Degradation properties of ZnO surge arrester due to lightning impulse current (뇌임펄스 전류에 의한 ZnO 배전용 피뢰기의 열화특성)

  • Lee, Seung-Ju;Lee, Bok-Hee;Lee, Su-Bong;Kim, Dong-Soung;Shin, Hee-Kyung;Jung, Dong-Cheol
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1305-1306
    • /
    • 2008
  • In this work, in order to investigate the effect of lightning impulse currents on ZnO surge arrester. and the deterioration characteristics of ZnO surge arrester, 8/20 [${\mu}s$], 2.5 [kA] impulse currents were applied to the ZnO surge arrester under test. The leakage currents of ZnO surge arrester were measured and ZnO element was analyzed by X-ray photoelectron spectroscopy. As a result, the resistive leakage current of ZnO surge arrester was increased with the injection number of lightning impulse currents.

  • PDF

A measuring Method of Ground Resistance for Energized Power Systems (운전중인 전력설비의 접지저항 측정방법)

  • 이복희;김성원;엄주홍;이승칠
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.77-81
    • /
    • 2000
  • The purpose of this paper is to describe a new measuring method of ground resistance for the grounding system in energized power equipment and substations. It is very difficult to measure the accurate ground resistance in energized power equipment and substations because of the noise conducted from all external connections to the grounding system and harmonics components caused by unbalanced loads and overloads. The ground resistance that is measured with existing methods includes not only the effect of desired signals but also noise components for the measurement period in grounding system. The measured value of ground resistance can entirely be different from actual value. In this paper, to eliminate 60[Hz] power system interference and harmonic components the low-pass filter method was used in the measurement of ground resistance.

  • PDF

Frequency Dependent Grounding Impedance As a Function of Soil Resistivity (대지저항률에 따른 접지임피던스의 주파수 의존성)

  • Bae, Sung-Bae;Choi, Jong-Hyuk;Park, Geon-Hun;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.57-60
    • /
    • 2008
  • A design criterion of grounding systems is commonly based on low frequency resistance in Korea. When lightning surges which have high frequency components are injected into the grounding system, the grounding impedance is greatly different from the static grounding resistance. This paper presents the grounding adimittance and phase on the frequency range from 100 [Hz] to 15 [MHz] using water tank simulating the grounding system in different water resistivities. As a result, capacitive effect is dominant over the frequency of 100 [kHz] at the water resistivity of 1,000 [$\Omega$ m]. On the other hand, the inductive characteristics appear at the low water resistivity. Consequently, dependence of grounding impedances on the frequency of injected current is strongly related to resistivity.

  • PDF

Frequency Dependence of Grounding Impedances of the Deeply-driven Ground Rods (심매설 접지전극의 접지임피던스의 주파수의존성)

  • Kim, Tae-Ki;Kang, Sung-Man;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.70-73
    • /
    • 2008
  • Grounding impedance depends on the frequency of current flowing into a grounding system. Especially, the lightning gives a broad frequency spectrum from low frequency up to 1 MHz. So the grounding impedance related to high frequency current like lightning should be measured with high frequency source. In this paper, we described the grounding impedances of deeply-driven ground rods of 10 ${\sim}$ 48 m long with respect to the frequency of injected currents and the feed point. For the experiments, we used the wideband power amplifier which can produce sinusoidal voltages with the frequency ranges of DC ${\sim}$ 250 MHz. As a result, the longer the ground rod is, the lower the ground resistance is. However the grounding impedance of deeply-driven ground rod in the range of higher frequency is significantly increased. As a consequence, it is important to evaluate the high frequency performance of grounding systems for lightning protection.

  • PDF

Analysis of the Potential Rises near Grounding Electrodes using Semisplere type scale Model (반구형 축소모델을 이용한 접지전극 주변의 전위상승 분석)

  • Lee, B.H.;Beak, Y.H.;Li, F.;Kim, K.B.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.259-262
    • /
    • 2008
  • This paper describes the ground surface potential profiles near the object to be grounded. The hemisphere water tank was used to simulate the. scale model. As a result, the ground surface potential near the ground electrode was considerably raised. In particular the ground surface potential at the just upper part of ground rod was higher than other part. The ground surface potential was lowered with increasing the buried depth of ground rod.

  • PDF

Electrical properties of 18kV ZnO surge arrester according to the variation of surrounding conditions (외부환경 변화에 따른 배전용 피뢰기의 전기적 특성)

  • Lee, Bok-Hee;Lee, Seung-Ju;Lee, Su-Bong;Jung, Dong-Sung;Shin, Hee-Kyung
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.289-292
    • /
    • 2008
  • This paper describes the electrical characteristics of the ZnO surge arrester according to the variation of surrounding conditions. To investigate the characteristics of degraded ZnO surge arrester, 8/20 [${\mu$s], 2.5 [kA] impulse currents were applied to the ZnO surge arrester to be test. To present the effect of the surrounding con야tions, the leakage currents of ZnO surge arrester were measured to the surrounding temperature and wet conditions. As a result, the increase of ambient temperature causes the increase of resistive leakage current of ZnO surge arrester. Also, in the wet test, the outside leakage current through the ZnO surge arrester housing is much larger than the intrinsic leakage current.

  • PDF

Transient impedance characteristics according to the injection position of deep-driven ground rods (심매설 접지전극의 전류인가위치에 따른 과도접지임피던스 특성)

  • Lee, Bok-Hee;Li, Feng;Lee, Su-Bong;Lee, Song-Zhu;Jeon, Byung-Wook;Eom, Ju-Hong;Cho, Sung-Chul;Lee, Tae-Hyung
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.297-300
    • /
    • 2008
  • This paper presents the behaviors of transient and conventional grounding impedances of a deep-driven ground rods associated with the injection point of lightning impulse currents. The transient impedance of deep-driven ground rods under lightning impulse currents were higher than the static ground resistance. The transient grounding impedances strongly depend on the injection point and size of grounding electrodes and the rising time of impulse current. Reduction of ground system inductance is an important factor to lightning surge protection.

  • PDF

The breakdown characteristics of $N_2$ gas with lightning impulse voltage in the non-uniform electrode (불평등전극계에서 뇌임펄스전압에 대한 $N_2$기체의 절연파괴 특성)

  • Lee, Bok-Hee;Lee, Feng;Joe, Jeong-Hyeon
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.301-304
    • /
    • 2008
  • This paper presents the experimental results on breakdown characteristics in $N_2$ gas under non-uniform electric fields caused by both the positive and negative lightning impulse voltages. $N_2$ gas have an advantage of eco-friendly and cost reduction, and safety aspects. In order to analyze the impulse pre-breakdown processes in $N_2$ gas, we carried out measurements and observations of the impulse breakdown voltages, pre-breakdown current and luminous signals. They were measured by a voltage divider, a shunt and a photo-multiplier tube, respectively. Additionally, the characteristics of discharge channels were observed by high speed cameras. The breakdown voltages in the positive polarity was lower than those in the negative polarity.

  • PDF

Analysis of Ionization Phenomena in Soils under Impulse Voltages (임펄스전압에 의한 토양이온화 현상의 분석)

  • Park, Geon-Hun;Kim, Hoe-Gu;Choi, Jong-Hyuk;Yang, Soon-Man;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.305-308
    • /
    • 2008
  • This paper presents characteristics of soil ionization when high currents such as lightning and switching surge currents are injected into a grounding rod. Soil ionization phenomena are investigated by using both voltage and current signals recorded by oscilloscope. As a result, a critical electric field intensity($E_C$) for ionization is decreased with reduction of grain size. The pre-ionization resistance($R_1$) and post-ionization resistance($R_2$) at the sand with fine grain size are getting lower with increasing current magnitude. Finally, the time to ionization($t_1$) and ionization current peak($t_2$) of fine grain size are significantly shorter than those of medium grain size.

  • PDF

Analysis of error factors of the Fall-of-potential test method in measurements of grounding impedance (전위강하법에 의한 접지임피던스 측정 시 오차요인 분석)

  • Jeon, Byung-Wook;Lee, Su-Bong;Jung, Dong-Cheol;Lee, Bok-Hee;Ahn, Chang-Hwan
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.313-316
    • /
    • 2008
  • This paper presents the error factors of Fall-of-potential test method used in measurements of the grounding-system impedance. This test methods inherently can introduce two possible errors in the measurements of grounding-system impedance: (1) ground mutual resistance due to current flow through ground from the ground electrode to the current probe, (2) ac mutual coupling between the current test lead and the potential test lead. The errors of ground mutual resistances and ac mutual coupling are expressed by the equation in calculating grounding impedance. These equations were calculated by Matlab that is commercial tool using mathematical calculation. The results of calculation were applied to correct grounding impedance.

  • PDF