• 제목/요약/키워드: 전자식팽창밸브

검색결과 16건 처리시간 0.026초

온도식팽창밸브의 전자식팽창밸브로의 대체 가능성에 관한 연구 (A Study on the Possibility for the Replacement of a Thermal Expansion Valve to an Electronic Expansion Valve)

  • 한도영;정성욱
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.695-700
    • /
    • 2006
  • For the precise superheat temperature control of an air conditioner, an electronic expansion valve may be used instead of a thermal expansion valve. In this paper, technical and economical aspects of expansion valves were studied in order to find out the possibility to use an electronic expansion valve to replace a thermal expansion valve.

  • PDF

공조.냉동장치의 제어시스템 개발을 위한 팽창밸브 특성 (Expansion Valves Characteristics for Development of Control System on Air Conditioning and Refrigeration Systems)

  • 김재돌;장재은;윤정인
    • 동력기계공학회지
    • /
    • 제2권3호
    • /
    • pp.34-40
    • /
    • 1998
  • Performance characteristics of a refrigeration systems with various expansion valves and superheat changes were investigated experimentally. Experimental data have been taken utilizing three different devices; a thermostatic expansion valve, a linear type electronic expansion valve and a solenoid type electronic expansion valve. The data taken from tile three types of expansion valves were discussed with the temperature distribution of each zone in the evaporator and the superheat changes of the evaporator outlet In each zone temperature distribution fluctuated larger with the thermostatic expansion valve than with the electronic expansion valves. The optimum superheat ranged from $5^{\circ}C\;to\;15^{\circ}C$, and the superheat with the thermostatic expansion valve showed hunting phenomenon, which affected the evaporating and condensing temperature.

  • PDF

전자(電子) 팽창밸브를 이용(利用)한 증발기(蒸發器)의 냉매(冷媒) 流量(유량) 제어(制御) 및 과열도(過熱度) 특성(特性)에 관한 연구(硏究) (Study on Control of Refrigerant Flow Rate and Characteristics of Superheat in Evaporator using Electronic Expansion Valve)

  • 최순오;김정훈;양현석;김종수
    • 설비공학논문집
    • /
    • 제6권4호
    • /
    • pp.380-387
    • /
    • 1994
  • An experimental study was performed to investigate the characteristics of refrigerant flow rate control and superheat in an evaporator with an electronic expansion valve(EEV). The EEV used in this study was devised using a needle valve coupled with a stepping motor controlled by a personal computer. A Pill control equation was used to control the superheat of the evaporator and to set the superheat to $5^{\circ}C$. In order to determine an optimum running condition for the system, Pill parameters were varied for the wide range of values. The running condition of an air conditioning system with a PI control was reasonably stable compared with that of the Pill control. Experimental results for the PI control using parameter values, $K_p=1.5$, $T_i=400(sec)$ and $T_s=6(sec)$ show that the superheat reached its target value. When external disturbances were introduced to the system, the superheat target value was reached within about 3 minutes. When the EEV was applied to the air conditioning system driven by an inverter, room temperature control was excellent.

  • PDF

멸티형 공조/냉동시스템의 증발기 과열도 제어 (Evaporator Superheat Control of a Multi-type Air-Conditioning/Refrigeration System)

  • 김태섭;홍금식;손현철
    • 에너지공학
    • /
    • 제10권3호
    • /
    • pp.253-265
    • /
    • 2001
  • 본 논문은 멀티형 공조/냉동시스템의 증발기의 과열도(증발기 2상영역과 출구영역의 냉매기 온도차)제어를 위한 모델링과 PI제어에 관한 연구이다. 먼저, 제어기 설계를 목적으로 하여 압축기, 응축기, 증발기 그리고 전자식 팽창밸브의 동특성이 수학적으로 모델링된다. 증발기에서의 일정한 크기의 과열도 발생을 제어목적으로 한정한 후 전자식 팽창밸브의 전류입력으로부터 증발기의 2상영역과 과열영역에서의 관벽의 온도로의 전달함수들이 유도된다. 비례적분 제어기의 폐루프시스템의 안정성과 제어성능은 Nyquist 안정성 판별법에 의해 분석된다. 시뮬레이션 결과가 제시된다.

  • PDF

R22를 적용한 전자팽창밸브의 냉매유량 특성 및 유량예측 모델링 (Mass Flow Characteristics and Empirical Modeling of R22 Flowing through Electronic Expansion Valves)

  • 박차식;이선일;김용찬;이영수
    • 설비공학논문집
    • /
    • 제18권11호
    • /
    • pp.881-887
    • /
    • 2006
  • The objective of this study are to analyze the flow characteristics of R22 flowing through EEVs and to develop an empirical correlation to predict the refrigerant flow rate. The mass flow rates of EEVs with different geometries were measured at various condensing temperatures, subcoolings, and EEV openings. Based on the experimental data, an empirical correlation for mass flow predictions in EEVs was developed by modifying the orifice equation. The correlation showed good agreement with the measured data for R22 with average and standard deviations of 1.4% and 6.1%, respectively. Approximately 90% of the measured data were within ${\pm}10%$ of the predictions.

증발기 과열도제어에 따른 냉동장치의 동특성에 관한 연구 (A Study on Dynamic Characteristics of a Refrigeration System by Controlling the Evaporator Superheat)

  • 김재돌;오후규;윤정인
    • 대한기계학회논문집
    • /
    • 제19권8호
    • /
    • pp.2012-2021
    • /
    • 1995
  • An experimental study was performed for the analysis of dynamic characteristics of refrigeration system by controlling the evaporator superheat. Experimental data have been taken utilizing two different devices, thermostatic expansion valve(T.E.V.) and electronic expansion valve(E.E.V.), for the control of the evaporator superheat. The ranges of parameters, such as superheat, mass flow rate of refrigerant and inlet temperature of evaporator were 5-30.deg. C 90-170 kg/h and 10-25.deg. C, respectively. The data taken from the T.E.v.and E.E.v.were discussed with the control of the superheat, pressure drop, refrigerating capacity, compression work, evaporating temperature, condensing temperature and COP affecting performance characteristics of refrigeration system. In case of the refrigerant flow control with T.E..V., the superheat and pressure drop of the evaporator varied periodically, but the control with E.E.V., the parameters were very stable. In E.E.v.control, refrigerating capacity, compression work and evaporating temperature were decreased with increasing superheat, and the highest COP was obtained in the range of superheat from 5.deg. C to 15.deg. C.

반도체 공정용 칠러의 채널별 제어특성에 관한 실험적 연구 (Experimental Study on the Control Characteristics of Each Channel in a Semiconductor Chiller)

  • 김현중;권오경;차동안;김용찬
    • 대한기계학회논문집B
    • /
    • 제35권12호
    • /
    • pp.1285-1292
    • /
    • 2011
  • 본 연구에서는 전자식 팽창밸브를 적용한 반도체 공정용 칠러에 관한 실험적 연구를 통해 시스템 특성을 파악하였다. 또한 온도 변화에 따른 신속한 대응을 할 수 있도록 온도상승 및 하강실험, 부하변화에 따른 온도영역별 제어정밀도 실험을 함으로써 각 제어 방식에 따른 운전 특성을 파악하였다. 온도상승 시 소비전력은 8.9 kW로 측정되었으며 CH1이 37.5분, CH2가 39.5분이 소요되었으며, 온도하강에는 총 26.5분이 소요되었다. 부분부하가 적용되는 경우 전부하가 적용되는 경우에 비해 제어정밀도의 변화폭이 큰 것으로 나타났으며 스텝모터 구동방식을 적용한 CH2의 제어정밀도가 상대적으로 우수한 것으로 나타났다. 냉각수를 이용한 냉각사이클 영역에서 소비전력은 1.8 kW로 냉동사이클을 적용한 방식에 비해 절반가량으로 감소된 것으로 나타났다. 본 연구는 실험결과를 바탕으로 반도체 공정용 칠러의 최적제어방안을 제시하였다.

노즐 팽창장치를 적용한 냉동시스템의 성능에 관한 실험적 연구 (An Experimental study on the Performance of a Refrigeration System using Nozzles as Expansion Devices)

  • 박윤철;고광수
    • 한국지열·수열에너지학회논문집
    • /
    • 제20권1호
    • /
    • pp.1-7
    • /
    • 2024
  • To In this study, a nozzle which is designed to work as expansion device was installed in a refrigeration system and performance test was conducted. The nozzle has 0.8mm, 1.0mm, 1.2mm diameter and inserted in a body of the devices. System performance was compared with a electronic expansion device(EEV, electric expansion valve) and designed nozzles at the environmental conditions such as dry bulb and wet bulb temperature. To reduce energy loss in the evaporator, a nozzle was inserted into the evaporator. In the comparison test, the opening of the EEV was adjusted to the same diameter as the 3 nozzles, and the experiments conducted at a 27℃ dry bulb temperature and 19.5℃ wet bulb temperature with 50% relative humidity as defined at KS C 9306 standard. To find out the effect of the environmental condition, the bulb temperature was varied 5 degree lower and higher than the standard condition temperature with the same relative humidity condition at 50%. The air flow rate to the evaporator was also changed 4, 7 and 10 m3/min. As results, the temperature drop in the nozzle was 153% higher than that of the EEV and the enhancement of the performance(COP) was up to 125.7% if install the nozzles in the refrigeration system. The highest performance was obatained at 1.0mm diameter nozzle.