• 제목/요약/키워드: 제연기 압력비

검색결과 2건 처리시간 0.018초

제연기 개스유동 해석에 관한 연구 (A Study of Bore Evacuator Gas Flow Analysis)

  • 강국정
    • 한국정밀공학회:학술대회논문집
    • /
    • 한국정밀공학회 1996년도 추계학술대회 논문집
    • /
    • pp.1083-1087
    • /
    • 1996
  • Bore evacuator which have circular structure of cylindrical form is located at tube, and its function is to evacuate toxic gases generated during firing intervals. Between bore evacuator and bore interior, gas flow field is developed through the nozzles, and the charging and discharging process is formed. By these flow cycle(charging and discharging) the evacuation effect can be generated. This report contains an analyses and results consideration about bore evacuator flowfield.

  • PDF

초고층 건축물에서 엘리베이터 구동이 부속실과 화재실 간 차압형성에 미치는 영향연구 (The Study on the Effect of Elevator Movement on the Pressure Difference between Vestibule and Living room in High-rise Buildings)

  • 박영기;홍기배;유홍선
    • 한국산학기술학회논문지
    • /
    • 제19권1호
    • /
    • pp.85-91
    • /
    • 2018
  • 최근 초고층 건축물에서 화재로 인해 많은 인명피해가 발생하고 있다. 특히, 화재 발생시 생성되는 유독성 가스 및 연기로 인해 많은 사망자가 발생하고 있다. 이러한 인명피해를 줄이기 위한 방안으로 제연시스템이 도입되어 있다. 제연시스템은 초고층 건축물에서 연기의 확산을 방지하고 재실자의 안전한 피난을 도와주는 장치이다. 또한, 엘리베이터를 이용한 피난은 초고층 건축물에서 필수적인 피난 방법으로 여겨진다. 하지만, 엘리베이터 구동시 생성되는 강력한 압력장 및 유동변화로 인해 제연시스템의 성능확보에 영향을 미친다. 따라서, 본 연구에서는 성능설계위주의 샌드위치 가압방식이 적용된 초고층 건축물에서 엘리베이터 구동에 따른 제연성능 확보에 미치는 영향을 실험 및 수치해석 연구로 수행하였다. 실제 초고층 건축물에서 발생되는 창문, 방화문 그리고 엘리베이터의 누설면적은 화재안전기준 및 면적비를 이용하여 산출하였다. 실제 엘리베이터 속도 7 m/s~17 m/s에 해당하는 20 m/s~100 m/s로 동역학적 상사를 통해 엘리베이터 속도를 변경하였다. 그 결과 엘리베이터 속도가 빠르면 빠를수록 부속실과 화재실 간 차압이 크게 발생하였으며 관계식은 ${\Delta}P=40{\cdot}{\exp}$(-Ves /-104.7)-23.735로 산출되었다. 본 연구 결과는 초고층 건축물에서 엘리베이터 구동을 고려한 제연시스템 설계 자료로 활용이 가능하다.