• Title/Summary/Keyword: 이산화탄소 냉동시스템

Search Result 29, Processing Time 0.03 seconds

Prediction on Maximum Performance of Cascade Refrigeration System Using R717 and R744 (R718-R744용 캐스케이드 냉동시스템의 최대 성능 예측)

  • Roh, Geun-Sang;Son, Chang-Hyo
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.10 no.10
    • /
    • pp.2565-2571
    • /
    • 2009
  • In this paper, cycle performance analysis of cascade refrigeration system using $NH_3-CO_2$(R717-R744) is presented to offer the basic design data for the operating parameters of the system. The operating parameters considered in this study include subcooling and superheating degree and condensing and evaporating temperature in the ammonia(R717) high temperature cycle and the carbon dioxide low temperature cycle. The COP of cascade refrigeration system increases with the increasing superheating degree, but decreases with the increasing subcooling degree. The COP of cascade refrigeration system increases with the increasing condensing temperature, but decreases with the increasing evaporating temperature. Therefore, superheating and subcoolng degree, evaporating and condensing temperature of cascade refrigeration system using $NH_3-CO_2$ have an effect on the COP of this system. A multilinear regression analysis was employed in terms of subcooling, superheating, evaporating, condensing, and cascade heat exchanger temperature difference in order to develop mathematical expressions for maximum COP and an optimum evaporating temperature.

Performance analysis of R404A refrigeration system using R744 as secondary refrigerant (R744를 2차냉매로 사용하는 R404A용 냉동시스템의 성능 분석)

  • Oh, H.K.;Son, C.H.
    • Journal of Power System Engineering
    • /
    • v.16 no.2
    • /
    • pp.24-29
    • /
    • 2012
  • In this paper, an analysis on performance and exergy of R404A refrigeration system using R744 secondary refrigerant was performed numerically to optimize the design for the operating parameters. The operating parameters considered in this study include subcooling and superheating degree, internal heat exchanger and compression efficiency, evaporation and condensation temperature in the R404A refrigeration cycle and temperature difference of cascade heat exchanger. The main results are summarized as follows : The COP(coefficient of performance) of R404A refrigeration system increases with increasing evaporation temperature. The evaporation capacity of R744 as secondary refrigerant increases with the increase in evaporation pressure of R744 secondary refrigeration. And the enthalpy in the evaporator outlet of R744 increases with the increasing evaporation pressure of R744 secondary refrigeration. Therefore, it is important to analysis for the relationship between COP of R404A refrigeration system and refrigeration capacity of R744. As cascade evaporation temperature increase, the exergy loss of condenser and compressor using R404A is the largest among all components. Therefore, the exergy loss in the condenser and compressor using R404A must be decreased to enhance the COP of R404A refrigeration system with R744 secondary refrigerant.

Performance Evaluation of $CO_2$ Air-Conditioning System (이산화탄소를 사용하는 냉동 시스템의 성능 평가 (I))

  • 신지영
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.24 no.2
    • /
    • pp.24-30
    • /
    • 2000
  • The high-pressure natural refrigerant $CO_2$ is now being evaluated for use in the motor vehicle air-conditioning systems and for several types of unitary equipment. In this study thermodynamic properties of $CO_2$ is compared to those of R-22 and R-134a and the performance characteristics of $CO_2$ refrigeration cycle is analyzed. The results show that the optimum discharge pressure for the cycle performance exists. New design concept for the $CO_2$ refrigeration system should be developed due to the high-operating pressure of itself.

  • PDF

An Experimental Study on PAG Oil Separation Characteristics of an Oil Separator for a $CO_2$ Refrigeration system ($CO_2$ 냉동시스템의 오일 분리기에서 PAG오일 분리 특성에 관한 실험적 연구)

  • Cho, Eun-Young;Lee, Sung-Kwang;Kang, Byung-Ha;Kim, Suk-Hyun
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.271-276
    • /
    • 2008
  • The oil trap in oil separator is one of the most important characteristics for normal operation of compressor. In this study, oil separation characteristics has been investigated for $CO_2$/PAG mixture using a gravity type of oil separator. The experimental study has been carried out in the range of oil concentration 0 to 5 weight-percent and the mixture temperature range of $0^{\circ}C$ to $15^{\circ}C$. The results obtained indicate that oil separation ratio in oil separator is increased with an increase in the oil concentration and mixture temperature.

  • PDF

Performance Variation with Length of Internal Heat Exchanger in CO2 Cooling Cycle Using an Ejector (이젝터를 적용한 이산화탄소 냉동사이클의 내부열교환기 길이에 따른 성능 변화)

  • Kang, Byun;Cho, Hong-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.2
    • /
    • pp.147-154
    • /
    • 2012
  • Recently, many researchers have studied the performance of the transcritical $CO_2$ refrigeration cycle in order to improve the system efficiency. In this study, the length of IHX in the $CO_2$ ejector cycle was varied so as to evaluate the performance improvement. As a result, compressor work and cooling capacity was increased by 3% and 5% as the length of internal heat exchanger was changed from 3 m to 15 m. The best COP was appeared at internal heat exchanger length of 12 m, and it was 3.01. Besides, the length of internal heat exchanger has a big effect to pressure lift ratio and entrainment ratio in the ejector $CO_2$ cycle and it may be changed with operating conditions and system specifications.

Next generation absorption technologies in USA and Japan(2) - Next generations technologies in Japan - (미국 및 일본의 차세대 홉수식 열펌프 기술(2) - 일본의 차세대 흡수식 연구동향 -)

  • 강용태
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.28 no.4
    • /
    • pp.300-314
    • /
    • 1999
  • 가스구동 흡수식 시스템은 인류와 환경에 여러 가지 유익을 가져다준다. 첫째, 시스템의 고효율에 따른 매력적인 경제성을 제공하고, 둘째 천연가스의 사용으로 인하여 여름철 피크 전력소요(peak electric demand)를 완화하고, 셋째 이산화탄소 ($CO_2$)의 발생을 감소시킴으로써 지구 온난화 현상을 완화한다 실제로 가스구동 흡수식 시스템으로부터의 $CO_2$발생량은 증기보일러를 사용하는 전기구동 냉동기에 비하여 85% 수준인 것으로 보고되었다(Suzuki 등). 넷째로 암모니아 및 물과 같은 환경 친화적인 냉매들을 사용함으로서 오존층을 파괴하는 Chlorofluorocarbon(CFC) 및 Hydrochlorofluorocarbon(FCFC)계 냉매들을 대체할 수 있는 이점이 있다.

  • PDF

An Experimental Study on PAG and POE Oils Return in $CO_2$ Evporator Model ($CO_2$ 냉동시스템 증발기에서 PAG 및 POE 오일 회수에 관한 실험적 연구)

  • Lee, Sung-Kwang;Kang, Byung-Ha;Kim, Suk-Hyun
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.646-651
    • /
    • 2007
  • This study has been conducted to select the suitable refrigeration oil for a $CO_2$ refrigeration system. The oil return is one of the most important characteristics for refrigeration oils. PAG and POE oils are considered as a test fluids in this study. An evaporator model is employed to simulate the evaporator of a $CO_2$ refrigeration system. Oil return characteristics has been investigated for $CO_2$/PAG and $CO_2$/POE mixtures in the range of oil concentration 0 to 5 weight-percent and the mixture temperature range of $0^{\circ}C$ to $15^{\circ}C$. The results obtained indicate that oil return is decreased with an increase in the oil concentration and mixture temperature for both POE and PAG oils. It is also found that POE oil is seen to be superior than PAG oil in terms of oil return in an evaporator of a $CO_2$ refrigeration system.

  • PDF

Comparison of Performance in CO2 Cooling System with an Ejector for Various Operating Conditions (다양한 운전조건에서 이젝터를 적용한 CO2 냉동기의 성능비교)

  • Kang, Byun;Cho, Hong-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.7
    • /
    • pp.505-512
    • /
    • 2011
  • Recently, many researchers have analyzed the performance of the transcritical $CO_2$ refrigeration cycle in order to identify opportunities to improve the system energy efficiency. The reduction of the expansion process losses is one of the key issues to improve the efficiency of the transcritical $CO_2$ refrigeration cycle. In this study, the analytical study on the performance characteristics of $CO_2$ cycle with an ejector carried out with a variation of outdoor temperature, gascooler inlet air velocity, evaporator inlet air velocity, and evaporator inlet air temperature. As a result, the system performance could be improved over 85% by using an ejector for various operating condition because of the reduction of compressor work. Moreover, the cooling capacity increased about 18% for variable outdoor condition. Therefore, the high performance of an ejector system could be maintained for wide operating conditions and system reliability could be improved compared to that of a basic system.

Performance Analysis of a Carbon Dioxide(R744) Two-Stage Compression and One-Stage Expansion Refrigeration Cycle ($CO_2$용 2단압축 1단팽창 냉동 사이클의 성능 분석)

  • Roh, G.S.;Son, C.H.
    • Journal of Power System Engineering
    • /
    • v.13 no.6
    • /
    • pp.70-75
    • /
    • 2009
  • In this paper, cycle performance analysis of R744($CO_2$) two-stage compression and one-stage expansion refrigeration system is presented to offer the basic design data for the operating parameters of the system. The operating parameters considered in this study include superheating degree, compressor efficiency, gas cooling pressure, mass flowrate ratio, outlet temperature of gas cooler and evaporating temperature in the carbon dioxide two-stage refrigeration cycle. The main results were summarized as follows : The cooling capacity of two-stage compression and one-stage expansion refrigeration system increases with the increasing superheating degree, compressor efficiency and gas cooling pressure, but decreases with the increasing mass flowrate ratio and evaporating temperature. The compression work of two-stage compression and one-stage expansion refrigeration system increases with the increasing superheating degree, outlet temperature of gas cooler, gas cooling pressure and evaporating temperature, but decreases with the increasing compressor efficiency and mass flowrate ratio. The COP of two-stage compression and one-stage expansion refrigeration system increases with the increasing compressor efficiency, but decreases with the increasing superheating degree, gas cooling pressure, mass flowrate ratio and evaporating temperature. Therefore, superheating degree, compressor efficiency, gas cooling pressure, mass flowrate ratio, outlet temperature of gas cooler and evaporating temperature of R744($CO_2$) two-stage compression and one-stage expansion refrigeration system have an effect on the cooling capacity, compressor work and COP of this system.