Empirical evaluation of the heating performance by a heat pump system with surplus heat from a greenhouse (온실 태양잉여열을 이용한 히트펌프시스템의 난방 성능평가에 관한 실증 연구)

  • Jeon, Byung-Yong;Park, Youn-Cheol;Ko, Gwang-Soo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.41 no.1
    • /
    • pp.99-104
    • /
    • 2017
  • This study evaluated the heating performance of a hybrid heat pump system. The system was installed in a $100-m^2$ greenhouse to utilize surplus solar energy. A hybrid heat pump system was installed at Jocheon-ri, Jeju Island, for an empirical evaluation of the performance. The system consists of a heat storage tank and plate heat exchangers for several heat exchanges between the greenhouse and heat pump or storage tank. The system uses R410a as the working fluid and is controlled automatically by a defined set temperature of the greenhouse. This system incorporates two kinds of heat sources: outdoor air and a storage tank that collects heat from the topside of the greenhouse. The results showed that the heating capacity was 19.9 kW in the outdoor air source mode and 21.4 kW with direct heating from hot water in the thermal storage tank. These results are very similar to those of a previous study.

A Study on the Horizontal Ground Source Beat Pump Greenhouse Heating System with Thermal Storage Tank (축열조를 채용한 수평형 지열원 히트펌프 온실 난방 시스템에 관한 연구)

  • Park, Yong-Jung;Kim, Kyoung-Hoon
    • Journal of Energy Engineering
    • /
    • v.15 no.3 s.47
    • /
    • pp.194-201
    • /
    • 2006
  • Greenhouses should be heated during nights and cold days in order to fit growth conditions in greenhouses. Ground source heat pump (GSHP) systems are recognized to be outstanding heating and cooling systems. A horizontal GSHP system with thermal storage tank was installed in greenhouse and investigated the performance characteristics. The reasons for using thermal storage tank were discussed in detail. Thermal storage tank can provide heat for heating load that is larger than GSHP system heating capacity. The results of study showed that the heating coefficient of performance of the heat pump system was 2.69.

Performance Test of Heat Pump System for Low Temperature Treatment of Phalaenopsis (히트펌프를 이용한 호접란(팔레놉시스) 저온 처리 시스템의 성능 평가)

  • 유영선;장진택;김영중;이건중;윤진하
    • Proceedings of the Korean Society for Bio-Environment Control Conference
    • /
    • 1999.11a
    • /
    • pp.95-99
    • /
    • 1999
  • 자연에너지와 전기에너지를 조합하여 냉방과 난방을 수행할 수 있는 방법중의 하나로 히트펌프 이용기술이 있으며, 국내의 경우 히트펌프는 주로 냉방 또는 냉동을 목적으로 이용되고 있으나, 1980년 이후 전기가 풍부한 경제선진국을 중심으로 난방 또는 냉난방겸용의 히트펌프가 개발되어 주택, 빌딩, 온실 등의 공조시스템에 이용되고 있다. (중략)

  • PDF

Performance Improvement of an Air Source Heat Pump by Storage of Surplus Solar Energy in Greenhouse (온실 내 잉여 태양열을 이용한 공기열원 히트펌프 성능향상)

  • Kwon, Jin Kyung;Kang, Geum Chun;Moon, Jong Pil;Kang, Youn Ku;Kim, Chung Kil;Lee, Su Jang
    • Journal of Bio-Environment Control
    • /
    • v.22 no.4
    • /
    • pp.328-334
    • /
    • 2013
  • A greenhouse heating system to improve heat pump performance using inside and outside air of greenhouse as a heat source selectively and cut $CO_2$ enrichment costs by delay of greenhouse ventilation was developed. In this system, thermal storage modes divided into inside circulation mode using surplus solar energy and outside circulation mode using outside air heat. The thermal storage modes were designed to be switched mutually according to inside greenhouse temperature and six temperature values were input to control the heat pump operating, thermal storage mode switching and greenhouse heating automatically. Operating characteristics of this system were tested in a plastic greenhouse of non-ventilation condition. The results of test showed that the inside circulation mode began at about 11:00 and lasted for about 210 minutes and inside greenhouse temperature was maintained between $20{\sim}28^{\circ}C$ in spite of non-ventilation. System heating COP of the inside circulation mode in the daytime was 3.35, which was 36% and 25% higher than that of the outside circulation modes in the nighttime and daytime respectively.

Analysis of the Effect of Fog Cooling during Daytime and Heat Pump Cooling at Night on Greenhouse Environment and Planst in Summer (하절기 주간 포그 냉방과 야간 히트펌프 냉방이 온실 환경 및 작물에 미치는 영향 분석)

  • Lee, Taeseok;Kim, Jingu;Park, Seokho;Lee, Choungkeun
    • Journal of Bio-Environment Control
    • /
    • v.30 no.4
    • /
    • pp.328-334
    • /
    • 2021
  • This study was conducted to analyze the effect of fog cooling during daytime and heatpump cooling at night in greenhouses in summer. During daytime, the average temp. and RH of the control greenhouse which had shading screen were 32.1℃ and 59.4%. and the average temp. and RH of the test greenhouse which had fog cooling were 30.0℃ and 74.3%. At this time, the average outside temp. and RH were 31.4℃ and 57.7%. So, the temp. of the control was 0.7℃ higher than outside temp., but the temp. of the test was 1.4℃ lower than outside and 2.1℃ lower than control. The average RH was 74.3% in the test and 59.4% in control. The average temp. and RH of the control greenhouse which had natural ventilation at night were 25.2℃ and 85.1%, and the average temp. and RH of the test greenhouse which had heat pump cooling were 23.4℃, 82.4%. The average outside temp. and RH at night were 24.4℃ and 88.2%. The temp. of the control was 0.8℃ higher than outside temp., but the temp. of the test was 1.0℃ lower than outside and 1.8℃ lower than control. The average RH was 82.4% in test and 85.1% in control greenhouse. There was no significant difference between the plants growth eight weeks after planting. But after the cooling treatment, the values of stem diameter, plant height, chlorophyll in test were higher than control. The total yield was 81.3kg in test, 73.8kg in control, so yield of test was 10.2% higher than control. As a result of economic analysis, 142,166 won in profits occurred in control greenhouse, but 28,727 won in losses occurred in test greenhouse, indicating that cooling treatment was less economical.

Analysis on the transmittance of shading materials (차광재의 광 투과율 분석)

  • 이현우;이석건;김길동;이종원
    • Proceedings of the Korean Society for Bio-Environment Control Conference
    • /
    • 1999.11a
    • /
    • pp.241-244
    • /
    • 1999
  • 시설원예는 노지원예와 달리 인위적인 환경조절을 통하여 주년안정생산이 가능하여야 하고 단위면적당 생산성을 증대시키면서 품질향상을 극대화시키는 것이 생산의 목표이다. 따라서, 주년안정생산을 위하여 고온기에 작물생산이 가능하도록 시설내 고온환경을 조절해야할 것이다. 고온환경을 조절하기 위한 냉방방식에는 자연환기 및 팬을 이용한 온실내부의 공기를 치환하는 방법, 온실내ㆍ외부에 차광망을 설치하여 온실내로 유입되는 일사량의 일부를 차단하는 방법, 수분증발을 통하여 온실내부의 잠열을 빼앗는 증발냉각방식, 히트펌프나 에어컨을 이용한 기계적인 방법이 이용되고 있다. (중략)

  • PDF

Heat Exchanger Design of a Heat Pump System Using the Heated Effluent of Thermal Power Generation Plant as a Heat Source for Greenhouse Heating (화력발전소의 온배수를 열원으로 이용하는 시설원예 난방용 히트펌프 시스템의 열교환기 설계기준 설정)

  • Ryou, Young Sun;Kang, Youn Ku;Jang, Jae Kyung;Kim, Young Hwa;Kim, Jong Goo;Kang, Geum Chun
    • Journal of Bio-Environment Control
    • /
    • v.21 no.4
    • /
    • pp.372-378
    • /
    • 2012
  • This study was carried out in order to determine the optimum length of a roll type PE pipe heat exchanger employed in the water-to-water heat pump system using the waste heat of the heated effluent flowed out from thermal power generation plants as a heat source. And the heat pump system of 30 RT for an experimental test was designed and manufactured. And also PE pipes were employed to recover the waste heat from the heated effluent. The inside diameter of PE pipe heat exchanger was 20 mm, the thickness was 2 mm and the diameter of a roll was 1,000 mm. And from the results of this study, we found that the optimum length of PE pipe heat exchanger was 75 m per the heat pump capacity of 1.0 RT (3.51 kW) and then the heating COP of heat pump system was 3.8.