 현대화의 중심사업이었다 하지 않을 수 없다.

  • PDF

An Experimental Study on the Response of Concrete Pole to Impulsive Current (콘크리트전주의 임펄스전류 응답에 대한 실험적 고찰)

  • Park, Sang-Man;Kang, Moon-Ho;Jeong, Yeong-Ho;Ryoo, Hee-Suk;Nam, Kee-Young;Lee, Jae-Duck;Jung, Dong-Hak
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.482-484
    • /
    • 2003
  • 특별고압 가공배전선로는 일반적으로 콘크리트전주를 지지물로 하고 있고, 선로의 상부에는 가공지선을, 하부에는 중성선을 설치하되, 매전주에서 가공지선, 중성선, 완철을 서로 접속하고 적절한 경간마다 전주에서 접지하도록 하고 있다. 또한 콘크리트전주는 기계적 강도의 유지를 위하여 철근이나 강선을 주골재로 사용하면서도 설계기준에서는 콘크리트전주의 뇌격에 대한 접지효과를 고려하지 않고 있는데, 실험에 의해, 접지선에 어느 정도 이상의 임펄스전류가 흐르면 전주의 철근이 접지회로의 일부를 구성하는 것으로 확인되었다. 본 논문에서는 콘크리트전주의 뇌임펄스에 대한 응답을 실험적으로 고찰하였다.