• Title/Summary/Keyword: 전자 팽창밸브

Search Result 60, Processing Time 0.025 seconds

An Experimental Study on the Optimal Intermediate Pressure of a 2-Stage Compression Heat Pump Using River Water (하천수 열원 2단압축 열펌프의 최적 중간압에 관한 실험적 연구)

  • Park, Cha-Sik;Jung, Tae-Hun;Joo, Young-Ju;Kim, Yong-Chan
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.6
    • /
    • pp.333-339
    • /
    • 2009
  • The objective of this study is to predict optimal intermediate pressure of a 2-stage compression heat pump system using river water. To determine the maximum performance of the 2-stage compression heat pump system, the experimental evaluations on the 2-stage compression cycle were carried out under various operating conditions. Electronic expansion valves were applied to control intermediate pressure and superheat. Based on the experimental data, an empirical correlation for predicting optimal intermediate pressure which considering cycle operating parameters was developed. The present correlation was verified by comparing the predicted data with the measured data. The predictions showed a good agreement with the measured data within a relative deviation of ${\pm}4%$ at various operating conditions.

Cooling and Heating Performances of a CO2 Heat Pump with the Variations of Operating Conditions (운전조건 변화에 따른 이산화탄소 열펌프의 냉난방 성능특성 비교)

  • Cho, Hong-Hyun;Baek, Chang-Hyun;Lee, Eung-Chan;Kang, Hun;Kim, Yong-Chan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.32 no.6
    • /
    • pp.454-462
    • /
    • 2008
  • Since operating conditions are significantly different for heating and cooling mode operations in a $CO_2$ heat pump system, it is difficult to optimize the performance of the $CO_2$ cycle. In addition, the performance of a $CO_2$ heat pump is very sensitive to outdoor temperature and gascooler pressure. In this study, the cooling and heating performances of a variable speed $CO_2$ heat pump with a twin-rotary compressor were measured and analyzed with the variations of EEV opening and compressor frequency. As a result, the cooling and heating COPs were 2.3 and 3.0, respectively, when the EEV opening was 22%. When the optimal EEV openings for heating and cooling were 28% and 16%, the cooling and heating COPs increased by 3.3% and 3.9%, respectively, over the COPs at the EEV opening of 22%. Beside, the heating performance was more sensitive to EEV opening than the cooling performance. As the compressor speed decreased by 5 Hz, the cooling COP increased by 2%, while the heating COP decreased by 8%.

Experimental Study on the Heating Performance Improvement of R134a Heat Pump System for Zero Emission Vehicles (무공해자동차용 R134a 히트펌프 시스템의 난방성능 향상에 관한 실험적 연구)

  • Lee, Dae-Woong
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.26 no.6
    • /
    • pp.257-262
    • /
    • 2014
  • This paper describes an experimental study for heating performance that can be used in R-134a automobile heat pump systems. The heat pump system is widely studied for heating system in zero-emission vehicles to attain both the small power consumption and the effective heating of the cabin. This paper presents the experimental results of the influence on heating capacity and coefficient of performance of heat pump system. Tests were performed with different sizes of internal and external heat exchangers, and refrigerant flow rate was also considered in two-way flow devices. In addition, the heat, air, and water sources with the heat pump system were examined. The experimental results with the heat pump system were used to analyze the impact on performances. The best combination of performance was A-inside heat exchanger, B-outside heat exchanger, and B-flow device, respectively. In addition, a water heat-source was found to give roughly 40% of better performance than an air heat-source heat pump system.

The Performance of Capacity Modulation and MIMO Control for System Heat Pump (시스템 히트펌프의 용량조절 및 다변수 제어 특성에 관한 연구)

  • Song, In-Sik;Joo, Young-Ju;Chung, Hyun-Joon;Kang, Hoon;Kim, Yong-Chan;Choi, Jong-Min
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.364-369
    • /
    • 2007
  • A system heat pump provides the benefits of comfort, energy conservation and easy maintenance. Recently, the system heat pump has been employed in small and medium-sized buildings. However, the performance data and control algorithm for system heat pump are limited in literature due to complicated system parameters and operating conditions. In the present study, the performance of a system heat pump with two indoor unit is measured by varying indoor loads, EEV opening, and compressor speed. In addition, the integral optimum regulator which includes MIMO control algorithm is proposed. The capacity modulation and optimum capacity for each indoor unit can be adjusted by utilizing the EEVs opening and compressor speed. The proposed scheme shows appropriate control performance at test conditions.

  • PDF

Experimental Study of Adoption of Alternative Refrigerant for Avionic Equipment Cooling System (항공전자기기용 냉각시스템의 대체냉매 적용에 관한 실험적 연구)

  • Kang, Hoon;Jung, Jongho;Jung, Minwoo;Chi, Yongnam;Yoo, Yongseon;Choi, Heeju;Byeon, Youngman;Kim, Youngjin;Oh, Kwangyoon;Kim, Yongchan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.37 no.5
    • /
    • pp.431-439
    • /
    • 2013
  • A cooling system is adopted to control the thermal load from the avionic equipments in an aircraft for stable operation. In this study, an avionic cooling system was designed and manufactured by adopting a vapor compression cycle with a closed-loop air-circulation system to investigate the operating characteristics of an alternative refrigerant. The performance characteristics of a cooling system adopting R236fa as an alternative refrigerant were experimentally determined by varying the refrigerant charging amount, expansion valve opening, and compressor rotation speed. The experimental results were analyzed and compared with those of a cooling system adopting R124 as a refrigerant. The possibility of the adoption of R236fa as an alternative refrigerant was verified, and design solutions were suggested to improve the system efficiency.

Characteristics of Temperature Control by Hot-gas Bypass Flow Rate on Industrial Water Cooler (핫가스 바이패스 유량에 따른 산업용 냉각기의 온도제어 특성)

  • Baek, Seung-Moon;Choi, Jun-Hyuk;Byun, Jong-Yeong;Moon, Choon-Geun;Lee, Ho-Saeng;Jeong, Seok-Kwon;Yoon, Jung-In
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.33 no.8
    • /
    • pp.1129-1136
    • /
    • 2009
  • The paper presents the performance characteristics for a cooling system using EEV. The water cooler was used to reduce thermal deformation and contraction due to high speed of machine tools and the EEV was used for capacity control for water cooler. The apparatus was designed for hot-gas bypass system which a hot-gas can flows from outlet of compressor to the inlet of evaporator. This experiment is the intermediary study for precise temperature control through PID control. The results show that the evaporator pressure increased and refrigeration capacity decreased as the EEV opening step of hot-gas bypass increased. These results can be used as basic data for the design of effective water cooler.

Performance Analysis of a Multi-type Inverter Heat Pump (멀티형 인버터 열펌프의 냉방성능해석에 관한 연구)

  • Kim, Y. C.;Park, G. W.;Youn, Y.;Min, M. K.;Choi, Y, D,
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.3
    • /
    • pp.153-159
    • /
    • 2001
  • A system simulation program was developed for a multi-type inverter heat pump. Electronic expansion valve(EEV) was used to extend the capacity modulating range of the heat pump as expansion device. The program was also developed to calculate actual system performance with the building load variation with climate during a year. The performance variation of a multi-type hat pump with two EEV and an inverter compressor was simulated with compressor speed, capacity, and flow area of the EEV. As a result, the optimum operating frequency of the compressor and openings of the expansion device were decided at a given load. As compressor speed increased, he capacity of heat pump increased, the capacity of heat pump increased. Therefore flow area of EEV should be adjusted to have wide openness. Thus the coefficient of performance(COP) of the heat pump decreased due to increasement of compressor power input. The maximum COP point at a given load was decided according to the compressor speed. And under the given specific compressor speed and the load, the optimum openings point of EEV was also decided. Although the total load of indoor units was constant, the operating frequency increased as the fraction of load in a room increased. Finally ad the compressor power input increased, the coefficient of performance decreased.

  • PDF

A Study on a Precision Temperature Control of Oil Coolers with Hot-gas Bypass Manner for Machine Tools Based on Fuzzy Control (퍼지제어를 이용한 공작 기계용 오일 쿨러의 핫가스 바이패스방식 정밀 온도 제어에 관한 연구)

  • Lee, Sang-Yun
    • Journal of the Institute of Convergence Signal Processing
    • /
    • v.14 no.3
    • /
    • pp.205-211
    • /
    • 2013
  • Recently, the needs of system performances such as working speed and processing accuracy in machine tools have been increased. Especially, the working speed increment generates harmful heat at both moving part of the machine tools and handicrafts. The heat is a main drawback to progress accuracy of the processing. Hence, a oil cooler to control temperature is inevitable for the machine tools. In general, two representative control schemes, hot-gas bypass and variable speed control of a compressor, have been adopted in the oil cooler system. This paper deals with design and implementation method of fuzzy controller for obtaining precise temperature characteristic of HB oil cooler system in machine tools. The opening angle of an electronic expansion valve are controlled to keep reference value and room temperature of temperature at oil outlet. Especially, the fuzzy controller is added to suppress temperature fluctuation under abrupt disturbances. Through some experiments, the suggested method can control the target temperature within steady state error of ${\pm}0.22^{\circ}C$.

Experimental Study on the Heating Performance of a $CO_2$ Heat Pump Water Heater (이산화탄소 급탕 열펌프의 난방 성능에 관한 실험적 연구)

  • Baek, Chang-Hyun;Lee, Eung-Chan;Kang, Hoon;Kim, Yong-Chan;Cho, Hong-Hyun;Cho, Sung-Wook
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.310-315
    • /
    • 2008
  • In this study, experimental study on the heating performance of a $CO_2$ heat pump water heater with a variation of operating conditions such as refrigerant charge amount, outdoor temperature, compressor frequency, EEV opening and water mass flow rate. Based on the test results, the optimum charge amount was 1800 g. At the water mass flow rates of 75, 85, 95 kg/hr, the water heating temperature was 62, 67, $74^{\circ}C$ and COP was 2.6, 2.8, 3.0, respectively. Besides, the water mass flow rate and compressor frequency were varied to maintain above the water heating temperature of $60^{\circ}C$ with the decrease of outdoor temperature. So, The compressor frequency increased beyond 65 Hz and the water mass flow rate was 45 kg/hr at the outdoor temperature of $-13^{\circ}C$, 65 kg/hr at $-8^{\circ}C$, 75 kg/hr at $-3^{\circ}C$ and 85 kg/hr at 2, $7^{\circ}C$. As the outdoor temperature decreased, the heating COP decreased by 2.5-39.8%.

  • PDF

Precise Temperature Control of Oil Coolers with Hot-gas Bypass Manner for Machine Tools Based on PI and Feedforward Control (PI와 피드포워드 제어를 이용한 공작기계용 오일쿨러의 핫가스 바이패스 방식 정밀 온도 제어)

  • Jeong, Seok-Kwon;Byun, Jong-Yeong;Kim, Sang-Ho;Yoon, Jung-In
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.2
    • /
    • pp.111-119
    • /
    • 2011
  • Recently, the performances of speed and accuracy are enhanced in machine tools. The high speed of the machine tools usually causes harmful thermal displacements on the objects. To reduce the thermal displacements, machine tools generally adopt oil coolers with precise temperature control function. This study aims at precise control of oil outlet temperature in the oil coolers with hot-gas bypass manner based on PI control logic. The control system was designed for obtaining steady state error within ${\pm}0.1^{\circ}C$ and maximum overshoot with 0.8% even though abrupt disturbances are added to the system. We showed that the PI gains could be easily decided by numerical simulations using practical transfer function which got experiments. Also, transient characteristics could be improved significantly by reflecting the inlet temperature of an evaporator to the output of a controller feedforwardly considering periodic abrupt disturbances. Through some experiments, excellent control performances were established by the suggested control.